Chapter 4 Explanation of Functions<br />

The commands are described below.<br />

(i) 00 command: This command instructs the inverter to drive the motor (for forward or reverse rotation)<br />

or stop the motor. (To use this command, set "A002" to "03" [RS485].)<br />

- Transmission frame<br />

Frame format<br />

STX Station No. Command Data BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32, or FF (broadcast to all stations)<br />

Command Command to be transmitted 2 bytes 00<br />

Data Data to be transmitted 1 byte See Note 1.<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

Note 1:<br />

Data Description Remarks<br />

0 Stop command<br />

1 Forward rotation command<br />

2 Reverse rotation command<br />

(Example) When sending a forward rotation command to the inverter with station No. 01:<br />

(STX) |01|00|1| (BCC) | (CR) Conversion into ASCII format 02|30 31|30 30|31|33 30|0D<br />

- Response frame<br />

Positive response: See Item (2)-(i) of this section.<br />

Negative response: See Item (2)-(ii) of this section.<br />

(ii) 01 command: This command sets the inverter output frequency. (To use this command, set "A001" to<br />

"03" [RS485].)<br />

- Transmission frame<br />

Frame format<br />

STX Station No. Command Data BCC CR<br />

Description Data size Setting<br />

STX Control code (Start of TeXt) 1 byte STX (0x02)<br />

Station No.<br />

Station number of control-target<br />

inverter<br />

2 bytes 01 to 32, or FF (broadcast to all stations)<br />

Command Command to be transmitted 2 bytes 01<br />

Data<br />

Data to be sent (decimal ASCII<br />

code)<br />

6 bytes See Note 2.<br />

BCC Block check code 2 bytes<br />

XOR of the items from "Station No." to "Data."<br />

See Item (3) of this section.<br />

CR Control code (Carriage Return) 1 byte CR (0x0D)<br />

Note 2: For example, to set the output frequency of the inverter with station No. 01 to 5 Hz, the data is as<br />

follows:<br />

(STX) |01|01|000500| (BCC) | (CR)<br />

Conversion into ASCII format<br />

02|30 31|30 31|30 30 30 35 30<br />

30|30 35|0D<br />

Note 3: The data indicates a value 100 times as large as the actual frequency value to be set.<br />

(Example) 5 (Hz) → 500 → 000500<br />

Conversion into ASCII format<br />

30 30 30 35 30 30<br />

Note 4: When using the data as the feedback data for PID control, set the most-significant byte to "1".<br />

(Example) 5 (%) → 500 → 100500<br />

Conversion into ASCII format<br />

31 30 30 35 30 30<br />

- Response frame<br />

Positive response: See Item (2)-(i) of this section.<br />

Negative response: See Item (2)-(ii) of this section.<br />

4 - 118