fluorescent dimming systems |selection guide - Lutron
fluorescent dimming systems |selection guide - Lutron
fluorescent dimming systems |selection guide - Lutron
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
fl uorescent <strong>dimming</strong> <strong>systems</strong> | selection <strong>guide</strong><br />
July 2007<br />
<strong>Lutron</strong> | 1
<strong>Lutron</strong>® | fl uorescent <strong>dimming</strong> <strong>systems</strong><br />
Innovation and quality from the world leader in lighting controls.<br />
<strong>Lutron</strong> invented the world’s fi rst electronic<br />
<strong>dimming</strong> ballast over 30 years ago. From that<br />
point forward, <strong>Lutron</strong> has delivered value through<br />
a wide range of fl uorescent <strong>dimming</strong> options.<br />
<strong>Lutron</strong> offers an extensive selection of ballasts<br />
and controls, providing complete fl uorescent<br />
<strong>dimming</strong> <strong>systems</strong> to our customers.<br />
NEW Hi-lume® 3D digitally addressable <strong>dimming</strong> ballast<br />
2 | <strong>Lutron</strong>
<strong>Lutron</strong>’s fi rst principle:<br />
Taking care of you, our customer.<br />
Worldwide sales<br />
and service<br />
The <strong>Lutron</strong> Team is here to<br />
support you wherever and<br />
whenever you need us.<br />
Technical Support:<br />
24 Hours/7 Days<br />
1.800.523.9466<br />
Customer Service:<br />
8am-8pm ET<br />
1.888.LUTRON1<br />
Internet Support:<br />
www.lutron.com<br />
Commitment to innovation<br />
For over 45 years, <strong>Lutron</strong> has been dedicated to providing<br />
innovative products, services and technologies. We help you<br />
design, specify, and deliver the best performance, quality,<br />
and value to your customers.<br />
World-class quality<br />
<strong>Lutron</strong> quality is fueled by a relentless pursuit of the highest<br />
standards. Constant improvement includes an integrated<br />
quality system, strict engineering <strong>guide</strong>lines, and world-class<br />
quality and manufacturing processes.<br />
Comprehensive lighting control solutions<br />
<strong>Lutron</strong> is your comprehensive resource for lighting control<br />
solutions for any commercial or institutional application.<br />
Lighting Control Institute:<br />
1.610.282.6280<br />
Field Service:<br />
1.800.523.9466<br />
How to use this selection <strong>guide</strong>:<br />
The <strong>Lutron</strong> Fluorescent Dimming Systems Selection Guide helps you:<br />
• Determine the <strong>dimming</strong> range required for your application<br />
• Choose the appropriate <strong>Lutron</strong> <strong>dimming</strong> ballast<br />
• Choose your <strong>Lutron</strong> fl uorescent control<br />
In other sections of the Lighting Controls for Commercial<br />
Applications binder you will fi nd information on:<br />
• Architectural <strong>dimming</strong> <strong>systems</strong><br />
• Low-voltage switching <strong>systems</strong><br />
• Architectural <strong>dimming</strong> ballasts<br />
• Theatrical <strong>dimming</strong> capabilities<br />
• Integrated lighting<br />
automation <strong>systems</strong><br />
• Motorized window treatments<br />
• Floorplan based control software<br />
• Factory service plans<br />
<strong>Lutron</strong> | 01
<strong>Lutron</strong>® | table of contents<br />
Why dim fl uorescent 03<br />
<strong>Lutron</strong> quality 04<br />
Ballast control types 06<br />
Digitally addressable <strong>dimming</strong> ballasts 07<br />
Measured light vs. perceived light 08<br />
Dimming applications 09<br />
Benefi ts of 1% <strong>dimming</strong> 10<br />
Hi-lume® 1% 3-wire <strong>dimming</strong> ballasts 12<br />
Hi-lume® 3D 1% digital addressable <strong>dimming</strong> ballasts 14<br />
Compact SE 5% 3-wire <strong>dimming</strong> ballasts 16<br />
Tu-Wire® 5% 2-wire <strong>dimming</strong> ballasts 18<br />
EcoSystem 10% multi-input digital <strong>dimming</strong> ballasts 20<br />
Eco-10® 10% 3-wire <strong>dimming</strong> ballasts 22<br />
TVE 10% 0-10V <strong>dimming</strong> ballasts 24<br />
Select your <strong>dimming</strong> ballasts 26<br />
Ballast case dimensions 36<br />
Fluorescent <strong>dimming</strong> controls 38<br />
EcoSystem components 40<br />
Select your fl uorescent <strong>dimming</strong> controls 42<br />
Please see the <strong>Lutron</strong> Fluorescent<br />
Dimming Systems Technical Guide<br />
(P/N 366-606) for details on <strong>dimming</strong><br />
ballast installation, wiring, and other<br />
important information.<br />
See the <strong>Lutron</strong> EcoSystem Technical<br />
Guide (shown at right) (P/N 367-1028)<br />
for detailed information on EcoSystem<br />
light control solution.<br />
02 | <strong>Lutron</strong>
<strong>Lutron</strong>® | why dim fl uorescent<br />
The benefi ts of <strong>dimming</strong><br />
Create enticing ambiance<br />
Dimming creates a rich visual experience and adds<br />
fl exibility to any room, providing the right lighting<br />
environment for a variety of activities.<br />
Save electricity, maintain lamp life, and<br />
save the environment<br />
Dimming saves electricity and reduces the demand on<br />
HVAC <strong>systems</strong>. Dimming fl uorescent lighting instead<br />
of repeated switching helps to maintain lamp life.<br />
Give employees greater personal control<br />
Allowing employees to set preferred light levels<br />
for specifi c tasks results in greater employee<br />
comfort and improved performance.<br />
Combine lighting control strategies to<br />
enhance building performance<br />
Using occupancy sensors, daylight sensors and time<br />
clocks with fl uorescent <strong>dimming</strong> can help manage<br />
the lighting in an entire building and further reduce<br />
electric demand.<br />
Dimming fl uorescents saves energy<br />
Fluorescent lighting uses much less power<br />
than incandescent lighting. In a typical<br />
installation, a 32 watt compact fl uorescent<br />
lamp provides approximately the same light<br />
output as a 100 watt incandescent lamp.<br />
As both sources are dimmed, fl uorescent<br />
