Chapter 4 Explanation of Functions<br />

4.2.33 Start frequency setting<br />

The start frequency setting function allows you to specify the inverter<br />

output frequency that the inverter initially outputs when an operation<br />

command is input.<br />

Use this function mainly to adjust the start torque.<br />

Related code<br />

b082: Start frequency adjustment<br />

If the start frequency (b082) is set too high, the inverter will start the motor with a full voltage, which will<br />

increase the start current. Such status may trigger the overload restriction operation or make the inverter<br />

prone to easily tripping because of the overcurrent protection.<br />

Specifying "04" (0SLV: 0Hz-range sensorless vector control) or "05" (V2: vector control with sensor) for the<br />

V/F characteristic curve selection (A044) disables the start frequency setting function.<br />

Item Function code Range of data Description<br />

Start frequency<br />

adjustment<br />

b082 0.10 to 9.99 (Hz) Setting of the start frequency<br />

FW<br />

Output frequency<br />

b082<br />

Output voltage<br />

4.2.34 Reduced voltage start function<br />

The reduced voltage start function enables you to make the inverter<br />

increase the output voltage gradually when starting the motor.<br />

Set a small value for the reduced voltage start selection (b036) if you<br />

intend to increase the start torque. On the other hand, setting a small<br />

value will cause the inverter to perform full-voltage starting and to easily<br />

trip because of overcurrent.<br />

Related code<br />

b036: Reduced voltage start selection<br />

b082: Start frequency adjustment<br />

Item Function code Range of data Description<br />

00 Disabling the reduced voltage starting<br />

Reduced voltage start<br />

01: Short (about 6 ms)<br />

b036<br />

selection<br />

01 to 255<br />

255: Long (about 1.53 s)<br />

FW<br />

Output frequency<br />

Start frequency<br />

b082<br />

Output voltage<br />

Reduced Voltage Start<br />

b036<br />

00 01 06 ・・・<br />

4 - 43