Chapter 4 Explanation of Functions<br />
4.2.58 Intelligent output terminal setting<br />
You can assign the functions described below to the intelligent<br />
output terminals [11] to [15] (C021 to C025) and the alarm relay<br />
terminal (C026).<br />
The intelligent output terminals [11] to [15] are used for open-collector output, and the alarm relay terminal<br />
is used for relay output.<br />
You can select the a-contact or b-contact output for individual output terminals by using functions "C031" to<br />
"C035" and "C036".<br />
When "01" (3 bits) or "02" (4 bits) is specified for the alarm code output "C062" (see Section 4.2.65), the<br />
alarm code output is assigned to output terminals 11 to 13 or output terminals 11 to 14 (AC0 to AC3),<br />
respectively. Subsequently, the settings of "C021" to "C024" are invalidated.<br />
Data Description Reference item Page<br />
00 RUN: Running signal Running signal (RUN) 4-62<br />
01 FA1: Constant-speed reached<br />
02 FA2: Set frequency overreached<br />
Frequency-arrival signals 4-62<br />
03 OL: Overload notice advance signal (1) Overload restriction/overload notice advance signal 4-40<br />
04 OD: Output deviation for PID control PID function 4-26<br />
05 AL: Alarm signal Protective functions -<br />
06 FA3: Set frequency reached Frequency-arrival signals 4-62<br />
07 OTQ: Over-torque Over-torque signal 4-65<br />
08 IP: Instantaneous power failure<br />
09 UV: Undervoltage<br />
Instantaneous power failure/undervoltage 4-35<br />
10 TRQ: Torque limited Torque limitation function 4-92<br />
11 RNT: Operation time over Operation time over signal 4-64<br />
12 ONT: Plug-in time over Plug-in time over signal 4-64<br />
13 THM: Thermal alarm signal Electronic thermal protection 4-37<br />
19 BRK: Brake release<br />
20 BER: Brake error<br />
Brake control function 4-81<br />
21 ZS: 0 Hz detection signal 0 Hz detection signal 4-64<br />
22 DSE: Speed deviation maximum V2 control mode selection function 4-96<br />
23 POK: Positioning completed Orientation function 4-104<br />
24 FA4: Set frequency overreached 2<br />
25 FA5: Set frequency reached 2<br />
Frequency-arrival signals 4-62<br />
26 OL2: Overload notice advance signal (2) Overload restriction/overload notice advance signal 4-40<br />
27 Odc: Analog O disconnection detection<br />
28 OIDc: Analog OI disconnection detection Window comparators function 4-71<br />
29 O2Dc: Analog O2 disconnection detection<br />
31 FBV: PID feedback comparison PID function 4-26<br />
32 NDc: Communication line disconnection RS485 4-67<br />
33 LOG1: Logical operation result 1<br />
34 LOG2: Logical operation result 2<br />
35 LOG3: Logical operation result 3<br />
36 LOG4: Logical operation result 4<br />
Logical operation function 4-66<br />
37 LOG5: Logical operation result 5<br />
38 LOG6: Logical operation result 6<br />
39 WAC: Capacitor life warning Capacitor life warning 4-67<br />
40 WAF: Cooling-fan speed drop Cooling-fan speed drop 4-68<br />
41 FR: Starting contact signal Starting contact signal 4-68<br />
42 OHF: Heat sink overheat warning Heat sink overheat warning 4-68<br />
43 LOC: Low-current indication signal Low-current indication signal 4-69<br />
44 M01: General output 1<br />
45 M02: General output 2<br />
46 M03: General output 6<br />
47 M04: General output 4<br />
Easy sequence function<br />
-<br />
48 M05: General output 5<br />
49 M06: General output 6<br />
50 IRDY: Inverter ready Inverter ready signal 4-69<br />
51 FWR: Forward rotation Forward rotation signal 4-69<br />
52 RVR: Reverse rotation Reverse rotation signal 4-70<br />
4 - 61<br />
Related code<br />
C021 to C025: Terminal [11] to [15] functions<br />
C026: Alarm relay terminal function