lamps continue to be a more energy<br />
effi cient light source.<br />
100W<br />
Power consumed by incandescent source<br />
Power<br />
80<br />
60<br />
40<br />
Over 60 watts of power<br />
is saved per fi xture by using<br />
fl uorescent lamps<br />
Power consumed by fl uorescent source<br />
20<br />
0<br />
0 20 40 60 80 100%<br />
Measured Light<br />
<strong>Lutron</strong> | 03
<strong>Lutron</strong>® | quality<br />
Superior components<br />
<strong>Lutron</strong> ballasts are manufactured to the highest<br />
level of quality, using carefully selected components.<br />
Maximum ballast lifetime is achieved by using only<br />
long-life components with signifi cant performance<br />
history. In many cases, <strong>Lutron</strong> works with component<br />
suppliers to design custom parts in order to improve<br />
overall ballast quality.<br />
Additionally, <strong>Lutron</strong> uses only metal ballast<br />
enclosures, allowing for optimal heat transfer<br />
to the lighting fi xture.<br />
Thermal Foldback<br />
<strong>Lutron</strong>’s patented Thermal Foldback technology<br />
is included in high-power ballasts, and actively<br />
monitors the ballast temperature. Power delivery<br />
to the lamps is automatically reduced, or “folded<br />
back”, to regulate ballast temperature, with minimal<br />
impact on light output. Thermal Foldback is designed<br />
to activate only if the ballast calibration point exceeds<br />
its rating. This maintains the ballast temperature to<br />
within 5ºC of its rating, preventing premature ballast<br />
failure from overheating. In a properly designed<br />
application, Thermal Foldback will not engage.<br />
Refer to Fluorescent Dimming Systems Technical<br />
Guide P/N 366-606 for information about proper<br />
installation and the calibration point.<br />
04 | <strong>Lutron</strong>
Failure Rate<br />
100% Test<br />
<strong>Lutron</strong> tests the performance of every ballast prior to<br />
shipment. This important step eliminates ballasts that<br />
do not meet specifi cations.<br />
100% Burn-in<br />
<strong>Lutron</strong> “burns in” every ballast prior to shipment.<br />
Defects due to faulty components are screened<br />
out in this process, resulting in a dramatic reduction<br />
of early failures in the fi eld.<br />
Extending ballast lifetime<br />
All electronic ballasts use components with a fi nite<br />
lifetime. A major factor for ballast lifetime is operating<br />
temperature. <strong>Lutron</strong> <strong>dimming</strong> ballasts are designed<br />
to maximize ballast lifetime.<br />
You have an opportunity to extend the lifetime of the<br />
ballast even further by designing or choosing fi xtures<br />
that operate the ballast at a lower temperature. For<br />
every 10ºC reduction in ballast case temperature,<br />
the ballast lifetime will be doubled.<br />
Customer receives<br />
<strong>Lutron</strong> ballast<br />
Low<br />
failure rate<br />
Useful life<br />
Running ballasts 10˚C Cooler<br />
DOUBLES useful life<br />
<strong>Lutron</strong> test<br />
and burn-in<br />
Product reliability curve<br />
<strong>Lutron</strong> <strong>dimming</strong> ballasts are burnt in prior to<br />
shipment, ensuring lower failure rate in the fi eld.<br />
Running ballasts 10ºC cooler can also double<br />
their useful life.<br />
Time<br />
Dimming by <strong>Lutron</strong>® OEM Program<br />
<strong>Lutron</strong> offers on-site factory training to OEM fi xture<br />
manufacturers through the Dimming by <strong>Lutron</strong> OEM<br />
Program. Additionally, the program allows OEM<br />
fi xture manufacturers to work together with <strong>Lutron</strong><br />
to grow sales, strengthen customer loyalty and<br />
satisfaction, and differentiate products. Doing<br />
business with <strong>Lutron</strong> has never been easier.<br />
For more information on the Dimming by<br />
<strong>Lutron</strong> OEM Program, please visit<br />
www.lutron.com/OEM.<br />
<strong>Lutron</strong> | 05
<strong>Lutron</strong>® | ballast control types<br />
In addition to offering ballasts with different low-end<br />
<strong>dimming</strong> levels, <strong>Lutron</strong> offers <strong>dimming</strong> ballasts with<br />
a variety of industry-standard control options.<br />
Hot<br />
Dimmed Hot<br />
Neutral<br />
3-wire<br />
3-wire control is a line-voltage phase-control <strong>dimming</strong> method.<br />
Along with Hot and Neutral, the <strong>dimming</strong> signal is communicated<br />
via a third wire called Dimmed Hot. All three wires are rated Class 1<br />
and can be run within the same conduit. 3-wire control is stable over<br />
long wire runs, allows for maximum circuit loading, and is very easy<br />
to wire.<br />
Dimmed Hot<br />
Neutral<br />
2-wire<br />
2-wire control is a line-voltage phase-control <strong>dimming</strong> method.<br />
The ballast receives the <strong>dimming</strong> signal through the Dimmed Hot<br />
wire. Intended for small-scale retrofi t applications, the 2-wire control<br />
method is often the easiest way to implement <strong>dimming</strong> in existing<br />
fl uorescent fi xtures.<br />
Hot<br />
Neutral<br />
Control (+)<br />
Control (–)<br />
0-10V<br />
0-10V control is a low-voltage DC <strong>dimming</strong> method. Power<br />
wires are rated Class 1 and control wires are rated Class 2.<br />
This separation allows multiple circuits to use the same <strong>dimming</strong><br />
signal without additional power equipment. 0-10V control is not<br />
recommended for <strong>dimming</strong> below 10%, as fi xture-to-fi xture<br />
tracking can be signifi cantly affected by control wire length.<br />
Hot<br />
Neutral<br />
Control<br />
Control<br />
Multi-input digital<br />
Multi-input digital control is a wired communication technology that<br />
facilitates individual ballast addressing, connection of multiple control<br />
devices, and control of ballasts individually or in groups. The digital<br />
wires are polarity insensitive and may be wired in any topology. Digital<br />
communication wires may be run with the mains voltage (Class 1) or<br />
