Chapter 4 Explanation of Functions<br />

4.2.69 Cooling-fan speed drop signal (WAF)<br />

Related code<br />

The inverter outputs the cooling-fan speed drop (WAF) signal<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

when it detects that the rotation speed of its internal cooling fan b092: Cooling fan control<br />

has fallen to 75% or less of the full speed.<br />

d022: Life-check monitoring<br />

If "01" has been selected for the cooling fan control (b092), the<br />

inverter will not output the WAF signal, even when the cooling fan<br />

stops.<br />

If the WAF signal is output, check the cooling-fan cover for clogging.<br />

You can monitor the state of the WAF signal by using the life-check monitoring function (d022).<br />

Item Function code Data Description<br />

Terminal function<br />

C021 to C025<br />

WAF: Cooling-fan speed<br />

40<br />

Alarm relay terminal function<br />

C026<br />

drop signal<br />

4.2.70 Starting contact signal (FR)<br />

Related code<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

The inverter outputs the starting contact (FR) signal while it is<br />

receiving an operation command.<br />

The FR signal is output, regardless of the setting of the run command source setting (A002).<br />

If the forward operation (FW) and reverse operation (RV) commands are input at the same time, the<br />

inverter stops the motor operation.<br />

Item Function code Data Description<br />

Terminal function<br />

C021 to C025<br />

FR: Starting contact<br />

41<br />

Alarm relay terminal function<br />

C026<br />

signal<br />

Forward operation command<br />

Reverse operation command<br />

Starting contact signal (FR)<br />

4.2.71 Heat sink overheat warning signal (OHF)<br />

The inverter monitors the temperature of its internal heat sink,<br />

and outputs the heat sink overheat warning (OHF) signal when<br />

the temperature exceeds the heat sink overheat warning level<br />

(C064).<br />

Related code<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

C064: Heat sink overheat warning level<br />

Item Function code Data or range of data Description<br />

Terminal function<br />

C021 to C025<br />

OHF: Heat sink overheat warning<br />

42<br />

Alarm relay terminal function<br />

C026<br />

signal<br />

Setting of the threshold<br />

Heat sink overheat warning level C064 0. to 200. (℃) temperature at which to output the<br />

heat sink overheat warning signal<br />

4 - 69