SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd. SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

hitachi.america.us
from hitachi.america.us More from this publisher
29.01.2015 Views

Chapter 4 Explanation of Functions The commands are described below. (i) 00 command: This command instructs the inverter to drive the motor (for forward or reverse rotation) or stop the motor. (To use this command, set "A002" to "03" [RS485].) - Transmission frame Frame format STX Station No. Command Data BCC CR Description Data size Setting STX Control code (Start of TeXt) 1 byte STX (0x02) Station No. Station number of control-target inverter 2 bytes 01 to 32, or FF (broadcast to all stations) Command Command to be transmitted 2 bytes 00 Data Data to be transmitted 1 byte See Note 1. BCC Block check code 2 bytes XOR of the items from "Station No." to "Data." See Item (3) of this section. CR Control code (Carriage Return) 1 byte CR (0x0D) Note 1: Data Description Remarks 0 Stop command 1 Forward rotation command 2 Reverse rotation command (Example) When sending a forward rotation command to the inverter with station No. 01: (STX) |01|00|1| (BCC) | (CR) Conversion into ASCII format 02|30 31|30 30|31|33 30|0D - Response frame Positive response: See Item (2)-(i) of this section. Negative response: See Item (2)-(ii) of this section. (ii) 01 command: This command sets the inverter output frequency. (To use this command, set "A001" to "03" [RS485].) - Transmission frame Frame format STX Station No. Command Data BCC CR Description Data size Setting STX Control code (Start of TeXt) 1 byte STX (0x02) Station No. Station number of control-target inverter 2 bytes 01 to 32, or FF (broadcast to all stations) Command Command to be transmitted 2 bytes 01 Data Data to be sent (decimal ASCII code) 6 bytes See Note 2. BCC Block check code 2 bytes XOR of the items from "Station No." to "Data." See Item (3) of this section. CR Control code (Carriage Return) 1 byte CR (0x0D) Note 2: For example, to set the output frequency of the inverter with station No. 01 to 5 Hz, the data is as follows: (STX) |01|01|000500| (BCC) | (CR) Conversion into ASCII format 02|30 31|30 31|30 30 30 35 30 30|30 35|0D Note 3: The data indicates a value 100 times as large as the actual frequency value to be set. (Example) 5 (Hz) → 500 → 000500 Conversion into ASCII format 30 30 30 35 30 30 Note 4: When using the data as the feedback data for PID control, set the most-significant byte to "1". (Example) 5 (%) → 500 → 100500 Conversion into ASCII format 31 30 30 35 30 30 - Response frame Positive response: See Item (2)-(i) of this section. Negative response: See Item (2)-(ii) of this section. 4 - 118

Chapter 4 Explanation of Functions (iii) 02, 12 command: This command turns the specified intelligent input terminals on or off. - Transmission frame Frame format STX Station No. Command Data BCC CR Description Data size Setting STX Control code (Start of TeXt) 1 byte STX (0x02) Station No. Station number of control-target inverter 2 bytes 01 to 32, or FF (broadcast to all stations) Command Command to be transmitted 2 bytes 02 Data Data to be transmitted 16 bytes See Note 5. BCC Block check code 2 bytes XOR of the items from "Station No." to "Data." See Item (3) of this section. CR Control code (Carriage Return) 1 byte CR (0x0D) Note 5: The table below lists the functions of the intelligent input terminals and corresponding hexadecimal data. (For details, see the explanation of the intelligent input terminal functions.) Data Description (hexadecimal) 0000000000000001 FW: Forward rotation 0000000000000002 RV: Reverse rotation 0000000000000004 CF1: Multispeed 1 setting 0000000000000008 CF2: Multispeed 2 setting 0000000000000010 CF3: Multispeed 3 setting 0000000000000020 CF4: Multispeed 4 setting 0000000000000040 JG: Jogging 0000000000000080 DB: External DC braking 0000000000000100 SET: Set 2nd motor data 0000000000000200 2CH: 2-stage acceleration/deceleration 0000000000000400 - 0000000000000800 FRS: Free-run stop 0000000000001000 EXT: External trip 0000000000002000 USP: Unattended start protection 0000000000004000 CS: Commercial power source enable 0000000000008000 SFT: Software lock 0000000000010000 AT: Analog input voltage/current select 0000000000020000 SET3: 3rd motor control 0000000000040000 RS: Reset 0000000000080000 - 0000000000100000 STA: Starting by 3-wire input 0000000000200000 STP: Stopping by 3-wire input 0000000000400000 F/R: Forward/reverse switching by 3-wire input 0000000000800000 PID: Enabling/disabling PID 0000000001000000 PIDC: PID reset 0000000002000000 - 0000000004000000 CAS: Control gain setting 0000000008000000 UP: Remote control UP function 0000000010000000 DWN: Remote control DOWN function 0000000020000000 DWN: Remote control data clearing 0000000040000000 - 0000000080000000 OPE: Forcible operation Data (hexadecimal) 0000000100000000 0000000200000000 0000000400000000 0000000800000000 0000001000000000 0000002000000000 0000004000000000 0000008000000000 0000010000000000 0000020000000000 0000040000000000 0000080000000000 0000100000000000 0000200000000000 0000400000000000 0000800000000000 0001000000000000 0002000000000000 0004000000000000 0008000000000000 0010000000000000 0020000000000000 0040000000000000 0080000000000000 0100000000000000 0200000000000000 0400000000000000 0800000000000000 1000000000000000 2000000000000000 4000000000000000 8000000000000000 Description SF1: Multispeed bit 1 SF2: Multispeed bit 2 SF3: Multispeed bit 3 SF4: Multispeed bit 4 SF5: Multispeed bit 5 SF6: Multispeed bit 6 SF7: Multispeed bit 7 OLR: Overload restriction selection TL: Enabling /disabling torque limitation TRQ1: Torque limit selection bit 1 TRQ2: Torque limit selection bit 2 PPI: P/PI mode selection BOK: Braking confirmation ORT: Orientation LAC: LAD cancellation PCLR: Clearance of position deviation STAT: Pulse train position command input enable - ADD: Trigger for frequency addition F-TM: Forcible-terminal operation ATR: Permission of torque command input KHC: Cumulative power clearance SON: Servo On FOC: Forcing MI1: General-purpose input 1 MI2: General-purpose input 2 MI3: General-purpose input 3 MI4: General-purpose input 4 MI5: General-purpose input 5 MI6: General-purpose input 6 MI7: General-purpose input 7 MI8: General-purpose input 8 4 - 119