isolated from mains (Class 2). Multi-input digital control allows for the<br />
quick connection of devices and re-confi gurability.<br />
06 | <strong>Lutron</strong>
<strong>Lutron</strong>® | digitally addressable <strong>dimming</strong> ballasts<br />
A revolution in light control for<br />
open offi ces and classrooms<br />
A breakthrough in fl uorescent lighting control,<br />
multi-input digital control solutions start with a<br />
simple but essential building block–a digitally<br />
addressable <strong>dimming</strong> ballast–which replaces a<br />
non-dim ballast in a fi xture. Hi-lume® 3D and<br />
EcoSystem are examples of digitally addresable<br />
ballasts. Benefi ts:<br />
Simple to design<br />
• Fewer components<br />
• Can be wired topology- and polarity-free<br />
• No interfaces required<br />
Easy to maintain<br />
• No reprogramming when components are replaced<br />
• Infi nite re-confi gurability without Class 1 rewiring<br />
Cost effective<br />
• Costs less than other solutions available today<br />
• Fewer parts and pieces to install<br />
For details on Hi-Lume 3D,<br />
visit www.lutron.com/3d.<br />
For details on Ecosystem,<br />
visit www.lutron.com/ecosystem.<br />
<strong>Lutron</strong> | 07
<strong>Lutron</strong>® | measured light vs. perceived light<br />
The human eye responds to low light levels by<br />
enlarging the pupil, allowing more light to enter the<br />
eye. This response results in a difference between<br />
measured and perceived light levels. A lamp<br />
that is dimmed to 10% of its maximum measured<br />
light output is perceived as being dimmed to<br />
only 32%. Likewise, a lamp dimmed to 1%<br />
is perceived to be at 10%.<br />
1% Architectural <strong>dimming</strong><br />
5% High performance <strong>dimming</strong><br />
100%<br />
10% Lighting management <strong>dimming</strong><br />
90<br />
80<br />
70<br />
Measured<br />
Light<br />
60<br />
50<br />
40<br />
30<br />
20<br />
10<br />
5<br />
1<br />
0 10 22 32 40 50 60 70 80 90 100%<br />
Perceived Light<br />
Formula:<br />
Perceived Light (%) = 100 x<br />
Measured Light (%)<br />
100<br />
Source: IESNA Lighting Handbook, 9th Edition, (New York: IESNA, 2000), 27-4.<br />
08 | <strong>Lutron</strong>
<strong>Lutron</strong>® | <strong>dimming</strong> applications<br />
1%<br />
Architectural <strong>dimming</strong><br />
5%<br />
High performance <strong>dimming</strong><br />
10%<br />
Lighting management <strong>dimming</strong><br />
• Conference room/Boardroom<br />
• Lecture hall<br />
• Patient room/Examination<br />
and treatment room<br />
• House of worship<br />
• Theater<br />
• Convention area<br />
• Restaurants<br />
• Air traffi c control center<br />
• Industrial control room<br />
• Partitioned meeting room<br />
• Graphic art workstation<br />
• CAD/CAM workstation<br />
• Private offi ce<br />
• Retail<br />
• Presentation spaces<br />
• Critical task spaces<br />
• Small meeting room<br />
• Lobby<br />
• Hotel guest room<br />
• Residential (See page 28 for<br />
appropriate ballast types.)<br />
• Large open offi ce<br />
• Corridor/Stairwell<br />
• Utility room<br />
• Restroom<br />
• Customer service area/<br />
Call center<br />
• Classroom<br />
Design example<br />
At full brightness, the measured light in a space is 60 foot-candles.<br />
At the lowest dimmed level, 10% perceived light is desired.<br />
1% measured light (0.6 fcd)<br />
is perceived as 10%<br />
(desired result)<br />
5% measured light (3 fcd)<br />
is perceived as 22%<br />
(2x brighter than desired)<br />
10% measured light (6 fcd)<br />
is perceived as 32%<br />
(3x brighter than desired)<br />
<strong>Lutron</strong> | 09
<strong>Lutron</strong>® | benefi ts of 1% <strong>dimming</strong><br />
Architectural <strong>dimming</strong><br />
Architectural spaces often have a strong<br />
focus on aesthetics and comfort, creating an<br />
environment that portrays class and distinction.<br />
Architects and designers create these spaces<br />
for maximum versatility and require subtle<br />
control of the lighting. At <strong>Lutron</strong>, we design<br />
fl uorescent <strong>dimming</strong> ballasts to respond<br />
to the fi nest lighting adjustments required.<br />
Hi-lume® <strong>dimming</strong> ballasts allow control<br />
of your fl uorescent lights through full-range<br />
100% to 1% light output, providing the<br />
greatest available functionality for architectural<br />
fl uorescent lighting.<br />
10 | <strong>Lutron</strong><br />
Photograph © Nikolas Koenig.<br />
Architect: Richard Meyer & Partners, Architects.<br />
Lighting design: L’Observatoire International.
Hi-lume® | 1%<br />
Hi-lume 1% applications<br />
For years, 1% <strong>dimming</strong> has been the standard<br />
for conference room lighting. 1% CFL (compact<br />
fl uorescent lamps) <strong>dimming</strong> has opened up new<br />
areas for fl uorescents, giving required performance<br />
while meeting strict energy codes.<br />
In restaurants, combining Hi-lume with inviting,<br />
colored refl ectors creates a warm and intimate<br />
atmosphere for distinctive dining.<br />
Patient care areas need dimmed lights at<br />
night, but require bright light and true color<br />
rendering for accurate medical examinations.<br />
Fluorescent sources, with their consistent<br />
color temperature throughout the <strong>dimming</strong><br />
range, are an ideal source.<br />
Partitioned spaces, like conference rooms<br />
or ballrooms, require 1% <strong>dimming</strong> for specifi c<br />
tasks, allowing for a variety of activities to use<br />
the same space.<br />
Restaurants<br />
Patient<br />
Care Areas<br />
Photograph © Nikolas Koenig.<br />
Partitioned Spaces<br />
<strong>Lutron</strong> | 11
<strong>Lutron</strong>® | 1% architectural <strong>dimming</strong><br />
Hi-lume®<br />
Experience the benefi ts of true full-range 100%<br />
to 1% fl uorescent <strong>dimming</strong>. Designed to meet<br />
the most demanding lighting requirements,<br />
Hi-lume ballasts enable you to provide the<br />
ideal visual environment for any application.<br />
