Chapter 4 Explanation of Functions<br />
4.2.62 Running time over and power-on time over signals (RNT and ONT)<br />
The inverter outputs the operation time over (RNT) signal or the<br />
plug-in time over (ONT) signal when the time specified as the<br />
run/power-on warning time (b034) is exceeded.<br />
Item Function code Range of data Description<br />
Disabling the signal output<br />
0.<br />
Setting in units of 10 hours<br />
Run/power-on warning time b034<br />
1. to 9999.<br />
Setting in units of 100 hours<br />
1000 to 6553<br />
(range: 100,000 to 655,300 hours)<br />
(1) Operation time over (RNT) signal<br />
To use this signal function, assign function "11" (RNT) to one of the intelligent output terminals [11] to [15]<br />
(C021 to C025) and the alarm relay terminal (C026).<br />
Specify the run/power-on warning time (b034).<br />
(2) Plug-in time over (ONT) signal<br />
To use this signal function, assign function "12" (ONT) to one of the intelligent output terminals [11] to [15]<br />
(C021 to C025) and the alarm relay terminal (C026).<br />
Specify the run/power-on warning time (b034).<br />
4.2.63 0 Hz speed detection signal (ZS)<br />
The inverter outputs the 0 Hz speed detection signal when the inverter<br />
output frequency falls below the threshold frequency specified as the<br />
zero speed detection level (C063).<br />
To use this signal function, assign function "21" (ZS) to one of the<br />
intelligent output terminals [11] to [15] (C021 to C025) and the alarm relay<br />
terminal (C026).<br />
Related code<br />
b034: Run/power-on warning time<br />
C021 to C025: Terminal [11] to [15]<br />
functions<br />
C026: Alarm relay terminal function<br />
d016: Cumulative operation RUN time<br />
monitoring<br />
d017: Cumulative power-on time monitoring<br />
Related code<br />
A044/A244/A344: V/F characteristic<br />
curve selection, 1st/2nd/3rd motors<br />
C021 to C025: Terminal [11] to [15]<br />
functions<br />
C063: Zero speed detection level<br />
This signal function applies to the inverter output frequency when the V/F characteristic curve selection is<br />
based on the constant torque characteristic (VC), reduced-torque characteristic (1.7th power of VP), free<br />
V/f characteristic, sensorless vector control, or 0Hz-range sensorless vector control. It applies to the motor<br />
speed when the V/F characteristic curve selection is based on the vector control with sensor.<br />
Item Function code Data or range of data Description<br />
Terminal function<br />
C021 to C025<br />
21 ZS: 0 Hz speed detection signal<br />
Alarm relay terminal function<br />
C026<br />
Setting of the frequency to be<br />
Zero speed detection level C063 0.00 to 100.0 (Hz)<br />
determined as 0 Hz<br />
4 - 65