Chapter 4 Explanation of Functions<br />
Intelligent output terminals When "4 bits" is selected When "3 bits" is selected<br />
14 13 12 11<br />
AC3 AC2 AC1 AC0<br />
Factor code Cause of tripping Factor code Cause of tripping<br />
Temperature error due to<br />
1 1 0 1 E20, E21 low cooling-fan speed<br />
-<br />
-<br />
Temperature error<br />
1 1 1 0 E24 Phase loss input protection - -<br />
1 1 1 1 E50 to E79<br />
Easy sequence user trip 0-9,<br />
option 1,2 error 0-9<br />
-<br />
-<br />
Item Function code Data Description<br />
00 No output of alarm code<br />
Alarm code output<br />
C062<br />
01 Output of 3-bit code<br />
02 Output of 4-bit code<br />
4.2.66 Logical output signal operation function (LOG1 to LOG6)<br />
The logical output signal operation function allows you to make<br />
the inverter internally perform a logical operation of output<br />
signals.<br />
This function applies to all output signals, except to logical<br />
operation results (LOG1 to LOG6).<br />
Three types of operators (AND, OR, and XOR) are selectable.<br />
Output signal 1<br />
Output signal 2<br />
LOGx (AND)<br />
LOGx (OR)<br />
LOGx (XOR)<br />
Related code<br />
C021 to C025: Terminal [11] to [15] functions<br />
C026: Alarm relay terminal function<br />
C142: Logical output signal 1 selection 1<br />
C143: Logical output signal 1 selection 2<br />
C144: Logical output signal 1 operator selection<br />
C145: Logical output signal 2 selection 1<br />
C146: Logical output signal 2 selection 2<br />
C147: Logical output signal 2 operator selection<br />
C148: Logical output signal 3 selection 1<br />
C149: Logical output signal 3 selection 2<br />
C150: Logical output signal 3 operator selection<br />
C151: Logical output signal 4 selection 1<br />
C152: Logical output signal 4 selection 2<br />
C153: Logical output signal 4 operator selection<br />
C154: Logical output signal 5 selection 1<br />
C155: Logical output signal 5 selection 2<br />
C156: Logical output signal 5 operator selection<br />
C157: Logical output signal 6 selection 1<br />
C158: Logical output signal 6 selection 2<br />
C159: Logical output signal 6 operator selection<br />
The necessary parameters depend on the logical output signal to be operated. The following table lists the<br />
parameters to be set for each logical output signal:<br />
Selected signal<br />
Operation-target 1 Operation-target 2 Operator<br />
selection<br />
selection selection<br />
33: Logical output signal 1 (LOG1) C142 C143 C144<br />
34: Logical output signal 2 (LOG2) C145 C146 C147<br />
35: Logical output signal 3 (LOG3) C148 C149 C150<br />
36: Logical output signal 4 (LOG4) C151 C152 C153<br />
37: Logical output signal 5 (LOG5) C154 C155 C156<br />
38: Logical output signal 6 (LOG6) C157 C158 C159<br />
(Example) To output the AND of the running signal (00: RUN) and set the frequency overreached signal<br />
(02: FA2) as the logical output signal 1 (LOG1) to the intelligent output terminal [2]:<br />
- Intelligent output terminal [2] (C002): 33 (LOG1)<br />
- Logical output signal 1 selection 1 (C142): 00 (RUN)<br />
- Logical output signal 1 selection 2 (C143): 02 (FA2)<br />
- Logical output signal 1 operator (C143): 00 (AND)<br />