The Hi-lume family is extensive, featuring the<br />
world’s only 100% to 1% <strong>dimming</strong> ballasts<br />
for T4 compact fl uorescent lamps. Integrating<br />
Hi-lume 1% technology into your designs<br />
affords you full control over the lighting<br />
in any space.<br />
For maximum fl exibility, <strong>Lutron</strong> offers a<br />
full line of Hi-lume ballasts that are compatible<br />
with 3-wire and digital controls.<br />
Photograph © Kerun Ip,<br />
courtesy of Pei Partnership Architects.<br />
<strong>Lutron</strong> ballasts are tested for performance<br />
with Philips®, Sylvania®, and GE® lamps.<br />
For the complete listing of Hi-lume ballasts<br />
by <strong>Lutron</strong>, please see pages 26-29.<br />
• Dims T5-HO linear lamps<br />
• Hi-lume 3D Dims T8 Linear and<br />
T8 U-bent<br />
• Just 1” high x 1.18” wide<br />
• Color-keyed push-in connectors<br />
12 | <strong>Lutron</strong><br />
• Dims T8 linear and<br />
U-bent lamps<br />
• Dims T4 triple-tube<br />
compact lamps<br />
• Slim-profi le design–just 1” high<br />
• Color-keyed push-in connectors<br />
• Available with or without<br />
mounting studs
Hi-lume® | 1%<br />
Performance<br />
• Continuous, fl icker-free <strong>dimming</strong><br />
from 100% to 1%<br />
• Models available for T4 triple-tube CFL,T5-<br />
HO, and T8 lamps<br />
• 3-wire line voltage control for consistent fi x-<br />
ture-to-fi xture <strong>dimming</strong><br />
• Lamps turn on at any dimmed level without<br />
fl ashing to full brightness<br />
• Low harmonic distortion<br />
• Miswire protection<br />
• Slim-profi le and standard designs available<br />
• 100% performance tested<br />
• Ultra-quiet operation<br />
• Designed in the USA<br />
• 5-year warranty (limited) with fi eld service<br />
commissioning (3-year warranty standard)<br />
Specifications<br />
• Architectural <strong>dimming</strong> from 100% to 1% relative<br />
light output<br />
• No visible fl icker<br />
• Total Harmonic Distortion (THD) less than 10%<br />
• Power factor greater than .95<br />
• Ballast factor greater than .85 for T8 lamps<br />
• Ballast factor greater than .95 for T4 lamps<br />
• Ballast factor equal to 1.0 for T5-HO lamps<br />
• Frequency of operation greater than 25 kHz for T8<br />
lamps<br />
• Frequency of operation greater than 42 kHz for T4<br />
and T5-HO lamps<br />
• Inaudible in 27 dBA ambient environment<br />
• Inrush current limiting circuitry built-in (maximum of<br />
7 amps for 120V and 3 amps at 277V)<br />
• Internal fusing<br />
• Minimum lamp starting temperature 10°C (50°F)<br />
• Maximum ballast case temperature 75°C (167°F)<br />
3-wire control<br />
For the full offering of Hi-lume <strong>dimming</strong> ballast controls by<br />
<strong>Lutron</strong>, please see pages 42 and 43.<br />
Hot<br />
Control<br />
Hot<br />
120/277VAC<br />
60Hz Feed<br />
Neutral<br />
Dimmed Hot<br />
Neutral<br />
Dimming<br />
Ballast<br />
<strong>Lutron</strong> | 13
<strong>Lutron</strong>® | 1% architectural <strong>dimming</strong><br />
Hi-lume® 3D<br />
Hi-lume 3D is a high-performance, energy-effi cient<br />
<strong>dimming</strong> ballast for demanding architectural<br />
applications. Hi-lume 3D is the world’s fi rst<br />
fl uorescent <strong>dimming</strong> ballast that can dim lights<br />
to less than 1% and more than 100% of rated<br />
lamp illumination for the most demanding lighting<br />
requirements. With Hi-lume 3D you get the highest<br />
performance fl uorescent <strong>dimming</strong> with the same<br />
effi ciency as non-dim ballasts.<br />
Hi-lume 3D is ideal for:<br />
• Ballrooms<br />
• Conference rooms<br />
• Critical task applications<br />
• Presentation spaces<br />
• Lobbies<br />
• Control rooms<br />
• Classrooms<br />
3 Dimensions of innovation<br />
Performance: broadest <strong>dimming</strong> range, 100% to<br />
0.7% of full light output.<br />
Versatility: compatible with a broad range of 3-wire<br />
controls and digital controls (EcoSystem /DALI). Plus,<br />
universal voltage input and small 1” high profi le to fi t<br />
any fi xture.<br />
Efficiency: industry-leading ballast effi cacy of up to<br />
91 lumens per watt.<br />
For the complete listing of Hi-lume® 3D ballasts<br />
by <strong>Lutron</strong>, please see page 30.<br />
• Dims T8 linear and U-bent lamps<br />
• Slim-profi le design–just 1” high x 1.18” wide<br />
14 | <strong>Lutron</strong>
Hi-lume® 3D | 1%<br />
Performance<br />
• Continuous, fl icker-free <strong>dimming</strong> down to<br />
0.7% of full light output<br />
• Models available for T8 lamps<br />
• EcoSystem digital bus control<br />
• Digital inputs allow for rezoning without rewiring<br />
• Lamps turn on at any dimmed level without<br />
fl ashing to full brightness<br />
• Low harmonic distortion<br />
• Miswire protection<br />
• Meets FCC Part 18 Non-Consumer requirements<br />
for EMI/RFI emissions<br />
• 100% performance tested<br />
• Ultra-quiet operation<br />
Specifications<br />
• No visible fl icker<br />
• Total Harmonic Distortion (THD) less than 10%<br />
• Power factor greater than .95<br />
• Frequency of operation greater than 42 kHz<br />
• Inaudible in 27 dBA ambient environment<br />
• Inrush current limiting circuitry built-in (maximum of<br />
7 amps for 120V and 3 amps at 277V)<br />
• Internal fusing<br />
• Minimum lamp starting temperature 10°C (50°F)<br />
• Maximum ballast case temperature 75°C (167°F)<br />
• Universal input voltage 120V/277V<br />
• Available in 1.0 and 1.17 ballast factor<br />
• Designed in the USA<br />
• 5-year warranty (limited) with fi eld service<br />
commissioning (3-year warranty standard)<br />
Multi-input digital control<br />
For the full offering of Hi-lume 3D <strong>dimming</strong> ballast<br />
controls by <strong>Lutron</strong>, please see page 42 and 43.<br />
Hot<br />
Neutral<br />
Dimming<br />
Ballast<br />
E1*<br />
E2*<br />
or<br />
Hot<br />
Dimmed Hot<br />
Neutral<br />
* To other ballasts and digital bus control<br />
<strong>Lutron</strong> | 15
<strong>Lutron</strong>® | 5% high performance <strong>dimming</strong><br />
Compact SETM<br />
