SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.
SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.
SJ700-2 Instruction Manual NT204DX - Hitachi America, Ltd.
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Chapter 4 Explanation of Functions<br />
(2) Overload nitice function<br />
The overload notice function allows you to make the inverter output an overload notice signal before<br />
tripping because of overload.<br />
You can use this function effectively to prevent the machine (e.g., a conveyor)driven by the inverter from<br />
being overloaded and prevent the conveyor from being stopped by the overload protection of the inverter.<br />
To use this function, assign function "03" (OK) or "26" (OL2) to one of the intelligent output terminals [11] to<br />
[15] (C021 to C025) and the alarm relay terminal (C026). (Two types of overload notice signal are available<br />
for output.)<br />
Item Function code Data or range of data Description<br />
Enabling the warning output during<br />
Overload signal output<br />
00<br />
C040<br />
acceleration, deceleration, and constant<br />
mode<br />
01 Enabling the warning output during constant<br />
0.0 Disabling the warning output<br />
Specifying the current at which to output the<br />
Overload level setting C041 0.1 to "2.0 x rated<br />
OL signal (overload notice advance signal<br />
current" (A)<br />
(1))<br />
0.0 Disabling the warning output<br />
Overload setting (2) C111 0.1 to "2.0 x rated<br />
current" (A)<br />
(NOTE) :applied for 75 to 150kW<br />
Overload restriction<br />
setting b022/b025<br />
Overload level setting<br />
C041/C111<br />
Specifying the current at which to output the<br />
OL2 signal (overload notice advance signal<br />
(2))<br />
Output current<br />
OL/OL2 output<br />
4.2.31 Overcurrent restraint<br />
Related code<br />
The overcurrent restraint function allows you to restrain the<br />
b027: Overcurrent suppression enable<br />
overcurrent that can occur when the output current sharply increases<br />
because of rapid acceleration.<br />
You can enable or disable the function by setting the overcurrent suppression enable (b027).<br />
Item Function code Data or range of data Description<br />
Overcurrent<br />
00 Disabling the overcurrent restraint<br />
b027<br />
suppression enable<br />
01 Enabling the overcurrent restraint<br />
Note: When using the inverter for a lift, disable the overcurrent restraint function. If the overcurrent<br />
restraint functions during the lift operation, the lift may slide down because of insufficient torque.<br />
4 - 41