Chapter 4 Explanation of Functions<br />

4.2.83 Initialization setting<br />

Related code<br />

b084: Initialization mode (parameters<br />

The initialization function allows you to initialize the adjusted settings on<br />

or trip history)<br />

the inverter to restore the factory settings. You can also clear the trip b085: Country code for initialization<br />

history data alone.<br />

The settings of initialization are described below.<br />

The settings of "P100" to "P131", running-time data, and power-on time data cannot be cleared.<br />

Item Function code Data Description<br />

00 Clearing on the trip history data<br />

b084<br />

01<br />

Initializing only the settings<br />

The factory settings are restored.<br />

02<br />

Initialization mode<br />

(parameters or trip<br />

history)<br />

Country code for<br />

initialization<br />

b085<br />

Clearing the trip history data and initializing the<br />

settings<br />

00 Defaults intended for Japan<br />

01 Defaults intended for Europe<br />

02 Defaults intended for the U.S.A.<br />

(Initializing procedure)<br />

Adjust the above settings as required, and then perform the following procedure:<br />

RUN<br />

STOP/<br />

RESET<br />

RUN<br />

STOP/<br />

RESET<br />

RUN<br />

STOP/<br />

RESET<br />

FUNC<br />

STR<br />

FUNC<br />

STR<br />

FUNC<br />

STR<br />

1) Holding down the FUNC and [2]<br />

(down) keys, press and hold down<br />

the STOP/RESET key.<br />

- After the monitor starts blinking,<br />

release only the STOP/RESET<br />

key. (The display on the monitor<br />

changes to that shown in the<br />

middle figure above.<br />

- Release the FUNC and [2]<br />

(down) keys.<br />

Initialization-in-progress<br />

display intended for Europe<br />

2) Initialization is in progress.<br />

- The above figure shows the<br />

monitor display (indicating that the<br />

initialization is in progress)<br />

intended for Japan. Those<br />

intended for other regions and trip<br />

history clearance are shown<br />

below.<br />

3) When the initialization is<br />

completed, the monitor displays<br />

code "d001".<br />

Confirm that the settings have<br />

been initialized.<br />

Initialization-in-progress<br />

display intended for the U.S.A.<br />

Initialization-in-progress display for<br />

trip history clearance<br />

In the far-left digit, the lighting<br />

segments move round for<br />

Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121,<br />

C122, and C123) and thermistor coefficient setting (C085).<br />

Note 2: The initialization operation does not initialize the settings of easy sequence user parameters<br />

(P100 to P131).<br />