Chapter 4 Explanation of Functions<br />
4.2.47 Free-run stop (FRS) function<br />
The free-run stop (FRS) function allows you to shut off the<br />
inverter output to let the motor start free-running.<br />
You can effectively use this function when stopping the<br />
motor with a mechanical brake (e.g., electromagnetic<br />
brake). If an attempt is made to forcibly stop the motor with<br />
a mechanical brake while the inverter keeps its output, the<br />
inverter may trip because of overcurrent.<br />
To use this function, assign function "11" (FRS) to one of the terminal [1] to [8] functions (C001 to C008).<br />
The free-run stop (FRS) function operates as long as the FRS terminal is on. When the FRS terminal is<br />
turned off, the inverter restarts the motor after the retry wait time (b003). However, the inverter does not<br />
restart the motor if the digital operator (02) has been specified for the run command source setting (A002).<br />
To restart the motor in such status, enter a new operation command.<br />
You can select the inverter output mode for restarting with the restart mode after FRS (b088) from starting<br />
the motor with 0 Hz, starting the motor with a matching frequency, and restarting the motor with the input<br />
frequency. (See examples 1, 2, and 3.)<br />
Even when restarting with matching frequency has been selected, the inverter restarts the motor with 0 Hz<br />
if it detects a frequency lower than the restart frequency threshold (b007).<br />
The settings, including that of the FRS terminal, which you make for this function will affect the inverter<br />
operation at recovery of the motor from the free-running status.<br />
Item Function code Data or range of data Description<br />
00 Start with 0 Hz (See example 1.)<br />
Restart mode after<br />
b088<br />
01 Start with matching frequency (See example 2.)<br />
FRS<br />
02 Restart with input frequency (See example 3.)<br />
Retry wait time before<br />
motor restart<br />
b003 0.3 to 100. (s) Time to wait until restarting the motor<br />
Restart frequency<br />
Setting of the minimum level for frequency<br />
b007 0.00 to 400.0 (Hz)<br />
threshold<br />
adjustment<br />
Active frequency<br />
matching, scan start<br />
frequency<br />
b028<br />
"0.20 x rated current" to<br />
"2.00 x rated<br />
current"<br />
Active frequency<br />
matching, scan-time<br />
constant<br />
Active frequency<br />
matching, restart<br />
frequency select<br />
b029<br />
b030<br />
(NOTE):applied for 75 to 150kW<br />
(Example 1) Restarting with 0 Hz<br />
0.10 to 30.00 (s)<br />
Related code<br />
b088: Restart mode after FRS<br />
b003: Retry wait time before motor restart<br />
b007: Restart frequency threshold<br />
b028: Active frequency matching, scan start frequency<br />
b029: Active frequency matching, scan-time constant<br />
b030: Active frequency matching, restart frequency<br />
select<br />
C001 to C008: Terminal [1] to [8] functions<br />
00<br />
Frequency set when the inverter output has<br />
been shut off<br />
01 Maximum frequency<br />
02 Newly set frequency<br />
(Example 2) Restarting with matching frequency<br />
FW<br />
FW<br />
FRS<br />
Motor<br />
speed<br />
0<br />
Free-running<br />
Restarting with 0 Hz<br />
The inverter restarts the motor with 0 Hz<br />
regardless of the motor speed. The setting of retry<br />
wait time is ignored for restarting with 0 Hz.<br />
If the inverter restarts the motor with 0 Hz when<br />
the motor speed is high, the inverter may trip<br />
because of overcurrent.<br />
4 - 53<br />
FRS<br />
Motor<br />
speed<br />
0<br />
b003<br />
Free-running<br />
Restarting with<br />
matching frequency<br />
The inverter waits for the retry wait time after the FRS<br />
terminal has been turned off, detects the motor speed<br />
(frequency), and restarts the motor with the matching<br />
frequency without stopping it. If the inverter trips because<br />
of overcurrent when it restarts the motor with matching<br />
frequency, prolongs the retry wait time.<br />
Even when restarting with matching frequency has been<br />
selected, the inverter may start the motor with 0 Hz if:<br />
1) the output frequency is no more than half the base<br />
frequency or<br />
2) the voltage induced on the motor is attenuated quickly.