For designs requiring the energy savings<br />
and aesthetic appeal of dimmed compact<br />
fl uorescent lamps, Compact SE <strong>dimming</strong><br />
ballasts are your solution. The Compact SE<br />
product family includes ballasts for nearly<br />
every type of compact fl uorescent lamp.<br />
Compact SE <strong>dimming</strong> ballasts deliver<br />
high performance 100% to 5% <strong>dimming</strong>,<br />
making them ideal for use in a variety of<br />
applications. In addition, Compact SE<br />
ballasts are compatible with the full line<br />
of 3-wire controls by <strong>Lutron</strong>.<br />
For the complete listing of Compact SE<br />
ballasts by <strong>Lutron</strong>, please see pages 26-29.<br />
Photograph © Kerun Ip,<br />
courtesy of Pei Partnership Architects.<br />
• Dims T5 twin-tube lamps<br />
16 | <strong>Lutron</strong><br />
• Dims T4 quad- and triple-tube<br />
compact lamps<br />
• Slim-profi le design–just 1” high<br />
• Color-keyed push-in connectors<br />
• Available with or without mounting studs
Compact SETM |<br />
5%<br />
Performance<br />
• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />
to 5% (for 1% <strong>dimming</strong> of compact fl uorescent<br />
lamps, see page 12)<br />
• 3-wire line voltage control for consistent fi x-<br />
ture-to-fi xture <strong>dimming</strong><br />
• Lamps turn on at any dimmed level without<br />
fl ashing to full brightness<br />
• Low harmonic distortion<br />
• Miswire protection<br />
• Slim-profi le design<br />
• 100% performance tested<br />
• Ultra-quiet operation<br />
• Designed in the USA<br />
• 5-year warranty (limited) with fi eld service<br />
commissioning (3-year warranty standard)<br />
Specifications<br />
• High performance <strong>dimming</strong> from 100% to 5%<br />
relative light output<br />
• No visible fl icker<br />
• Total Harmonic Distortion (THD) less than 10%<br />
• Power factor greater than .95<br />
• Ballast factor greater than .85 for<br />
T5 twin-tube lamps<br />
• Ballast factor greater than .95 for T4 quadand<br />
triple-tube compact lamps<br />
• Frequency of operation greater than 27 kHz for<br />
T5 twin-tube lamps<br />
• Frequency of operation greater than 42 kHz for<br />
T4 quad- and triple-tube compact lamps<br />
• Inaudible in 27 dBA ambient environment<br />
• Inrush current limiting circuitry built-in (maximum<br />
of 7 amps for 120V and 3 amps at 277V)<br />
• Internal fusing<br />
• Minimum lamp starting temperature 10°C (50°F)<br />
• Maximum ballast case temperature 75°C (167°F)<br />
3-wire control<br />
For the full offering of Compact SE <strong>dimming</strong> ballast controls<br />
by <strong>Lutron</strong>, please see pages 42 and 43.<br />
Hot<br />
Control<br />
Hot<br />
120/277VAC<br />
60Hz Feed<br />
Neutral<br />
Dimmed Hot<br />
Neutral<br />
Dimming<br />
Ballast<br />
<strong>Lutron</strong> | 17
<strong>Lutron</strong>® | 5% high performance <strong>dimming</strong><br />
Tu-Wire ®<br />
Retrofi t and small-space applications can<br />
benefi t from the ease of installation offered<br />
by <strong>Lutron</strong> Tu-Wire <strong>dimming</strong> ballasts.<br />
Tu-Wire ballasts offer high performance<br />
100% to 5% <strong>dimming</strong> for linear and<br />
compact fl uorescent lamps.<br />
Tu-Wire ballasts require only two wires<br />
(hot and neutral) for power and control.<br />
<strong>Lutron</strong> offers a wide range of compatible<br />
2-wire controls, making Tu-Wire a perfect<br />
choice for many applications. Additionally,<br />
one-lamp T4 models have been designed to<br />
meet FCC Part 18 consumer requirements.<br />
For the complete listing of Tu-Wire ballasts<br />
by <strong>Lutron</strong>, please see page 32.<br />
Interiors by Staffelbach<br />
Design Associates.<br />
• Dims T8 lamps<br />
• Slim-profi le design–just 1” high x 1.18” wide<br />
• Color-keyed push-in connectors<br />
18 | <strong>Lutron</strong><br />
• Dims T4 quad- and triple-tube<br />
compact lamps<br />
• Slim-profi le design–just 1” high<br />
• Color-keyed push-in connectors<br />
• Available with or without mounting studs
Tu-Wire ® | 5%<br />
Performance<br />
• Continuous, fl icker-free <strong>dimming</strong> from<br />
100% to 5%<br />
• 2-wire line voltage control for<br />
retrofi t applications<br />
• Lamps turn on at any dimmed level without<br />
fl ashing to full brightness<br />
• Low harmonic distortion<br />
• Slim-profi le design<br />
• One-lamp T4 models meet FCC Part 18<br />
consumer requirements for residential use<br />
(FCC ID: JPZB001)<br />
• 100% performance tested<br />
• Ultra-quiet operation<br />
• Designed in the USA<br />
• 5-year warranty (limited) with fi eld service<br />
commissioning (3-year warranty standard)<br />
Specifications<br />
• High performance <strong>dimming</strong> from 100% to 5%<br />
relative light output<br />
• No visible fl icker<br />
• Total Harmonic Distortion (THD) less than 20%<br />
• Power factor greater than .95<br />
• Ballast factor greater than .85 for T4 lamps<br />
• Ballast factor equal to 1.0 for T8 lamps<br />
• Frequency of operation greater than 42 kHz<br />
• Inaudible in 27 dBA ambient environment<br />
• Inrush current limiting circuitry built-in (maximum of<br />
7 amps inrush current per ballast)<br />
• Internal fusing<br />
• Minimum lamp starting temperature 10°C (50°F)<br />
• Maximum ballast case temperature 75°C (167°F)<br />
2-wire control<br />
For the full offering of Tu-Wire <strong>dimming</strong> ballast controls by<br />
<strong>Lutron</strong>, please see page 44.<br />
Hot<br />
Control<br />
Dimmed Hot<br />
120VAC<br />
60Hz Feed<br />
Neutral<br />
Neutral<br />
Dimming<br />
Ballast<br />
<strong>Lutron</strong> | 19
<strong>Lutron</strong>® | 10% lighting management <strong>dimming</strong><br />
EcoSystemTM<br />
EcoSystem devices employ revolutionary<br />
technology allowing each device to listen, think,<br />
decide and remember. EcoSystem fl uorescent<br />
lighting control solutions create fl uorescent lighting<br />
control <strong>systems</strong> with a simple building block<br />
