Chapter 4 Explanation of Functions<br />

4.3.21 Pulse train frequency input<br />

The pulse train frequency input function allows you to use the<br />

pulse train input via the SAP or SAN terminal as a frequency<br />

command or PID feedback data in each control mode. (You<br />

can use this function in every control mode.)<br />

Specify the input frequency corresponding to the allowable<br />

maximum frequency as the pulse train frequency scale<br />

(P055).<br />

Related code<br />

P055: Pulse-string frequency scale<br />

P056: Time constant of pulse-string frequency filter<br />

P057: Pulse-string frequency bias<br />

P058: Pulse-string frequency limit<br />

A002: Frequency source setting<br />

A076: PV source setting<br />

A141: Operation-target frequency selection 1<br />

A142: Operation-target frequency selection 2<br />

You cannot use the start/end frequency setting function for external analog input together with this function.<br />

To limit the input frequency, specify the desired values for the pulse train frequency bias (P057) and pulse<br />

train frequency limit (P058).<br />

Item Function code Data or range of data Description<br />

Pulse train frequency scale P055 1.0 to 50.0 (kHz)<br />

Specification of the input frequency<br />

corresponding to the maximum<br />

allowable frequency<br />

Time constant of pulse train<br />

Setting of the filter time constant for<br />

P056 0.01 to 2.00 (s)<br />

frequency filter<br />

the pulse train input<br />

Pulse train frequency bias P057 -100. to +100. (%)<br />

Pulse train frequency limit P058 0. to 100. (%)<br />

Frequency source setting A001 06<br />

PV source setting A076 03<br />

Operation-target frequency<br />

Settings for the frequency input as a<br />

A141 05<br />

selection 1<br />

pulse train<br />

Operation-target frequency<br />

selection 2<br />

A142 05<br />

Bias limitation<br />

Limit<br />

Frequency<br />

measurement<br />

Hz % % Hz<br />

1<br />

÷ 1+sT<br />

Bias<br />

×<br />

Frequency<br />

command<br />

Frequency scale<br />

(1.0 to 50.0 kHz)<br />

Primary delay filter<br />

Maximum<br />

frequency (F004)<br />

Block diagram for pulse train frequency input<br />

4 - 113