Chapter 4 Explanation of Functions<br />

(3) Restarting methods<br />

- Restart with matching frequency<br />

The inverter detects the frequency and rotation direction based on the residual voltage in the motor,<br />

and then restarts the motor based on the detected frequency.<br />

- Restart with input frequency<br />

The inverter starts the output with the frequency specified for the start frequency selection (b030),<br />

searches for the point where the frequency and voltage are balanced while keeping the current at<br />

the restart current level (b028), and then restarts the motor.<br />

If the inverter trips when it restarts the motor in this way, reduce the setting of "b028".<br />

- After the inverter output has been shut off, the digital operator continues to display until<br />

the inverter restarts the motor operation.<br />

FW<br />

Output current<br />

Inverter output<br />

frequency<br />

Motor speed<br />

FRS<br />

b003<br />

b028<br />

Deceleration according to<br />

the setting of "b029"<br />

Frequency selected as the<br />

setting of "b030"<br />

4.2.28 Phase loss power input protection<br />

The phase loss power input protection function gives a warning when<br />

phase loss power is input to the inverter.<br />

Related code<br />

b006: Phase loss detection enable<br />

Item Function code Data Description<br />

Phase loss detection<br />

00 Disabling the protection<br />

b006<br />

enable<br />

01 Enabling the protection<br />

An phase loss power input may cause the following conditions, resulting in an inverter failure:<br />

(1) The ripple current increases in the main capacitor, and the capacitor life will be shortened significantly.<br />

(2) When the inverter is connected to a load, the internal converter or thyristor of the inverter may be<br />