Chapter 4 Explanation of Functions<br />

Item Function code Data or range of data Description<br />

33<br />

LOG1: Logical operation result 1<br />

(C142, C143, and C144)<br />

Terminal function<br />

34<br />

LOG2: Logical operation result 2<br />

(C145, C146, and C147)<br />

LOG3: Logical operation result 3<br />

35<br />

C021 to C025<br />

(C148, C149, and C150)<br />

C026<br />

LOG4: Logical operation result 4<br />

36<br />

(C151, C152, and C153)<br />

Alarm relay<br />

LOG5: Logical operation result 5<br />

37<br />

terminal function<br />

(C154, C155, and C156)<br />

38<br />

LOG6: Logical operation result 6<br />

(C157, C158, and C159)<br />

Selection of "00" to "56" from the Selection of operation-target 1<br />

Logical output C142/C145/C148/<br />

data (except LOG1 to LOG6) output<br />

signal selection 1 C151/C154/C157<br />

Logical output<br />

signal selection 2<br />

Logical output<br />

signal operator<br />

selection<br />

C143/C146/C149/<br />

C152/C155/C158<br />

C144/C147/C150/<br />

C153/C156/C159<br />

4.2.67 Capacitor life warning signal (WAC)<br />

to intelligent output terminals<br />

Selection of "00" to "56" from the<br />

data (except LOG1 to LOG6) output<br />

to intelligent output terminals<br />

The inverter checks the operating life of the capacitors on the<br />

internal circuit boards on the basis of the internal temperature<br />

and cumulative power-on time.<br />

00 AND<br />

01 OR<br />

02 XOR<br />

Selection of operation-target 2<br />

Related code<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

You can monitor the state of the capacitor life warning (WAC) signal by using the life-check monitoring<br />

function (d022).<br />

If the WAC signal is output, you are recommended to replace the main circuit and logic circuit boards.<br />

Item Function code Data or range of data Description<br />

Terminal function<br />

C021 to C025<br />

WAC: Capacitor life warning signal<br />

39<br />

Alarm relay terminal function<br />

C026<br />

(for on-board capacitors)<br />

4.2.68 Communication line disconnection signal (NDc)<br />

This signal function is enabled only when ModBus-RTU has been Related code<br />

selected for the RS485 communication.<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

If a reception timeout occurs, the inverter continues to output the<br />

C077: Communication trip time<br />

communication line disconnection signal until it receives the next<br />

data.<br />

Specify the limit time for reception timeout by setting the communication trip time (C077).<br />

For details, see Section 4.4, "Communication Functions."<br />

External control equipment<br />

Inverter<br />

Monitoring timer<br />

Communication line<br />

disconnection signal (NDc)<br />

Communication trip time<br />

(C077)<br />

Item Function code Data or range of data Description<br />

Terminal function<br />

C021 to C025<br />

NDc: Communication line<br />

32<br />

Alarm relay terminal function<br />

C026<br />

disconnection signal<br />

Setting of the limit time for<br />

Communication trip time C077 0.00 to 99.99 (s)<br />

reception timeout<br />

4 - 68