29.01.2015 Views

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Chapter 4 Explanation of Functions<br />

4.2.96 Sensorless vector control<br />

The sensorless vector control function estimates and controls<br />

the motor speed and output torque on the basis of the inverter<br />

output voltage and output current and the motor constants set<br />

on the inverter. This function enables the inverter to accurately<br />

operate the motor with a high starting torque, even at a low<br />

frequency (0.3 Hz or more).<br />

To use this function, specify "03" for the V/F characteristic curve<br />

selection (A044/A244).<br />

Before using this function, be sure to make optimum constant<br />

settings for the motor with reference to Section 4.2.91, "Motor<br />

constant selection."<br />

When using this function, observe the following precautions:<br />

1) If you use the inverter to drive a motor of which the capacity<br />

is two classes lower than the maximum applicable capacity<br />

of the inverter, you may not be able to obtain adequate<br />

motor characteristics.<br />

2) If you cannot obtain the desired characteristics from the motor driven under the sensorless vector<br />

control, readjust the motor constants according to the symptom, as described in the table below.<br />

Operation<br />

status<br />

Symptom Adjustment method Adjustment item<br />

Powering<br />

Momentary speed Increase the motor constant R2 step by step from the<br />

H021/H221/H031<br />

variation is negative. set value up to 1.2 times as high as the set value.<br />

Momentary speed Reduce the motor constant R2 step by step from the set<br />

H021/H221/H031<br />

variation is positive. value down to 0.8 times as high as the set value.<br />

Regenerating<br />

Increase the motor constant R1 step by step from the<br />

Torque is insufficient at<br />

H020/H220/H030<br />

set value up to 1.2 times as high as the set value.<br />

low frequencies<br />

Increase the motor constant Io step by step from the set<br />

(several Hz)<br />

H023/H223/H033<br />

value up to 1.2 times as high as the set value.<br />

Starting<br />

The motor generates an<br />

Reduce the motor constant J from the set value.<br />

impact when it starts.<br />

H024/H224/H034<br />

Decelerating<br />

The motor runs Reduce the speed response setting.<br />

H005/H205<br />

unsteadily. Reduce the motor constant J from the set value. H024/H224/H034<br />

Torque is insufficient<br />

Torque-limited during torque-limited Reduce the overload restriction level to lower than the<br />

operation operation at a low torque limiter level.<br />

b021, b041 to b044<br />

frequency.<br />

Low-frequency Motor rotation is<br />

operation inconsistent.<br />

Increase the motor constant J from the set value. H024/H224/H034<br />

starting<br />

Motor runs backwards<br />

for short moment.<br />

Set 01 (enable) on reverse run protection function<br />

(b046)<br />

Related code<br />

A001: Frequency source setting<br />

A044/A244: V/F characteristic curve selection,<br />

1st/2nd motors<br />

F001: Output frequency setting<br />

b040: Torque limit selection<br />

b041 to b044: Torque limits (1) to (4)<br />

H002/H202: Motor data selection, 1st/2nd motors<br />

H003/H203: Motor capacity, 1st/2nd motors<br />

H004/H204: Motor poles setting, 1st/2nd motors<br />

H005/H205: Motor speed constant, 1st/2nd<br />

motors<br />

H020/H220: Motor constant R1, 1st/2nd motors<br />

H021/H221: Motor constant R2, 1st/2nd motors<br />

H022/H222: Motor constant L, 1st/2nd motors<br />

H023/H223: Motor constant Io, 1st/2nd motors<br />

H024/H224: Motor constant J, 1st/2nd motors<br />

H050/H250: PI proportional gain, 1st/2nd motors<br />

H051/H251: PI integral gain, 1st/2nd motors<br />

H052/H252: P proportional gain setting, 1st/2nd<br />

motors<br />

Note 1: Always set the carrier frequency (b083) to 2.1 kHz or more. If the carrier frequency is less than 2.1<br />

kHz, the inverter cannot operate the motor normally.<br />

Note 2: When driving a motor of which the capacity is one class lower than the inverter, adjust the torque<br />

limit (b041 to b044) so that the value "α" calculated by the expression below does not exceed<br />

200%. Otherwise, the motor may be burnt out.<br />

α = "torque limit" x (inverter capacity)/(motor capacity)<br />

(Example) When the inverter capacity is 0.75 kW and the motor capacity is 0.4 kW, the torque<br />

limit value is calculated as follows, based on the assumption that the value "α" should<br />

be 200%:<br />

Torque limit (b041 to b044) = α x (motor capacity)/(inverter capacity) = 200% x (0.4<br />

kW)/(0.75 kW) = 106%<br />

b046<br />

4 - 90

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!