architecture of EcoSystem fl uorescent <strong>dimming</strong><br />
ballasts, EcoSystem sensors, and EcoSystem<br />
controls, free from interfaces and power packs.<br />
EcoSystem fl uorescent solutions redefi ne<br />
fl uorescent lighting control as easy to design,<br />
easy to install, easy to maintain and cost effective.<br />
For the complete listing of EcoSystem<br />
ballasts by <strong>Lutron</strong>, please see<br />
pages 34 and 35.<br />
• Dims T8 linear and U-bent, T5 linear, and<br />
T5-HO linear lamps<br />
• Slim-profi le design–just 1” high x 1.18” wide<br />
• Color-keyed push-in connections<br />
• Dims T8 linear and U-bent lamps<br />
• Color-keyed push-in connectors<br />
with or without leads<br />
20 | <strong>Lutron</strong>
EcoSystemTM | 10%<br />
Performance<br />
• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />
to 10%<br />
• Models available for T5, T5-HO, and T8 lamps<br />
• Multi-input digital control<br />
• Digital inputs allow for rezoning without rewiring<br />
• High effi ciency–up to 92 lumen per watt<br />
• Lamps turn on at any dimmed level without<br />
fl ashing to full brightness<br />
• Low harmonic distortion<br />
• Miswire protection<br />
• Slim-profi le and standard designs available<br />
• Meets FCC Part 18 Non-Consumer requirements<br />
for EMI/RFI emissions<br />
• 100% performance tested<br />
• Ultra-quiet operation<br />
• Designed in the USA<br />
• 5-year warranty (limited) with fi eld service<br />
commissioning (3-year warranty standard)<br />
Specifications<br />
• Lighting management <strong>dimming</strong> from 100% to 10%<br />
relative light output<br />
• No visible fl icker<br />
• Total Harmonic Distortion (THD) less than 20%<br />
• Power factor greater than .95<br />
• Ballast factor greater than .85 for T8 lamps<br />
• Ballast factor equal to 1.0 for T5 and T5-HO lamps<br />
• Frequency of operation greater than 42 kHz<br />
• Inaudible in 27 dBA ambient environment<br />
• Inrush current limiting circuitry built-in (maximum of<br />
7 amps for 120V and 3 amps at 277V)<br />
• Internal fusing<br />
• Minimum lamp starting temperature 10°C (50°F)<br />
• Maximum ballast case temperature 75°C (167°F)<br />
Multi-input digital control<br />
For the full offering of EcoSystem <strong>dimming</strong> ballast<br />
controls by <strong>Lutron</strong>, please see page 45.<br />
Hot<br />
Neutral<br />
Dimming<br />
Ballast<br />
E1*<br />
E2* Sensors<br />
* To other ballasts and digital bus control<br />
<strong>Lutron</strong> | 21
<strong>Lutron</strong>® | 10% lighting management <strong>dimming</strong><br />
Eco-10®<br />
To maximize the benefi ts of a lighting<br />
management system, use Eco-10 <strong>dimming</strong><br />
ballasts by <strong>Lutron</strong>. Eco-10 offers 100%<br />
to 10% <strong>dimming</strong>, and is ideal for use in any<br />
space where saving energy is the primary<br />
goal, and critical performance is secondary.<br />
Eco-10 ballasts are available for a large<br />
range of lamps, making them an ideal<br />
choice for applications with many different<br />
fi xture types. In addition, Eco-10 ballasts<br />
are fully compatible with <strong>Lutron</strong>’s complete<br />
line of 3-wire fl uorescent controls.<br />
For the complete listing of Eco-10 ballasts<br />
by <strong>Lutron</strong>, please see pages 26-29.<br />
Photograph © Peter Aaron/Esto.<br />
Architect: Robert A.M. Stern Architects.<br />
• Dims T5 twin-tube lamps<br />
22 | <strong>Lutron</strong><br />
• Dims T8 linear and U-bent, T5 linear, and<br />
T5-HO linear lamps<br />
• Dims 2’ and 3’ T5 lamps<br />
• Slim-profi le design–just 1” high x 1.18” wide<br />
• Color-keyed push-in connectors
Eco-10® | 10%<br />
Performance<br />
• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />
to 10%<br />
• 3-wire line-voltage control for consistent<br />
fi xture-to-fi xture <strong>dimming</strong><br />
• Lamps turn on at any dimmed level without<br />
fl ashing to full brightness<br />
• Low harmonic distortion<br />
• Slim-profi le and standard designs available<br />
• 100% performance tested<br />
• Ultra-quiet operation<br />
• Designed in the USA<br />
• 5-year warranty (limited) with fi eld service<br />
commissioning (3-year warranty standard)<br />
Specifications<br />
• Lighting management <strong>dimming</strong> from 100% to 10%<br />
relative light output<br />
• No visible fl icker<br />
• Total Harmonic Distortion (THD) less than 20%<br />
• Power factor greater than .95<br />
• Ballast factor greater than .85 for T8 lamps and T5<br />
twin-tube lamps<br />
• Ballast factor equal to 1.0 for T5 and T5-HO lamps<br />
• Frequency of operation greater than 25 kHz for T8<br />
lamps and T5 twin-tube lamps<br />
• Frequency of operation greater than 42 kHz for T5<br />
and T5-HO lamps<br />
• Inaudible in 27 dBA ambient environment<br />
• Inrush current limiting circuitry built-in (maximum of<br />
7 amps for 120V and 3 amps at 277V)<br />
• Internal fusing<br />
• Minimum lamp starting temperature 10°C (50°F)<br />
• Maximum ballast case temperature 75°C (167°F)<br />
3-wire control<br />
For the full offering of Eco-10 <strong>dimming</strong> ballast controls<br />
by <strong>Lutron</strong>, please see pages 42 and 43.<br />
Hot<br />
Control<br />
Hot<br />
120/277VAC<br />
60Hz Feed<br />
Neutral<br />
Dimmed Hot<br />
Neutral<br />
Dimming Ballast<br />
<strong>Lutron</strong> | 23
<strong>Lutron</strong>® | 10% lighting management <strong>dimming</strong><br />
TVETM<br />
For applications requiring the use of 0-10V<br />
control, <strong>Lutron</strong> offers the TVE family of<br />
fl uorescent <strong>dimming</strong> ballasts. TVE ballasts<br />
are designed to work seamlessly with<br />
0-10V lighting management <strong>systems</strong>,<br />
including daylight harvesting and<br />
occupancy detection schemes.<br />
<strong>Lutron</strong> offers many choices for 0-10V<br />
controls, including interfaces to many of<br />
our <strong>dimming</strong> <strong>systems</strong>.<br />
For the complete listing of TVE ballasts<br />
by <strong>Lutron</strong>, please see page 33.<br />
