SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.
SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.
SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Chapter 4 Explanation of Functions<br />
4.2.104 Easy sequence function<br />
- You can create a user program with EzSQ (the<br />
programming software dedicated to the <strong>SJ700</strong>) on a<br />
personal computer, and download the program to your<br />
Related code<br />
A017: Easy sequence function selection<br />
P100 to P131: Easy sequence user parameters<br />
<strong>SJ700</strong> series inverter. Thus, you can convert your inverter to a special machine on which user-defined<br />
functions are installed. Please refer to programming instruction of EzSQ user manual.<br />
- The easy sequence function does not provide an operation mode exclusive for program-based operation.<br />
Therefore, you can arbitrarily select the devices to input frequency and operation commands to the<br />
inverter. On the other hand, the FW terminal must be used exclusively to run the program. If the control<br />
circuit terminal block is specified as the device to input operation commands, the FW terminal must be<br />
turned on by an instruction in the program.<br />
- The intelligent input/output terminals of the inverter include general-purpose input/output terminals<br />
dedicated to the easy sequence function. Those terminals can be used to freely write and read data to<br />
and from the inverter with instructions in the program.<br />
- You can assign the parameters (e.g., frequency setting and acceleration/deceleration time parameters)<br />
that require adjustments on the actual inverter to user parameters (P130 to P131). If you do so, you can<br />
readjust the parameter data by using the digital operator without having to connect your personal<br />
computer to the inverter.<br />
- If you specify a program number in each program you created, you will be able to check the program<br />
number on the monitor of the digital operator.<br />
- Each user program is compiled, and stored as an intermediate code in the internal EEPROM of the<br />
inverter. (Data can be stored in EEPROM.)<br />
- Even if the user data is initialized via the digital operator, downloaded programs and user parameters<br />
(P100 to P131) are not cleared.<br />
- You cannot copy the downloaded program by an operation from a remote operator. You cannot copy the<br />
user parameter codes "P***", either. If necessary, download the user parameter codes from your<br />
personal computer.<br />
Personal computer<br />
(Windows system)<br />
Programming/<br />
debugging support<br />
software<br />
EzSQ<br />
Inverter<br />
Special cable<br />
<strong>SJ700</strong><br />
Compilation<br />
Download<br />
User program<br />
Upload<br />
4 - 96