Chapter 4 Explanation of Functions<br />

Connection<br />

As illustrated below, connect the inverters in parallel to the external control system, and connect the<br />

RP and SN terminals with a jumper on the inverter at the end of the network. (Similarly jumper the RP<br />

and SN terminals when only one inverter is connected to the external control system for RS485<br />

communication.) Connecting the RP and SN terminals enables the terminating resistor in the control<br />

circuit terminal block board of the inverter, which suppresses signal reflections.<br />

External control<br />

system<br />

…<br />

SP SN RP SN<br />

SP SN RP SN<br />

SP SN RP SN<br />

(2) Required settings<br />

The following table lists the inverter settings required for the RS485 communication:<br />

Communication speed<br />

selection<br />

Item Function code Data or range of data Description<br />

02 Loopback test<br />

C071<br />

Node allocation C072 1. to 32.<br />

Communication data length<br />

selection<br />

Communication parity<br />

selection<br />

Communication stop bit<br />

selection<br />

Selection of operation after<br />

communication error<br />

Communication trip limit time<br />

setting<br />

Communication wait time<br />

Communication mode<br />

selection<br />

C073<br />

C074<br />

C075<br />

C076<br />

C077<br />

C078<br />

C079<br />

03 2,400 bps<br />

04 4,800 bps<br />

05 9,600 bps<br />

06 19,200 bps<br />

Assignment of a station number to the<br />

inverter<br />

(Set this item when your inverter is<br />

connected together with other(s) to a<br />

control system.)<br />

7 7 bits<br />

8 8 bits<br />

00 No parity<br />

01 Even parity<br />

02 Odd parity<br />

1 1 bit<br />

2 2 bits<br />

00 Tripping<br />

01<br />

Tripping after decelerating and stopping<br />

the motor<br />

02 Ignoring the errors<br />

03 Stopping the motor after free-running<br />

04 Decelerating and stopping the motor<br />

0.00 to 99.99 (s)<br />

Limit length of time to determine<br />

communication train disconnection<br />

0. to 1000. (ms)<br />

Time to wait until the inverter returns a<br />

response<br />

00 ASCII mode<br />

01 Modbus-RTU mode<br />

4 - 115