Chapter 4 Explanation of Functions<br />
4.2.42 Jogging (JG) command setting<br />
The jogging command setting function allows you to set and finely<br />
tune the motor-stopping position.<br />
To use this function, assign function "06" (JG) to an intelligent input<br />
terminal.<br />
(1) Jog frequency setting<br />
Related code<br />
A038: Jog frequency setting<br />
A039: Jog stop mode<br />
C001 to C008: Terminal [1] to [8] functions<br />
JG<br />
FW<br />
RV<br />
Output frequency<br />
A038<br />
Since the inverter operates the motor with a full voltage for the jogging operation, the inverter can easily<br />
trip during the latter. Adjust the jog frequency setting (A038) properly so that the inverter will not trip.<br />
Item Function code Range of data Description<br />
A038<br />
0.0 or "start frequency"<br />
to 9.99 (Hz)<br />
Jog frequency<br />
setting<br />
(2) Jog stop mode<br />
Setting of the frequency to output during jogging<br />
operation<br />
Item Function code Data Description<br />
00<br />
Disabling jogging while the motor is operating and<br />
enabling free-running when the motor is stopped<br />
01<br />
Disabling jogging while the motor is operating and<br />
enabling stopping after deceleration when the<br />
motor is stopped<br />
Jog stop mode A039<br />
02 (See Note 2.)<br />
Disabling jogging while the motor is operating and<br />
enabling DC braking when the motor is stopped<br />
03<br />
Enabling jogging while the motor is operating and<br />
enabling free-running when the motor is stopped<br />
Enabling jogging while the motor is operating and<br />
04<br />
enabling stopping after deceleration when the<br />
motor is stopped<br />
05 (See Note 2.)<br />
Enabling jogging while the motor is operating and<br />
enabling DC braking when the motor is stopped<br />
Note 1: To perform the jogging operation, always turn on the JG terminal before turning on the FW or RV<br />
terminals. (Follow this sequence of command inputs also when using the digital operator to enter<br />
operation commands.)<br />
(Example 1) (Example 2)<br />
JG<br />
JG<br />
FW<br />
FW<br />
Normal<br />
operation<br />
Deceleration<br />
Jogging operation<br />
Output<br />
frequency<br />
When "00", "01", or "02" is specified for the jog stop<br />
mode (A039), the jogging operation will not be<br />
performed if the FW signal is turned on earlier than<br />
the JG signal.<br />
Output<br />
frequency<br />
Free running<br />
Acceleration according to the setting of "b088"<br />
When "03", "04", or "05" is specified for the jog stop mode<br />
(A039), the jogging operation will be performed, even if the<br />
FW signal is turned on earlier than the JG signal. However,<br />
the motor will stop after free-running if the JG signal is turned<br />
off earlier than the FW signal.<br />
Note 2: You must set DC braking data if you specify "02" or "05" for the jog stop mode (A039). (See<br />
Section 4.2.19.)<br />
4 - 50