Chapter 4 Explanation of Functions<br />

4.2.29 Electronic thermal protection<br />

The electronic thermal protection function allows you to protect<br />

the motor against overheating. Make settings of this function<br />

based on the rated current of the motor. The inverter will trip for<br />

overheat protection according to the settings.<br />

This function provides optimum overheat protection that is also<br />

designed with the lowering of the motor's cooling performance<br />

at low speeds in mind.<br />

You can configure this function so that the inverter outputs a<br />

warning signal before it trips for electronic thermal protection.<br />

(1) Electronic thermal level<br />

Item Function code Range of data Description<br />

Electronic thermal<br />

setting (calculated within<br />

the inverter from current<br />

output)<br />

b012/b212/b312<br />

(Example) Setting on the <strong>SJ700</strong>-150LFF(0.4-55kW)<br />

Rated current: 64 A<br />

Range of setting: 12.8 A (20%) to 64.0 A (100%)<br />

When 64 A is set as the electronic thermal setting (b012),<br />

the time-limit characteristic is as shown on the right.<br />

Trip time (s)<br />

"0.2 x rated current" to<br />

"1.0 x rated current"<br />

Trip time (s)<br />

Related code<br />

b012/b212/b312: Electronic thermal setting<br />

(calculated within the inverter from current output),<br />

1st/2nd/3rd motors<br />

b013/b213/b313: Electronic thermal characteristic,<br />

1st/2nd/3rd motors<br />

b015/b017/b019: Free setting, electronic thermal<br />

frequency (1) (2) (3)<br />

b016/b018/b020: Free setting, electronic thermal<br />

current (1) (2) (3)<br />

C021 to C025: Terminal [11] to [15] functions<br />

C026: Alarm relay terminal function<br />

C061: Electronic thermal warning level setting<br />

See the example below.<br />

(Example) Setting on the<br />

<strong>SJ700</strong>-750LFF(75-150kW)<br />

Rated current: 149 A<br />

Range of setting: 29.8 A (20%) to 149 A (100%)<br />

When 149 A is set as the electronic thermal setting<br />

(b012), the time-limit characteristic is as shown on the<br />

right.<br />

60<br />

3.0<br />

60<br />

0.5<br />

0 69.8 96 128<br />

(109%)(150%)<br />

(200%)<br />

Motor current (A)<br />

(Ratio to the rated<br />

current of inverter)<br />

0 158 223.5<br />

(106%) (150%)<br />

268<br />

(180%)<br />

Motor current (A)<br />

(Ratio to the rated<br />

current of inverter)<br />

(2) Electronic thermal characteristic<br />

The frequency characteristic set as the electronic thermal characteristic is integrated with the value of<br />

"b012", "b212", or "b312".<br />

The cooling-fan performance of a general-purpose motor lowers when the motor speed is low. So load<br />

(current) is decreased.<br />

The reduced-torque characteristic is designed to match the heat generation by <strong>Hitachi</strong>'s general-purpose<br />

motors.<br />

Item Function code Data Description<br />

00 Reduced-torque characteristic<br />

Electronic thermal<br />

b013/b213/b313 01 Constant-torque characteristic<br />

characteristic<br />

02 Free setting of electronic thermal characteristic<br />

4 - 37