Chapter 4 Explanation of Functions<br />
4.2.39 Intelligent input terminal setting<br />
You can assign the functions described below to intelligent input<br />
terminals [1] to [8]. To assign the desired functions to the<br />
terminals, specify the desired data listed in the table below for<br />
terminal settings "C001" to "C008". For example, "C001"<br />
corresponds to intelligent input terminal [1].<br />
You can select the a-contact or b-contact input for individual intelligent input terminals.<br />
Related code<br />
C001 to C008: Terminal [1] to [8] functions<br />
You can assign one function only to an intelligent input terminal. If you have attempted to assign a function<br />
to two or more intelligent input terminals, the function is assigned to only the terminal to which you have<br />
last attempted assignment. Function data "NO" (no assign) is assigned to other terminals, and those<br />
terminals are ineffective in terms of functions.<br />
After assigning the desired functions to intelligent input terminals [1] to [8], confirm that the assigned<br />
functions have been stored on the inverter.<br />
Function code Data Description Reference item Page<br />
01 RV: Reverse RUN command Operation command -<br />
02 CF1: Multispeed 1 setting (binary operation)<br />
03 CF2: Multispeed 2 setting (binary operation)<br />
04 CF3: Multispeed 3 setting (binary operation)<br />
Multispeed operation function 4-48<br />
05 CF4: Multispeed 4 setting (binary operation)<br />
06 JG: Jogging Jogging operation function 4-50<br />
07 DB: External DC braking DC braking (external DC braking) function 4-20<br />
08 SET: Set 2nd motor data 2nd/3rd motor control function 4-50<br />
09 2CH: 2-stage acceleration/deceleration 2-stage acceleration/deceleration function 4-30<br />
11 FRS: Free-run stop Free-run stop function 4-53<br />
12 EXT: External trip External trip function 4-58<br />
13 USP: Unattended start protection Unattended start protection function 4-57<br />
14 CS: Commercial power source enable Commercial power supply switching function 4-54<br />
15 SFT: Software lock (control circuit terminal block) Software lock function 4-52<br />
16 AT: Analog input voltage/current select External analog input setting function 4-12<br />
17 SET3: 3rd motor control 2nd/3rd motor control function 4-51<br />
18 RS: Reset Reset 4-55<br />
20 STA: Starting by 3-wire input<br />
21 STP: Stopping by 3-wire input<br />
3-wire input function 4-58<br />
22 F/R: Forward/reverse switching by 3-wire input<br />
23 PID: PID disable<br />
24 PIDC: PID reset<br />
PID function 4-26<br />
C001 to C008 26 CAS: Control gain setting Control gain switching function 4-59<br />
27 UP: Remote control UP function<br />
28 DWN: Remote control DOWN function<br />
Remote control (UP/DWN) function 4-57<br />
29 DWN: Remote control data clearing<br />
31 OPE: Forcible operation Forcible-operation function 4-52<br />
32 SF1: Multispeed 1 setting (bit operation)<br />
33 SF2: Multispeed 2 setting (bit operation)<br />
34 SF3: Multispeed 3 setting (bit operation)<br />
35 SF4: Multispeed 4 setting (bit operation) Multispeed operation function 4-48<br />
36 SF5: Multispeed 5 setting (bit operation)<br />
37 SF6: Multispeed 6 setting (bit operation)<br />
38 SF7: Multispeed 7 setting (bit operation)<br />
39 OLR: Overload restriction selection Overload restriction function 4-40<br />
40 TL: Torque limit enable<br />
41 TRQ1: Torque limit selection bit 1<br />
Torque limitation function 4-93<br />
42 TRQ2: Torque limit selection bit 2<br />
43 PPI: P/PI mode selection P/PI switching function 4-59<br />
44 BOK: Braking confirmation Brake control function 4-82<br />
45 ORT: Orientation Orientation function 4-105<br />
46 LAC: LAD cancellation LAD cancellation function 4-10<br />
47 PCLR: Clearance of position deviation<br />
V2 control mode selection function<br />
48 STAT: Pulse train position command input enable<br />
4-97<br />
50 ADD: Trigger for frequency addition (A145) Frequency addition function 4-14<br />
4 - 47