Chapter 4 Explanation of Functions<br />

(v) 04 command: This command reads the status of the inverter.<br />

- Transmission frame<br />

Frame format<br />

STX Station No. Command BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32<br />

Command Command to be transmitted 2 bytes 04<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

- Response frame<br />

Frame format<br />

STX Station No. Data BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32<br />

Data Data 8 bytes See Note 8.<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

Note 10: The data indicating the status of the inverter consists of the following three status elements (A, B,<br />

and C):<br />

Data<br />

Status A Status B Status C 00 (reserved)<br />

Inverter status A Inverter status B Inverter status C<br />

Code Status Code Status Code Status<br />

00 Initial status 00 Stopping 00 ---<br />

01 01 Running 01 Stopping<br />

02 Stopping 02 Tripping 02 Decelerating<br />

03 Running 03 Constant-speed operation<br />

04 Free-run stop (FRS) in progress 04 Accelerating<br />

05 Jogging (JG) in progress 05 Forward operation<br />

06 DC braking (DB) in progress 06 Reverse operation<br />

07 Retry in progress 07 Switching forward operation<br />

08 Tripping to reverse operation<br />

09 Undervoltage (UV) status 08 Switching reverse operation<br />

to forward operation<br />

09 Starting forward operation<br />

10 Starting reverse operation<br />

4 - 122