Chapter 4 Explanation of Functions<br />

(vi) 05 command: This command reads the trip history data from the inverter.<br />

- Transmission frame<br />

Frame format<br />

STX Station No. Command BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32<br />

Command Command to be transmitted 2 bytes 05<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

- Response frame<br />

Frame format<br />

STX Station No. Data BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32<br />

Data Data monitored at tripping 440 bytes See Note 9.<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

Note 11: The inverter stores the data (trip history) on the last six times of tripping, together with the total<br />

trip count (8 bytes).<br />

Total trip count Trip 1 data ・・・・・・ Trip 6 data<br />

Monitoring item Unit Magnification Data size Remarks<br />

Trip factor - - 8 bytes Factor code<br />

Inverter status A - - 8 bytes<br />

Inverter status B - - 8 bytes<br />

Inverter status C - - 8 bytes<br />

04 command<br />

See Note 7.<br />

Output frequency Hz ×10 8 bytes Decimal ASCII code<br />

Cumulative running time hour ×1 8 bytes Decimal ASCII code<br />

Output current A ×10 8 bytes Decimal ASCII code<br />

DC voltage V ×10 8 bytes Decimal ASCII code<br />

Cumulative power-on time hour ×1 8 bytes Decimal ASCII code<br />

↑High-order bytes Low-order bytes↓<br />