Chapter 4 Explanation of Functions<br />

(iii) 02, 12 command: This command turns the specified intelligent input terminals on or off.<br />

- Transmission frame<br />

Frame format<br />

STX Station No. Command Data BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32, or FF (broadcast to all stations)<br />

Command Command to be transmitted 2 bytes 02<br />

Data Data to be transmitted 16 bytes See Note 5.<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

Note 5: The table below lists the functions of the intelligent input terminals and corresponding hexadecimal<br />

data. (For details, see the explanation of the intelligent input terminal functions.)<br />

Data<br />

Description<br />

(hexadecimal)<br />

0000000000000001 FW: Forward rotation<br />

0000000000000002 RV: Reverse rotation<br />

0000000000000004 CF1: Multispeed 1 setting<br />

0000000000000008 CF2: Multispeed 2 setting<br />

0000000000000010 CF3: Multispeed 3 setting<br />

0000000000000020 CF4: Multispeed 4 setting<br />

0000000000000040 JG: Jogging<br />

0000000000000080 DB: External DC braking<br />

0000000000000100 SET: Set 2nd motor data<br />

0000000000000200 2CH: 2-stage acceleration/deceleration<br />

0000000000000400 -<br />

0000000000000800 FRS: Free-run stop<br />

0000000000001000 EXT: External trip<br />

0000000000002000 USP: Unattended start protection<br />

0000000000004000 CS: Commercial power source enable<br />

0000000000008000 SFT: Software lock<br />

0000000000010000 AT: Analog input voltage/current select<br />

0000000000020000 SET3: 3rd motor control<br />

0000000000040000 RS: Reset<br />

0000000000080000 -<br />

0000000000100000 STA: Starting by 3-wire input<br />

0000000000200000 STP: Stopping by 3-wire input<br />

0000000000400000 F/R: Forward/reverse switching by 3-wire input<br />

0000000000800000 PID: Enabling/disabling PID<br />

0000000001000000 PIDC: PID reset<br />

0000000002000000 -<br />

0000000004000000 CAS: Control gain setting<br />

0000000008000000 UP: Remote control UP function<br />

0000000010000000 DWN: Remote control DOWN function<br />

0000000020000000 DWN: Remote control data clearing<br />

0000000040000000 -<br />

0000000080000000 OPE: Forcible operation<br />

Data<br />

(hexadecimal)<br />

0000000100000000<br />

0000000200000000<br />

0000000400000000<br />

0000000800000000<br />

0000001000000000<br />

0000002000000000<br />

0000004000000000<br />

0000008000000000<br />

0000010000000000<br />

0000020000000000<br />

0000040000000000<br />

0000080000000000<br />

0000100000000000<br />

0000200000000000<br />

0000400000000000<br />

0000800000000000<br />

0001000000000000<br />

0002000000000000<br />

0004000000000000<br />

0008000000000000<br />

0010000000000000<br />

0020000000000000<br />

0040000000000000<br />

0080000000000000<br />

0100000000000000<br />

0200000000000000<br />

0400000000000000<br />

0800000000000000<br />

1000000000000000<br />

2000000000000000<br />

4000000000000000<br />

8000000000000000<br />

Description<br />

SF1: Multispeed bit 1<br />

SF2: Multispeed bit 2<br />

SF3: Multispeed bit 3<br />

SF4: Multispeed bit 4<br />

SF5: Multispeed bit 5<br />

SF6: Multispeed bit 6<br />

SF7: Multispeed bit 7<br />

OLR: Overload restriction selection<br />

TL: Enabling /disabling torque limitation<br />

TRQ1: Torque limit selection bit 1<br />

TRQ2: Torque limit selection bit 2<br />

PPI: P/PI mode selection<br />

BOK: Braking confirmation<br />

ORT: Orientation<br />

LAC: LAD cancellation<br />

PCLR: Clearance of position deviation<br />

STAT: Pulse train position command input enable<br />

-<br />

ADD: Trigger for frequency addition<br />

F-TM: Forcible-terminal operation<br />

ATR: Permission of torque command input<br />

KHC: Cumulative power clearance<br />

SON: Servo On<br />

FOC: Forcing<br />

MI1: General-purpose input 1<br />

MI2: General-purpose input 2<br />

MI3: General-purpose input 3<br />

MI4: General-purpose input 4<br />

MI5: General-purpose input 5<br />

MI6: General-purpose input 6<br />

MI7: General-purpose input 7<br />

MI8: General-purpose input 8<br />

4 - 119

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!