• Dims T8 linear and U-bent lamps<br />
• 0-10V control<br />
• 347V ballasts available<br />
24 | <strong>Lutron</strong>
TVETM | 10%<br />
Performance<br />
• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />
to 10%<br />
• 0-10V control<br />
• Lamps turn on at any dimmed level without<br />
fl ashing to full brightness<br />
• Low harmonic distortion<br />
• 100% performance tested<br />
• Ultra-quiet operation<br />
• Designed in the USA<br />
• 5-year warranty (limited) with fi eld service<br />
commissioning (3-year warranty standard)<br />
Specifications<br />
• Lighting management <strong>dimming</strong> from 100% to 10%<br />
relative light output<br />
• No visible fl icker<br />
• Total Harmonic Distortion (THD) less than 20%<br />
• Power factor greater than .95<br />
• Ballast factor greater than .85<br />
• Frequency of operation greater than 25 kHz<br />
• Inaudible in 27 dBA ambient environment<br />
• Inrush current limiting circuitry built-in (maximum of<br />
7 amps for 120V, 3 amps for 277V and 347V)<br />
• Internal fusing<br />
• Minimum lamp starting temperature 10°C (50°F)<br />
• Maximum ballast case temperature 75°C (167°F)<br />
0-10V control<br />
For the full offering of TVE <strong>dimming</strong> ballast controls by<br />
<strong>Lutron</strong>, please see page 45.<br />
Hot<br />
120/277/347VAC<br />
60Hz Feed<br />
Control*<br />
Hot<br />
Neutral<br />
Control (+)<br />
Control (–)<br />
Neutral<br />
* Based on control being used, wiring method may differ.<br />
Dimming Ballast<br />
<strong>Lutron</strong> | 25
<strong>Lutron</strong>® | Hi-lume®, Compact SE , Eco-10®<br />
120 volt 3-wire <strong>dimming</strong> ballasts<br />
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
1% Dimming<br />
Hi-lume<br />
5% Dimming<br />
10% Dimming<br />
Eco-10<br />
Ballast<br />
Current 2<br />
– Amps<br />
T5 Linear<br />
14W<br />
(22”)<br />
1<br />
2<br />
C 3 —<br />
C 3 —<br />
E 3 T514 C 120 1<br />
E 3 T514 C 120 2<br />
.17<br />
.32<br />
5/8” Dia 21W<br />
(34”)<br />
1<br />
2<br />
C 3 —<br />
C 3 —<br />
E 3 T521 C 120 1<br />
E 3 T521 C 120 2<br />
.25<br />
.43<br />
28W<br />
(45”)<br />
1<br />
2<br />
C 3 —<br />
C 3 —<br />
ECO-T528-120-1<br />
ECO-T528-120-2<br />
.30<br />
.55<br />
T5-HO<br />
Linear<br />
24W<br />
(22”)<br />
1<br />
2<br />
C 3<br />
C 3<br />
FDB-T524-120-1<br />
FDB-T524-120-2<br />
ECO-T524-120-1<br />
ECO-T524-120-2<br />
.26<br />
.45<br />
5/8” Dia<br />
39W<br />
(34”)<br />
1<br />
2<br />
C 3<br />
C 3<br />
FDB-T539-120-1<br />
FDB-T539-120-2<br />
ECO-T5H39-120-1<br />
ECO-T5H39-120-2<br />
.38<br />
.76<br />
54W<br />
(45”)<br />
1<br />
2<br />
C 3<br />
C 3<br />
FDB-T554-120-1<br />
FDB-T554-120-2<br />
ECO-T554-120-1<br />
ECO-T554-120-2<br />
.58<br />
1.1<br />
T8 Linear<br />
and U-Bent<br />
17W<br />
(24”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
FDB-2427-120-1<br />
FDB-2427-120-2<br />
FDB-2427-120-3<br />
ECO-T817-120-1<br />
ECO-T817-120-2<br />
ECO-T817-120-3<br />
.19<br />
.31<br />
.43<br />
1” Dia 25W<br />
(36”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
FDB-3627-120-1<br />
FDB-3627-120-2<br />
FDB-3627-120-3<br />
ECO-T825-120-1<br />
ECO-T825-120-2<br />
—<br />
.24<br />
.43<br />
.62<br />
32 W<br />
(48”)<br />
1<br />
1<br />
1<br />
2<br />
2<br />
2<br />
3<br />
F<br />
D<br />
D<br />
F<br />
D<br />
D<br />
F<br />
FDB-4827-120-1<br />
—<br />
—<br />
FDB-4827-120-2<br />
—<br />
—<br />
FDB-4827-120-3<br />
—<br />
ECO-T832-120-1-L<br />
ECO-T832-120-1-T<br />
—<br />
ECO-T832-120-2-L<br />
ECO-T832-120-2-T<br />
ECO-T832-120-3<br />
.30<br />
.34<br />
.34<br />
.57<br />
.53<br />
.53<br />
.82<br />
40W<br />
(60”)<br />
1<br />
2<br />
F<br />
F<br />
FDB-6027-120-1<br />
FDB-6027-120-2<br />
—<br />
—<br />
.36<br />
.64<br />
Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />
See page 30 for model numbers.<br />
1 For case type information, see pages 36 and 37.<br />
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.<br />
3 Standard with terminals. Leaded options available. Please consult factory.<br />
26 | <strong>Lutron</strong>
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
1% Dimming<br />
Hi-lume<br />
5% Dimming<br />
Compact SE<br />
10% Dimming<br />
Eco-10<br />
Ballast<br />
Current 2<br />
– Amps<br />
T4 4-Pin<br />
Quad-Tube<br />
18W 1<br />
2<br />
A 3 —<br />
B 3 —<br />
FDB-T418-120-1-S<br />
FDB-T418-120-2-S<br />
—<br />
—<br />
.20<br />
.42<br />
1/2” Dia<br />
26W 1<br />
2<br />
A 3 —<br />
B 3 —<br />
FDB-T426-120-1-S<br />
FDB-T426-120-2-S<br />
—<br />
—<br />
.26<br />
.50<br />
T4 4-Pin<br />
Triple-Tube<br />
18W 1<br />
2<br />
A 3 —<br />
B 3 —<br />
FDB-T418-120-1-S<br />
FDB-T418-120-2-S<br />
—<br />
—<br />
.20<br />
.42<br />
1/2” Dia<br />
26W 1<br />
2<br />
A 3<br />
B 3<br />
HL3-T426-120-1-S<br />
—<br />
FDB-T426-120-1-S<br />
FDB-T426-120-2-S<br />
—<br />
—<br />
.26<br />
.50<br />
32W 1<br />
2<br />
A 3<br />
B 3<br />
HL3-T432-120-1-S<br />
—<br />
FDB-T432-120-1-S<br />
FDB-T432-120-2-S<br />
—<br />
—<br />
.31<br />
.59<br />
42W 1<br />
2<br />
B 3 —<br />
B 3 —<br />
FDB-T442-120-1-S<br />
FDB-T442-120-2-S<br />
—<br />
—<br />
.39<br />
.67<br />
T5<br />
Twin-Tube<br />
36/39W<br />
(16”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
—<br />
—<br />
—<br />
FDB-1643-120-1<br />
FDB-1643-120-2<br />
FDB-1643-120-3<br />
ECO-T539-120-1<br />
ECO-T539-120-2<br />
ECO-T539-120-3<br />
.33<br />
.58<br />
.85<br />
5/8” Dia 40W<br />
(22”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
—<br />
—<br />
—<br />
FDB-2227-120-1<br />
FDB-2227-120-2<br />
FDB-2227-120-3<br />
ECO-T540-120-1<br />
ECO-T540-120-2<br />
ECO-T540-120-3<br />
.33<br />
.61<br />
.88<br />
50 W<br />
(22”)<br />
1<br />
2<br />
F<br />
F<br />
—<br />
—<br />
FDB-2243-120-1<br />
FDB-2243-120-2<br />
ECO-T550-120-1<br />
ECO-T550-120-2<br />
.38<br />
.69<br />
Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />
See page 30 for model numbers.<br />
1 For case type information, see pages 36 and 37.<br />
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.<br />
