Chapter 4 Explanation of Functions<br />
4.2.83 Initialization setting<br />
Related code<br />
b084: Initialization mode (parameters<br />
The initialization function allows you to initialize the adjusted settings on<br />
or trip history)<br />
the inverter to restore the factory settings. You can also clear the trip b085: Country code for initialization<br />
history data alone.<br />
The settings of initialization are described below.<br />
The settings of "P100" to "P131", running-time data, and power-on time data cannot be cleared.<br />
Item Function code Data Description<br />
00 Clearing on the trip history data<br />
b084<br />
01<br />
Initializing only the settings<br />
The factory settings are restored.<br />
02<br />
Initialization mode<br />
(parameters or trip<br />
history)<br />
Country code for<br />
initialization<br />
b085<br />
Clearing the trip history data and initializing the<br />
settings<br />
00 Defaults intended for Japan<br />
01 Defaults intended for Europe<br />
02 Defaults intended for the U.S.A.<br />
(Initializing procedure)<br />
Adjust the above settings as required, and then perform the following procedure:<br />
RUN<br />
STOP/<br />
RESET<br />
RUN<br />
STOP/<br />
RESET<br />
RUN<br />
STOP/<br />
RESET<br />
FUNC<br />
STR<br />
FUNC<br />
STR<br />
FUNC<br />
STR<br />
1) Holding down the FUNC and [2]<br />
(down) keys, press and hold down<br />
the STOP/RESET key.<br />
- After the monitor starts blinking,<br />
release only the STOP/RESET<br />
key. (The display on the monitor<br />
changes to that shown in the<br />
middle figure above.<br />
- Release the FUNC and [2]<br />
(down) keys.<br />
Initialization-in-progress<br />
display intended for Europe<br />
2) Initialization is in progress.<br />
- The above figure shows the<br />
monitor display (indicating that the<br />
initialization is in progress)<br />
intended for Japan. Those<br />
intended for other regions and trip<br />
history clearance are shown<br />
below.<br />
3) When the initialization is<br />
completed, the monitor displays<br />
code "d001".<br />
Confirm that the settings have<br />
been initialized.<br />
Initialization-in-progress<br />
display intended for the U.S.A.<br />
Initialization-in-progress display for<br />
trip history clearance<br />
In the far-left digit, the lighting<br />
segments move round for<br />
Note 1: The initialization operation does not initialize the analog input settings (C081, C082, C083, C121,<br />
C122, and C123) and thermistor coefficient setting (C085).<br />
Note 2: The initialization operation does not initialize the settings of easy sequence user parameters<br />
(P100 to P131).<br />
4 - 76