Chapter 4 Explanation of Functions<br />

4.2.95 Motor constants selection<br />

Adjust the motor constant settings to the motor to be driven by the inverter.<br />

When using a single inverter to drive multiple motors in the control mode based on VC, VP, or free V/f<br />

characteristic, calculate the total capacity of the motors, and specify a value close to the total capacity for<br />

the motor capacity selection (H003/H203).<br />

When the automatic torque boost function is used, the motor constant settings that do not match the motor<br />

may result in a reduced motor or unstable motor operation.<br />

You can select the motor constants that are used when the control mode is the sensorless vector control,<br />

0Hz-range sensorless vector control, or vector control with sensor from the following three types:<br />

(1) Motor constants of <strong>Hitachi</strong> general-purpose motor<br />

(2) Motor constants tuned by offline auto-tuning<br />

(3) Arbitrarily set motor constants<br />

The motor constants set for the 1st motor control apply to the 3rd motor control.<br />

Item Function code Data or range of data Description<br />

00 Constant torque characteristic (VC)<br />

V/F characteristic<br />

curve selection<br />

Motor data<br />

selection<br />

Motor capacity<br />

A044/A244/<br />

A344<br />

H002/H202<br />

H003/H203<br />

01<br />

Reduced-torque characteristic (1.7th power<br />

of VP)<br />

02 (*1) Free V/f characteristic<br />

03 (*1) Sensorless vector control (SLV)<br />

04 (*1) 0 Hz-range sensorless vector control<br />

05 (*1) Vector control with sensor (V2)<br />

00 <strong>Hitachi</strong> general-purpose motor constants<br />

01 Motor constants tuned by auto-tuning<br />

02 Motor constants tuned by online auto-tuning<br />

0.2 to 75.0 (kW)<br />

<br />

Note)applied for 75 to 150kW<br />

Motor poles setting H004/H204 2, 4, 6, 8, or 10 (poles)<br />

Motor constant R1 H020/H220 0.000 to 65.53 (Ω) (*2)<br />

Motor constant R2 H021/H221 0.000 to 65.53 (kgm 2 ) (*2)<br />

Motor constant L H022/H222 0.00 to 655.3 (mH)<br />

Motor constant Io H023/H223 0.00 to 655.3 (A) (*2)<br />

Motor constant J H024/H224 0.001 to 9999. (kgm 2 ) (*3)<br />

Auto constant R1 H030/H230 0.000 to 65.53 (Ω)<br />

Auto constant R2 H031/H231 0.000 to 65.53 (Ω)<br />

Auto constant L H032/H232 0.00 to 655.3 (mH)<br />

Auto constant Io H033/H233 0.00 to 655.3 (A)<br />

Auto constant J H034/H234 0.001 to 9999. (kgm 2 )<br />

*1 Any of "00" to "05" can be selected for the 1st motor (A044). Only "00" to "04" can be selected for the<br />

2nd motor (A244). Only "00" or "01" can be selected for the 3rd motor (A344).<br />

*2 If you copy the data from a J300 series inverter to your <strong>SJ700</strong> series inverter, set constants R1, R2,<br />

and Io as follows:<br />

R1 <strong>SJ700</strong> = R1 J300 /1.125 R2 <strong>SJ700</strong> = R2 J300 /1.2 Io = V/{272 x (2 x M J300 + L J300 ) x 10 -3 }<br />

V: Voltage class (200 or 400 V)<br />

*3 Convert the moment of inertia (J) into the motor shaft data. When the value of J is large, the motor<br />

response is fast, and the motor torque increases quickly. When the value of J is small, the motor<br />

response is slow, and the motor torque increases slowly. To control the response, set the value of J,<br />

and then adjust the speed response (H005/H205).<br />

*4 In the modes of sensorless vector control, 0Hz-range sensorless vector control and vector control with<br />

sensor, inverter may output reverse to given operation command in the low speed range as a nature of<br />

those control. In case there is a specific inconvenience for example reverse rotation damage the<br />

machine, enable the reverse run protection (b046). (see 4.2.101: Reverse run protection function)<br />

Arbitrary setting of motor constants<br />

For the arbitrary setting of the motor constants, the function codes requiring settings vary depending on<br />

the settings of the 1st/2nd control function and the motor constant selection.<br />

- When the 1st/2nd control function is enabled and "00" is specified for the motor constant selection →<br />

Directly input the desired values for "H020" to "H024".<br />

- When the 1st/2nd control function is enabled and "01" or "02" is specified for the motor constant<br />

selection → Directly input the desired values for "H030" to "H034".<br />

When the offline auto-tuning has not been performed, the constants (<strong>Hitachi</strong> general-purpose motor<br />

constants) of the motors in the same capacity class as the inverter have been set for "H030/H230" to<br />

"H034/H234".<br />

4 - 89