Chapter 4 Explanation of Functions<br />

4.2.52 External trip (EXT) function<br />

The external trip function allows you to make the inverter trip<br />

according to the error (trip) signal generated by an external system.<br />

To use this function, assign function "12" (EXT) to one of the terminal [1] to [8] functions (C001 to C008).<br />

When the EXT terminal is turned on, the inverter trips with error code "E12" displayed and stops the<br />

output.<br />

After the inverter trips with error code "E12" displayed, it will not be recovered from tripping, even when the<br />

error signal from the external system is reset (i.e., the EXT terminal is turned off).<br />

To recover the inverter from tripping, reset the inverter or turn the inverter power off and on.<br />

Item Function code Data Description<br />

Terminal [1] to [8] functions C001 to C008 12 EXT: External trip<br />

Note: Do not turn on the EXT terminal after the inverter power is shut off. Otherwise, the error history may<br />

not be stored correctly.<br />

Operation commands<br />

FW and RV<br />

Related code<br />

C001 to C008: Terminal [1] to [8] functions<br />

EXT terminal<br />

Motor speed<br />

Free running<br />

RS terminal<br />

Alarm output terminal<br />

4.2.53 3-wire interface operation function (STA, STP, and F/R)<br />

Related code<br />

The 3-wire interface operation function allows you to use automatic- C001 to C008: Terminal [1] to [8] functions<br />

reset contacts (e.g., pushbutton switches) to start and stop the inverter.<br />

Specify "01" (control circuit terminal block) for the run command source setting (A002).<br />

Assign function "20" (STA), "21" (STP), and "22" (F/R) to three of the terminal [1] to [8] functions (C001 to<br />

C008) to enable the control operations described below. Assigning the STP function to an intelligent input<br />

terminal disables the functions of the FW and RV terminals.<br />

The figure below shows the inverter outputs according to terminal operations.<br />

Item Function code Data Description<br />

20 STA: Starting the motor<br />

21 STP: Stopping the motor<br />

Terminal [1] to [8] functions C001 to C008<br />

F/R: Switching the motor operation<br />

22<br />

direction<br />

STA<br />

ON<br />

OFF<br />

STP<br />

ON<br />

OFF<br />

F/R<br />

Output frequency<br />

Forward<br />

rotation<br />

Reverse<br />

rotation<br />

4 - 58