Chapter 4 Explanation of Functions<br />

4.2.30 Overload restriction/overload notice<br />

(1) Overload restriction function<br />

- The overload restriction function allows you to make the<br />

inverter monitor the motor current during acceleration or<br />

constant-speed operation and automatically reduce the output<br />

frequency according to the deceleration rate at overload<br />

restriction when the motor current reaches the overload<br />

restriction level.<br />

- This function prevents the moment of inertia from excessively<br />

increasing during motor acceleration and prevents the inverter<br />

from tripping because of overcurrent, even when the load<br />

changes suddenly during the constant-speed operation of the<br />

motor.<br />

- You can specify two types of overload restriction operation by setting functional items "b021", "b022", and<br />

"b023" and functional items "b024", "b025", and "b026" separately.<br />

- To switch the overload restriction operation between the two settings (setting with b021, b022, and b023<br />

and setting with b024, b025, and b026), assign function "39" (OLR) to an intelligent input terminal. Turn the<br />

- OLR signal on and off to switch between the two settings.<br />

- The overload restriction level specifies the current at which to trigger the overload restriction function.<br />

- The deceleration rate at overload restriction specifies the length of time to decelerate the motor from the<br />

maximum frequency to 0 Hz.<br />

- When this function operates during deceleration, the acceleration time is prolonged over the set time.<br />

When you have selected the sensorless vector control, 0Hz-range sensorless vector control, or vector<br />

control with sensor as the V/F characteristic curve selection (see Section 4.2.18) and "03" for "b021" or<br />

"b024", the inverter output frequency increases if the current over the overload restriction level flows during<br />

the regenerative operation.<br />

If the value set as the deceleration rate at overload restriction (b023/b026) is too small, the inverter<br />

automatically decelerates the motor even during acceleration because of the overload restriction, and may<br />

trip because of the overvoltage caused by the energy regenerated by the motor.<br />

If this function operates during acceleration and the output frequency cannot reach the target frequency,<br />

try to make the following adjustments:<br />

- Increase the acceleration time. (See Section 4.2.8.)<br />

- Increase the torque boost setting. (See Section 4.2.19.)<br />

- Increase the overload restriction setting (b022/b025).<br />

Item Function code Data or range of data Description<br />

00 Disabling the overload restriction<br />

01<br />

Enabling the overload restriction during<br />

acceleration and constant-speed operation<br />

Overload<br />

Enabling the overload restriction during<br />

restriction<br />

b021/b024<br />

02<br />

constant-speed operation<br />

operation mode<br />

Enabling the overload restriction during<br />

03<br />

acceleration and constant-speed operation<br />

(increasing the frequency during regenerative<br />

operation)<br />

Overload<br />

restriction setting<br />

Deceleration rate<br />

at overload<br />

restriction<br />

b022/b025<br />

b023/b026<br />

"Rated current x 0.5" to<br />

"rated current<br />

x 2.0< x 1.8>" (A)<br />

0.1 to 30.0 (s)<br />

Current at which to trigger the overload restriction<br />

Deceleration time to be applied when the overload<br />

restriction operates<br />

Terminal function C001 to C008 39 Terminal to switch the overload restriction setting<br />

(NOTE):applied for 75 to 150kW<br />

Overload restriction level<br />

b022/b025<br />

Output current<br />

Related code<br />

b021: Overload restriction operation mode<br />

b022: Overload restriction setting<br />

b023: Deceleration rate at overload restriction<br />

b024: Overload restriction operation mode (2)<br />

b025: Overload restriction setting (2)<br />

b026: Deceleration rate at overload restriction (2)<br />

C001 to C008: Terminal [1] to [8] functions<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

C040: Overload signal output mode<br />

C041: Overload level setting<br />

C111: Overload setting (2)<br />

Deceleration according to the<br />

deceleration rate at overload<br />

restriction<br />

Maximum frequency<br />

A004/A204/A304<br />

Target frequency<br />

F001<br />

Inverter output<br />

frequency<br />

b023/b026<br />

4 - 40