Chapter 4 Explanation of Functions<br />

4.2.86 Automatic user-parameter setting<br />

The automatic user-parameter setting function allows you to make the<br />

inverter automatically store the parameters you readjusted sequentially<br />

as user parameters "U001" to "U012". You can use the stored data as a<br />

readjustment history. To enable this function, select "01" (enabling<br />

automatic user-parameter setting) for the automatic user-parameter<br />

setting function enable (b039).<br />

The setting data entered in (displayed on) the digital operator is stored when the STR key is pressed. Also<br />

the monitor screen code (d***) is stored at the same time.<br />

User parameter "U001" retains the latest update of setting; user parameter "U012", the oldest update.<br />

A functional parameter can be stored as only a single user parameter. After all the 12 user parameters<br />

have been used to store functional-parameter settings, new functional-parameter settings will be stored as<br />

user parameters on a first-in, first-out basis (that is, the next parameter will be written to "U012", storing the<br />

oldest update, first).<br />

Item Function code Data Description<br />

Automatic user-parameter setting<br />

00 Disabling automatic user<br />

b039<br />

function enable<br />

01 Enabling automatic user<br />

4.2.87 Stabilization constant setting<br />

The stabilization constant setting function allows you to adjust the inverter<br />

to stabilize the motor operation when the motor operation is unstable.<br />

If the motor operation is unstable, check the motor capacity setting (H003/H203) and motor pole setting<br />

(H004/H204) to determine whether the settings match the motor specifications. If they do not match,<br />

readjust the settings. If the primary resistance of the motor is less than the standard motor specification, try<br />

to increase the setting of "H006/H206/H306" step by step. Try to reduce the setting of "H006/H206/H306" if<br />

the inverter is driving a motor of which the capacity is higher than the inverter rating.<br />

You can also use the following methods to stabilize the motor operation:<br />

1) Reducing the carrier frequency (b083) (See Section 4.2.11.)<br />

2) Reducing the V/f gain setting (A045) (See Section 4.2.17.)<br />

Item Function code Data Description<br />

Stabilization constant<br />

H006/H206/<br />

Increase or reduce the setting to stabilize<br />

0. to 255.<br />

H306<br />

the motor.<br />

V/f gain setting A045 20. to 100. (%) Reduce the setting to stabilize the motor.<br />

Carrier frequency setting b083 0.5 to 15.0 (kHz) Reduce the setting to stabilize the motor.<br />

4.2.88 Selection of operation at option board error<br />

You can select how the inverter operates when an error results from<br />

a built-in option board between two modes. In one mode, the<br />

inverter trips. In the other mode, the inverter ignores the error and<br />

continues the operation.<br />

When you use the feedback option board (SJ-FB) as option board 1,<br />

specify "01" for "P001". When you use the SJ-FB as option board 2,<br />

specify "01" for "P002".<br />

Related code<br />

b039: Automatic user-parameter<br />

setting function enable<br />

U001 to U012: User parameters<br />

Related code<br />

H006/H206/H306: Motor stabilization<br />

constant, 1st/2nd/3rd motors<br />

A045: V/f gain setting<br />

b083: Carrier frequency setting<br />

Related code<br />

P001: Operation mode on expansion card 1<br />

error<br />

P002: Operation mode on expansion card 2<br />

error<br />

Item Function code Data Description<br />

Operation mode on<br />

00 TRP: Alarm output<br />

expansion card 1 and 2 P001/P002<br />

RUN: Continuation of operation<br />

01<br />

errors<br />

4 - 80