Chapter 4 Explanation of Functions<br />

Data Description Reference item Page<br />

53 MJA: Major failure Major failure signal 4-70<br />

54 WCO<br />

55 WCOI<br />

Window comparators function 4-71<br />

56 WCO<br />

4.2.59 Intelligent output terminal a/b (NO/NC) selection<br />

The intelligent output terminal a/b (NO/NC) selection function<br />

allows you to specify a-contact or b-contact output for each of<br />

the intelligent output terminals [11] to [15] and the alarm relay<br />

terminal.<br />

The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal<br />

is used for relay output.<br />

Item Function code Data Description<br />

Terminal active state<br />

C031 to C035<br />

00 a-contact (NO)<br />

01 b-contact (NC)<br />

Alarm relay active state<br />

C036<br />

00 a-contact (NO)<br />

01 b-contact (NC)<br />

- An a-contact turns on the output signal when closed and turns it off when opened.<br />

- A b-contact turns on the output signal when opened and turns it off when closed.<br />

(1) Specifications of intelligent output terminals [11] to [15]<br />

Intelligent output terminals [11] to [15] have the following specifications:<br />

Related code<br />

C031 to C035: Terminal [11] to [15] active state<br />

C036: Alarm relay active state<br />

Inside the<br />

inverter<br />

15 CM2 … … 11<br />

Setting of C031 to C035 Power supply Output signal<br />

ON<br />

00<br />

ON<br />

OFF<br />

(a-contact)<br />

OFF<br />

-<br />

ON<br />

01<br />

ON<br />

OFF<br />

(b-contact)<br />

OFF<br />

-<br />

Electric characteristics<br />

(Between each terminal and CM2)<br />

Voltage drop when turned on: 4 V or less<br />

Allowable maximum voltage: 27 VDC<br />

Allowable maximum current: 50 mA<br />

(2) Specifications of alarm relay terminal<br />

The alarm relay terminal uses a normally-closed (NC) contact that operates as described below.<br />

Inside the<br />

inverter<br />

AL0 AL1 AL2<br />

Example of operation as an alarm output terminal<br />

Setting<br />

of C036<br />

00<br />

01<br />

(default)<br />

Power<br />

supply<br />

Inverter Output terminal state<br />

status AL1-AL0 AL2-AL0<br />

Error Closed Open<br />

ON<br />

Normal Open Closed<br />

OFF - Open Closed<br />

ON<br />

Error Open Closed<br />

Normal Closed Open<br />

OFF - Open Closed<br />

AL1-AL0<br />

AL2-AL0<br />

4 - 62<br />

Maximum contact<br />

capacity<br />

Minimum contact<br />

capacity<br />

Maximum contact<br />

capacity<br />

Minimum contact<br />

capacity<br />

Resistance load<br />

250 VAC, 2 A<br />

30 VDC, 3 A<br />

250 VAC, 1A<br />

30 VDC, 1A<br />

100 V AC, 10 mA<br />

5 VDC, 100 mA<br />

100 VAC, 10 mA<br />

5 VDC, 100 mA<br />

Inductive load<br />

250 VAC, 2 A<br />

30 VDC, 8 A<br />

250 VAC, 0.2 A<br />

30 VDC, 0.2 A