Chapter 4 Explanation of Functions<br />

4.2.82 AM and AMI terminals<br />

You can monitor the inverter output frequency and output current via the AM<br />

and AMI terminals on the control circuit block.<br />

The AM terminal outputs an analog voltage signal (0 to 10 V).<br />

The AMI terminal outputs an analog current signal (4 to 20 mA).<br />

Related code<br />

C028: [AM] siginal selection<br />

C029: [AMI] siginal selection<br />

C106: AM gain adjustment<br />

C109: AM offset adjustment<br />

C108: AMI gain adjustment<br />

C110: AMI offset adjustment<br />

(1) AM siginal selection /AMI signal selection<br />

Select the signals to be output from the AM and AMI terminals among those shown below.<br />

Item Function code Data Description Full-scale value<br />

00 Output frequency 0 to maximum frequency (Hz) (*3)<br />

01 Output current 0 to 200%<br />

02 Output torque (*1) 0 to 200%<br />

04 Output voltage<br />

0 to 133% (75% of full scale is<br />

equivalent to 100%)<br />

05 Input power 0 to 200%<br />

Electronic thermal<br />

06<br />

0 to 100%<br />

overload<br />

[AM] siginal<br />

selection /<br />

07 LAD frequency 0 to maximum frequency (Hz)<br />

C028/C029<br />

[AMI] siginal<br />

0ºC to 200ºC (0ºC is output when the<br />

09 Motor temperature<br />

selection<br />

motor temperature is 0ºC or less.)<br />

0ºC to 200ºC (0ºC is output when the<br />

10 Heat sink temperature<br />

motor temperature is 0ºC or less.)<br />

11 Output torque (signed)<br />

(Output only from the AM terminal) 0<br />

to 200% (*1) (*2)<br />

13 General analog YA (1) (*4)<br />

(Output only from the AM terminal) 0<br />

14 General analog YA (2) (*4)<br />

to 100%<br />

(Output only from the AMI terminal) 0<br />

to 100%<br />

*1 This signal is output only when the V/F characteristic curve selection (see Section 4.2.18) is the<br />

sensorless vector control, 0Hz-range sensorless vector control, or vector control with sensor.<br />

*2 The specifications of the output torque (signed) are as follows:<br />

AM output (V)<br />

When the AM gain (C106) is 100%<br />

10<br />

When the AM gain (C106) is 200%<br />

5<br />

When the AM offset (C109) is 50%<br />

0<br />

100<br />

200<br />

Torque (%)<br />

*3 The actually detected output frequency is output when the V/F characteristic curve selection is the<br />

vector control with sensor (A044 = 05).<br />

*4 For detail of the function, refer “Programing software EZ-SQ user manuaru”.<br />

(2) AM/AMI adjustment<br />

Adjust the inverter output gain for the external meters connected to the AM and AMI terminals.<br />

Item Function code Range of data Description<br />

Setting of the gain for AM monitoring C106 50. to 200. (%) Setting of the gain for AM monitoring<br />

Setting of the offset for AM monitoring C109 0 to 100 (%) Setting of the offset for AM monitoring<br />

Setting of the gain for AMI monitoring C107 50. to 200. (%) Setting of the gain for AMI monitoring<br />

Setting of the offset for AMI monitoring C110 0 to 100 (%) Setting of the offset for AMI monitoring<br />

Note: The offset data is in percentage (%).<br />

(Example) When the current range of AMI terminal output is 4 to 20 mA (default), the offset of 4 mA<br />

is 20%.<br />

4 - 75