Chapter 4 Explanation of Functions<br />
4.2.92 Offline auto-tuning function<br />
The offline auto-tuning function allows you to make the inverter<br />
automatically measure and set the motor constants that are<br />
required for the sensorless vector control, 0Hz-range sensorless<br />
vector control, and vector control with sensor.<br />
When using the inverter to perform the sensorless vector control,<br />
0Hz-range sensorless vector control, and vector control with sensor<br />
for a motor of which the motor constants are unknown, measure the<br />
motor constants with the offline tuning function.<br />
When "00" (<strong>Hitachi</strong> general-purpose motor data) is specified for the<br />
motor constant selection (H002/H202), the motor constants of<br />
<strong>Hitachi</strong>'s general-purpose motors are set as defaults. When you drive a <strong>Hitachi</strong>'s general-purpose motor<br />
with the inverter, you can usually obtain the desired motor characteristics without problems. (If you cannot<br />
obtain the desired characteristics, adjust the motor constant settings as described in Section 4.2.92 or<br />
4.2.93.)<br />
If you intend to use the online tuning function described later, be sure to perform offline auto-tuning<br />
beforehand.<br />
The offline auto-tuning function applies only to the 1st motor and 2nd motor controls. Do not apply this<br />
function to the 3rd motor control.<br />
The motor constant data corresponding to the date of one phase of γ connection at 50 Hz.<br />
Item Function code Data or range of data Description<br />
00 Disabling the auto-tuning<br />
Auto-tuning Setting H001<br />
01<br />
Enabling the auto-tuning (without<br />
motor rotation)<br />
02<br />
Enabling the auto-tuning (with motor<br />
rotation)<br />
00 <strong>Hitachi</strong> general-purpose motor data<br />
01 Automatically tuned data<br />
Motor data selection H002/H202<br />
Automatically tuned data (online<br />
02<br />
auto-tuning enabled)<br />
Motor capacity H003/H203 0.2 to 75.0 (kW) Note):applied for 75 to 150kW<br />
Motor poles setting H004/H204 2, 4, 6, 8, or 10 (poles)<br />
Auto constant R1 H030/H230 0.000 to 65.53 (Ω)<br />
Auto constant R2 H031/H231 0.000 to 65.53 kgm 2<br />
Auto constant L H032/H232 0.00 to 655.3 (mH)<br />
Auto constant Io H033/H233 0.00 to 655.3 (A)<br />
Auto constant J H034/H234 0.001 to 9999. (kgm 2 )<br />
Base frequency<br />
30 to maximum frequency setting<br />
A003/A203<br />
setting<br />
(Hz)<br />
DC braking enable A051<br />
00 Disabling DC braking<br />
01 Enabling DC braking<br />
AVR voltage select A082<br />
200, 215, 220, 230, or 240<br />
Selectable only for 200 V class<br />
models<br />
380, 400, 415, 440, 460, or 480<br />
Selectable only for 400 V class<br />
models<br />
When using this function, follow the instructions below.<br />
1) Adjust the settings of base frequency (A003) and AVR voltage select (A082) to the motor specifications. When motor<br />
voltage is other than the altanatives, set as ”motor voltage (A082) “ * ”outputr voltage gain (A045) “ = “motor rated<br />
voltage”<br />
2) This function can properly apply to only the motors in the maximum applicable capacity class of your inverter or one<br />
class lower than the capacity class of your inverter. If this function is used for motors with other capacities, correct<br />
constant data may not be obtained. (In such cases, the auto-tuning operation may not be completed. If the<br />
auto-tuning operation is not completed, press the STOP/RESET key. The operation will end with an error code<br />
displayed.)<br />
3) If "01" (enabling) is specified for the DC braking enable (A051), motor constants cannot be measured by offline<br />
auto-tuning. Specify "00" (disabling) for the DC braking enable. (The default setting is "00".)<br />
4) If "02" (auto-tuning with motor rotation) is specified for the Auto-tuning Setting (H001), confirm or observe the<br />
following:<br />
a) No problem occurs when the motor rotates at a speed close to 80% of the base frequency.<br />
b) The motor is not driven by any other external power source.<br />
4 - 86<br />
Related code<br />
H001: Auto-tuning Setting<br />
H002/H202: Motor data selection, 1st motor<br />
H003/H203: Motor capacity, 1st motor<br />
H004/H204: Motor poles setting, 1st motor<br />
H030/H230: Auto constant R1, 1 st /2 nd motor<br />
H031/H231: Auto constant R2, 1 st /2 nd motor<br />
H032/H232: Auto constant L, 1 st /2 nd motor<br />
H033/H233: Auto constant Io, 1 st /2 nd motor<br />
H034/H234: Auto constant J, 1 st /2 nd motor<br />
A003/A203: Base frequency setting<br />
A051: DC braking selection<br />
A082: AVR voltage select<br />
b046: Reverse run proctection enable