Chapter 4 Explanation of Functions<br />

4.2.44 Software lock (SFT) function<br />

The software lock function allows you to specify whether to disable<br />

rewriting of the data set for functional items. Use this function to<br />

protect the data against accidental rewriting.<br />

You can select the functional items to be locked and the method of locking as described below.<br />

When using an intelligent input terminal for this function, assign function "15" (SFT) to one of the terminal<br />

[1] to [8] functions (C001 to C008).<br />

Function code Data SFT terminal Description<br />

00 ON/OFF<br />

Disabling rewriting of items other than "b031" (when SFT is on) or<br />

enabling rewriting (when SFT is off)<br />

01 ON/OFF<br />

Disabling the rewriting of items other than "b031", "F001", "A020",<br />

"A220", "A320", "A021" to "A035", and "A038" (when SFT is on) or<br />

b031<br />

enabling rewriting (when SFT is off)<br />

02 ― Disabling the rewriting of items other than "b031"<br />

03 ―<br />

Disabling the rewriting of items other than "b031", "F001", "A020",<br />

"A220", "A320", "A021" to "A035", and "A038"<br />

10 ―<br />

Disabling rewriting except in the mode allowing changes during<br />

operation<br />

4.2.45 Forcible-operation from digital operator (OPE) function<br />

The forcible-operation function allows you to forcibly enable the<br />

inverter operation from the digital operator when the digital operator is<br />

not selected as the device to input frequency and operation<br />

commands. An intelligent input terminal is used to turn this function<br />

on and off.<br />

When the intelligent input terminal to which the forcible-operation function is assigned is off, frequency and<br />

operation commands are input from the devices selected by functions "A001" and "A002". When the<br />

terminal is on, the device to input frequency and operation commands is forcibly switched to the digital<br />

operator.<br />

If the input device is switched while the inverter is operating, the current operation command is canceled<br />

and the inverter stops the output. When restarting the inverter operation, turn off the operation command<br />

that was to be entered from each input device for safety's sake, and then enter a new operation command.<br />

Item Function code Data Description<br />

Terminal function C001 to C008 31 OPE: Forcible operation<br />

4.2.46 Forcible-operation from terminal (F-TM) function<br />

The forcible-operation function allows you to forcibly enable the<br />

inverter operation via control circuit terminals when the control circuit<br />

terminal block is not selected as the device to input frequency and<br />

operation commands. An intelligent input terminal is used to turn this<br />

function on and off.<br />

Related code<br />

b031: Software lock mode selection<br />

C001 to C008: Terminal [1] to [8] functions<br />

Related code<br />

A001: Frequency source setting<br />

A002: Run command source setting<br />

C001 to C008: Terminal [1] to [8] functions<br />

Related code<br />

A001: Frequency source setting<br />

A002: Run command source setting<br />

C001 to C008: Terminal [1] to [8] functions<br />

When the intelligent input terminal to which the forcible-terminal operation function is assigned is off,<br />

frequency and operation commands are input from the devices selected by functions "A001" and "A002".<br />

When the terminal is on, the device to input frequency and operation commands is forcibly switched to the<br />

control circuit terminal block.<br />

If the input device is switched while the inverter is operating, the current operation command is canceled<br />

and the inverter stops the output. When restarting the inverter operation, turn off the operation command<br />

that was to be entered from each input device for safety's sake, and then enter a new operation command.<br />

Item Function code Data Description<br />

Terminal function C001 to C008 51 F-TM: Forcible-terminal operation<br />

4 - 52