Chapter 4 Explanation of Functions<br />

<br />

Master inverter<br />

Slave inverter<br />

AP,BP<br />

AN,BN<br />

EG5<br />

EAP,EBP<br />

EAN,EBN<br />

SAP,SBP<br />

SAN,SBN<br />

EG5<br />

EAP,EBP<br />

EAN,EBN<br />

Main motor<br />

M<br />

Sub-motor<br />

M<br />

EC<br />

EC<br />

On the inverter (master inverter) for the main motor, specify either the speed control (ASR:P012=00) or<br />

pulse train position control mode (APR:P012=01).<br />

On the inverter (slave inverter) for the sub-motor, specify the pulse train position control mode<br />

(APR:P012=01). And set the frequency source setting(A001) selection to the pulse row input”06”. Please<br />

set the pulse train position command input enable signal(STAT) to an unused input terminal. Afterwards,<br />

put the intelligent input terminal into the state of turning on.<br />

<br />

- Main motor: Encoder pulse-per-revolution (PPR) setting = 1024 (pulses)<br />

- Sub-motor: Encoder pulse-per-revolution (PPR) setting = 3000 (pulses)<br />

- Ratio of main motor speed to sub-motor speed: 2:1<br />

To operate the motors under the above conditions, adjust the parameters on the slave inverter as follows:<br />

Pulse train mode setting (P013): 00 (90º-phase-shift pulse train)<br />

Electronic gear set position selection (P019): 01 (REF)<br />

Electronic gear ratio numerator setting (P020): 3000<br />

Electronic gear ratio denominator setting (P021): 1024 x 2 = 2048<br />

The table below lists the examples of the ratio of main motor speed to sub-motor speed according to the<br />

settings of "P019" to "P021" (on the assumption that the encoder pulse-per-revolution (PPR) setting of<br />

"1024" should be set on both inverters).<br />

Electronic gear set position<br />

selection (P019)<br />

REF<br />

(Position<br />

command side)<br />

REF<br />

(Position<br />

command side)<br />

4 - 103<br />

FB<br />

(Position feedback<br />

side)<br />

FB<br />

(Position feedback<br />

side)<br />

Electronic gear ratio numerator<br />

setting (P020)<br />

1024 2048 1024 2048<br />

Electronic gear ratio<br />

denominator setting (P021)<br />

2048 1024 2048 1024<br />

Sub-motor speed/main motor<br />

speed<br />

1/2 2 2 1/2<br />

-Please confirm the instruction value in which the rotational speed corresponds between while the<br />

mastering inverter is driven is displayed in the output frequency setting(F001) on the slave side when the<br />

driving instruction is put, and the slave side doesn't drive.<br />

-Please raise and adjust the feed-forward gain setting(P022) or the positional loop gain setting(P023)<br />

when the response of the follow on the slave side is late. (Refer to Chapter 4.3.7 )