Chapter 4 Explanation of Functions<br />

When using the brake control function, assign the following signal functions to intelligent input and<br />

intelligent output terminals as needed.<br />

(1) To input a signal indicating that the brake is released from the external brake to the inverter, assign the<br />

braking confirmation signal (44: BOK) to one of the terminal [1] to [8] functions (C001 to C008).<br />

(2) Assign the brake release signal (19: BRK), which is a brake-releasing command, to one of the<br />

intelligent output terminals [11] to [15] (C021 to C025). To output a signal when braking is abnormal,<br />

assign the brake error signal (20: BER) to an intelligent output terminal.<br />

When using the brake control function, you are recommended to select the sensorless vector control<br />

(A044 = 03) 0Hz-range sensorless vector control (A044 = 04) or V2 (A044=05)as the V/F characteristic<br />

curve selection that ensures a high starting torque. (See Section 4.2.18.)<br />

Settings required for the brake control function<br />

Item Function code Data or range of data Description<br />

Brake Control Enable<br />

b120<br />

00 Disabling the brake control function<br />

01 Enabling the brake control function<br />

Time to wait after the output frequency<br />

Brake Wait Time for<br />

has reached the release frequency until<br />

b121<br />

0.00 to 5.00 (s)<br />

Release<br />

the output current reaches the release<br />

current<br />

Brake Wait Time for<br />

Acceleration<br />

Brake Wait Time for<br />

Stopping<br />

Brake Wait Time for<br />

Confirmation<br />

b122<br />

b123<br />

b124<br />

0.00 to 5.00 (s)<br />

0.00 to 5.00 (s)<br />

0.00 to 5.00 (s)<br />

Mechanical delay after the release<br />

signal has been output until the brake is<br />

released<br />

Mechanical delay after the release<br />

signal has been turned off until the brake<br />

is applied<br />

Wait time longer than the delay after the<br />

release signal output until the release<br />

completion signal output from the brake<br />

is input to the inverter<br />

Frequency at which to output the brake<br />

release signal (*1)<br />

Brake Release Frequency<br />

0.00 to 99.99 or 100.0 to<br />

b125<br />

Setting<br />

400.0 (Hz)<br />

"0 x rated current" to<br />

Brake Release Current<br />

b126<br />

"2.0x rated<br />

Setting<br />

current" (%)<br />

0.00 to 99.99 or 100.0 to<br />

Braking frequency<br />

b127<br />

400.0 (Hz)<br />

*1 Specify a frequency higher than the start frequency (b082).<br />

*2 Note that setting a low current may not ensure sufficient torque at brake releasing.<br />

*3 :applied for 75 to 150kW<br />

Frequency at which to permit brake<br />

releasing (*2)<br />

Frequency at which to apply the brake<br />

for stopping the motor (*1)<br />

The inverter will trip with the braking error signal (BER) (E36: brake error) output in one of the following<br />

cases:<br />

1) The inverter output current brake remains below the brake release current, even after the release wait<br />

time (b121).<br />

2) During acceleration, the braking confirmation signal (BOK) is not turned on within the braking wait time<br />

(b124). During deceleration, the braking confirmation signal (BOK) is not turned off within the braking<br />

wait time (b124). Otherwise, the braking confirmation signal is turned off although the brake release<br />

signal is output.<br />

4 - 83