Chapter 4 Explanation of Functions<br />

4.2.72 Low-current indication (LOC) signal<br />

The inverter outputs the low-current indication (LOC)<br />

signal when the inverter output current falls to the<br />

low-current indication signal detection level (C039) or<br />

less.<br />

Related code<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

C038: Low-current indication signal output mode selection<br />

C039: Low-current indication signal detection level<br />

You can select one of the two signal output modes with the low-current indication signal output mode<br />

selection (C038). In one mode, the LOC signal output is always enabled during the inverter operation. In<br />

the other mode, the LOC signal output is enabled only while the inverter is driving the motor for<br />

constant-speed operation.<br />

Item Function code Data or range of data Description<br />

Terminal function<br />

C021 to C025<br />

43 LOC: Low-current indication signal<br />

Alarm relay terminal function C026<br />

Enabling the signal output during<br />

00<br />

Low-current indication signal<br />

operation<br />

C038<br />

output mode selection<br />

Enabling the signal output only<br />

01<br />

during constant-speed operation (*1<br />

Setting of the threshold current level<br />

Low-current indication signal<br />

0.0 to "2.0 x rated<br />

C039<br />

at which to output the low-current<br />

detection level<br />

current" (A)<br />

indication signal<br />

(*1) When 01 (control circuit terminal) is selected as frequency source setting (A001), there is a case that<br />

inverter does not recognize the speed as constant value due to sampling. In this case, adjusting is to be<br />

made by setting C038=00 (valid during operation) or increasing analogue input filter (A016).<br />

Output current (A)<br />

Low-current indication<br />

signal detection level<br />

(C039)<br />

Low-current<br />

indication signal<br />

ON<br />

ON<br />

4.2.73 Inverter ready signal (IRDY)<br />

Related code<br />

The inverter outputs the inverter ready (IRDY) signal when it is ready C021 to C025: Terminal [11] to [15] functions<br />

for operation (i.e., when it can receive an operation command). C026: Alarm relay terminal function<br />

- The inverter can recognize only the operation command that is input while the IRDY signal is output.<br />

- If the IRDY signal is not output, check whether the input power supply voltage (connected to the R, S, and T<br />

terminals) is within the range of specification.<br />

- Signal is not output when the power is given only to control power supply.<br />

Item Function code Data or range of data Description<br />

Terminal function<br />

C021 to C025<br />

50 IRDY: Inverter ready signal<br />

Alarm relay terminal function<br />

C026<br />

4.2.74 Forward rotation signal (FWR)<br />

The inverter continues to output the forward rotation (FWR) signal<br />

while it is driving the motor for forward operation.<br />

The FWR signal is turned off while the inverter is driving the motor for<br />

reverse operation or stopping the motor.<br />

Item Function code Data or range of data Description<br />

Terminal function<br />

C021 to C025<br />

51 FWR: Forward rotation signal<br />

Alarm relay terminal function<br />

C026<br />

4 - 70<br />

Related code<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function