Chapter 4 Explanation of Functions<br />

4.2.50 Unattended start protection (USP) function<br />

The unattended start protection function allows you to make the<br />

inverter trip with error code "E13" displayed if the inverter power is<br />

turned on when an operation command has been turned on.<br />

You can recover the inverter from tripping by performing the reset operation or turning the operation<br />

command off. (See example 1.)<br />

If the inverter is recovered from tripping with the operation command left turned on, the inverter will start<br />

operation immediately after recovery. (See example 2.)<br />

The inverter can operate normally when an operation command is turned on after the inverter power is<br />

turned on. (See example 3.)<br />

To use this function, assign function "13" (USP) to one of the terminal [1] to [8] functions (C001 to C008).<br />

The following charts show examples of the timing of the unattended start protection operation:<br />

(Example 1) (Example 2) (Example 3)<br />

Power<br />

supply<br />

Power<br />

supply<br />

Related code<br />

C001 to C008: Terminal [1] to [8] functions<br />

Power<br />

supply<br />

FW<br />

FW<br />

FW<br />

USP<br />

RS<br />

Alarm<br />

Output<br />

frequency<br />

USP<br />

RS<br />

Alarm<br />

Output<br />

frequency<br />

USP<br />

RS<br />

Alarm<br />

Output<br />

frequency<br />

Item Function code Data Description<br />

Terminal [1] to [8] functions C001 to C008 13 USP: Unattended start protection<br />

4.2.51 Remote control function (UP and DWN)<br />

Related code<br />

C101: Up/Down memory mode selection<br />

C001 to C008: Terminal [1] to [8] functions<br />

The remote control function allows you to change the inverter output<br />

frequency by operating the UP and DWN terminals (intelligent input<br />

terminals).<br />

To use this function, assign functions "27" (UP) and "28" (DWN) to two of the terminal [1] to [8] functions<br />

(C001 to C008).<br />

- This function is only effective for multispeed operation when "01 (terminal)" or "02 (oprater)" has been<br />

specified for the frequency source setting (A001). If "01" (control circuit terminal block) has been specified,<br />

this function is only effective when the analog command holding function (AHD) is enabled. (see 4.2.56)<br />

This function is ineffective when the external analog input has been specified for the frequency source<br />

setting (A001). This function cannot be used to set frequencies for jogging operation.<br />

When the UP or DWN terminal is on, the 1st, 2nd, and 3rd acceleration/deceleration time follows the<br />

settings of "F002", "F003/F202", "F203/F302", and "F303". To switch between the 1st, 2nd, and 3rd<br />

controls, assign function "08" (SET) and "17" (SET3) to intelligent input terminals, and turn on and off the<br />

SET and SET3 terminals for switching.<br />

You can store the frequency settings adjusted using the remote control function (UP and DWN signals).<br />

Set 01 (enable) on C101 to store the frequency settings.<br />

You can also clear the stored frequency settings. Assign function "29" (UDC) to an intelligent input terminal,<br />

and turn on or off the UDC terminal to clear or store, respectively, the frequency settings adjusted with the<br />

UP and DWN signals. In this case 0Hz is set as initial value.<br />

Item Function code Data Description<br />

27 UP: Remote control UP function<br />

Terminal function<br />

C001 to C008 28 DWN: Remote control DOWN function<br />

29 DWN: Remote control data clearing<br />

Up/Down memory mode<br />

00 Disabling the storage of frequency settings<br />

C101<br />

selection<br />

01 Enabling the storage of frequency settings (*1)<br />

*1 Do not operate the UP or DWN terminal after the inverter power is shut off. Otherwise, the frequency<br />

settings may not be stored correctly.<br />

Operation command<br />

(FW or RV)<br />

UP<br />

DWN<br />

Output<br />

frequency<br />

4 - 57<br />

Turning on the UP and DWN terminals<br />

at the same time disables acceleration<br />

and deceleration.