3 Mounting studs standard. Delete suffi x -S if mounting studs not desired.<br />
<strong>Lutron</strong> | 27
<strong>Lutron</strong>® | Hi-lume®, Compact SE , Eco-10®<br />
277 volt 3-wire <strong>dimming</strong> ballasts<br />
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
1% Dimming<br />
Hi-lume<br />
5% Dimming<br />
10% Dimming<br />
Eco-10<br />
Ballast<br />
Current 2<br />
– Amps<br />
T5 Linear<br />
14W<br />
(22”)<br />
1<br />
2<br />
C 3 —<br />
C 3 —<br />
E 3 T514 C 277 1<br />
E 3 T514 C 277 2<br />
.08<br />
.14<br />
5/8” Dia 21W<br />
(34”)<br />
1<br />
2<br />
C 3 —<br />
C 3 —<br />
E 3 T521 C 277 1<br />
E 3 T521 C 277 2<br />
.11<br />
.19<br />
28W<br />
(45”)<br />
1<br />
2<br />
C 3 —<br />
C 3 —<br />
ECO-T528-277-1<br />
ECO-T528-277-2<br />
.14<br />
.25<br />
T5-HO<br />
Linear<br />
24W<br />
(22”)<br />
1<br />
2<br />
C 3<br />
C 3<br />
FDB-T524-277-1<br />
FDB-T524-277-2<br />
ECO-T524-277-1<br />
ECO-T524-277-2<br />
.13<br />
.20<br />
5/8” Dia<br />
39W<br />
(34”)<br />
1<br />
2<br />
C 3<br />
C 3<br />
FDB-T539-277-1<br />
FDB-T539-277-2<br />
ECO-T5H39-277-1<br />
ECO-T5H39-277-2<br />
.17<br />
.31<br />
54W<br />
(45”)<br />
1<br />
2<br />
C 3<br />
C 3<br />
FDB-T554-277-1<br />
FDB-T554-277-2<br />
ECO-T554-277-1<br />
ECO-T554-277-2<br />
.25<br />
.45<br />
T8 Linear<br />
and U-Bent<br />
17W<br />
(24”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
FDB-2427-277-1<br />
FDB-2427-277-2<br />
FDB-2427-277-3<br />
ECO-T817-277-1<br />
ECO-T817-277-2<br />
ECO-T817-277-3<br />
.08<br />
.15<br />
.20<br />
1” Dia 25W<br />
(36”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
FDB-3627-277-1<br />
FDB-3627-277-2<br />
FDB-3627-277-3<br />
ECO-T825-277-1<br />
ECO-T825-277-2<br />
—<br />
.12<br />
.19<br />
.28<br />
32 W<br />
(48”)<br />
1<br />
1<br />
1<br />
2<br />
2<br />
2<br />
3<br />
F<br />
D<br />
D<br />
F<br />
D<br />
D<br />
F<br />
FDB-4827-277-1<br />
—<br />
—<br />
FDB-4827-277-2<br />
—<br />
—<br />
FDB-4827-277-3<br />
ECO-T832-277-1<br />
ECO-T832-277-1-L<br />
ECO-T832-277-1-T<br />
ECO-T832-277-2<br />
ECO-T832-277-2-L<br />
ECO-T832-277-2-T<br />
ECO-T832-277-3<br />
.14/.15 4<br />
.14<br />
.14<br />
.25/.22 4<br />
.23<br />
.23<br />
.35<br />
40W<br />
(60”)<br />
1<br />
2<br />
F<br />
F<br />
FDB-6027-120-1<br />
FDB-6027-277-2<br />
—<br />
—<br />
.16<br />
.30<br />
Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />
See page 30 for model numbers.<br />
1 For case type information, see pages 36 and 37.<br />
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 277.<br />
3 Standard with terminals. Leaded options available. Please consult factory.<br />
4 Eco-10 ballast current.<br />
28 | <strong>Lutron</strong>
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
1% Dimming<br />
Hi-lume<br />
5% Dimming<br />
Compact SE<br />
10% Dimming<br />
Eco-10<br />
Ballast<br />
Current 2<br />
– Amps<br />
T4 4-Pin<br />
Quad-Tube<br />
18W 1<br />
2<br />
A 3 —<br />
B 3 —<br />
FDB-T418-277-1-S<br />
FDB-T418-277-2-S<br />
—<br />
—<br />
.08<br />
.17<br />
1/2” Dia<br />
26W 1<br />
2<br />
A 3 —<br />
B 3 —<br />
FDB-T426-277-1-S<br />
FDB-T426-277-2-S<br />
—<br />
—<br />
.12<br />
.21<br />
T4 4-Pin<br />
Triple-Tube<br />
18W 1<br />
2<br />
A 3 —<br />
B 3 —<br />
FDB-T418-277-1-S<br />
FDB-T418-277-2-S<br />
—<br />
—<br />
.08<br />
.17<br />
1/2” Dia<br />
26W 1<br />
2<br />
A 3<br />
B 3<br />
HL3-T426-277-1-S<br />
—<br />
FDB-T426-277-1-S<br />
FDB-T426-277-2-S<br />
—<br />
—<br />
.12<br />
.21<br />
32W 1<br />
2<br />
A 3<br />
B 3<br />
HL3-T432-277-1-S<br />
—<br />
FDB-T432-277-1-S<br />
FDB-T432-277-2-S<br />
—<br />
—<br />
.13<br />
.24<br />
42W 1<br />
2<br />
B 3 —<br />
B 3 —<br />
FDB-T442-277-1-S<br />
FDB-T442-277-2-S<br />
—<br />
—<br />
.16<br />
.29<br />
T5<br />
Twin-Tube<br />
36/39W<br />
(16”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
—<br />
—<br />
—<br />
FDB-1643-277-1<br />
FDB-1643-277-2<br />
FDB-1643-277-3<br />
ECO-T539-277-1<br />
ECO-T539-277-2<br />
ECO-T539-277-3<br />
.14<br />
.25<br />
.35<br />
5/8” Dia 40W<br />
(22”)<br />
1<br />
2<br />
3<br />
F<br />
F<br />
F<br />
—<br />
—<br />
—<br />
FDB-2227-277-1<br />
FDB-2227-277-2<br />
FDB-2227-277-3<br />
ECO-T540-277-1<br />
ECO-T540-277-2<br />
ECO-T540-277-3<br />
.14<br />
.25<br />
.38<br />
50 W<br />
(22”)<br />
1<br />
2<br />
F<br />
F<br />
—<br />
—<br />
FDB-2243-277-1<br />
FDB-2243-277-2<br />
ECO-T550-277-1<br />
ECO-T550-277-2<br />
.17<br />
.32<br />
Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />
See page 30 for model numbers.<br />
For case type information, see pages 36 and 37.<br />
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 277.<br />
3 Standard with terminals. Leaded options available. Please consult factory.<br />
<strong>Lutron</strong> | 29
<strong>Lutron</strong>® |<br />
Hi-lume® 3D Universal Voltage<br />
digital multi-input <strong>dimming</strong> ballasts<br />
NEW!<br />
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
T8 Linear<br />
and U-Bent<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
1% Dimming<br />
Hi-lume 3D<br />
Input<br />
Voltage<br />
Ballast<br />
Current<br />
– Amps<br />
Ballast<br />
Factor<br />
Input<br />
Power<br />
Ballast<br />
Effi cacy<br />
Factor<br />
System<br />
Lumens 2<br />
1 C<br />
120 0.298 1.00 36 2.80 3,000 84<br />
H3D T832 C UNV 1 10<br />
1 C 277 0.127 1.00 35 2.84 3,000 85<br />
System<br />
Effi cacy 2<br />
(Im/W)<br />
1” Dia<br />
32W<br />
(48”)<br />
1 C<br />
120 0.338 1.17 41 2.88 3,510 87<br />
H3D T832 C UNV 1 17<br />
1 C 277 0.143 1.17 40 2.95 3,510 89<br />
2 C<br />
120 0.573 1.00 69 1.45 6,000 87<br />
H3D T832 C UNV 2 10<br />
2 C 277 0.243 1.00 67 1.49 6,000 89<br />
2 C<br />
120 0.662 1.17 79 1.47 7,020 88<br />
H3D T832 C UNV 2 17<br />
2 C 277 0.279 1.17 77 1.51 7,020 91<br />
1 For case type information, see pages 36 and 37.<br />
2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specifi c data.<br />
30 | <strong>Lutron</strong>
Hi-lume® 3D | features<br />
Enhanced <strong>dimming</strong>, high ballast factor,<br />
and improved effi ciency<br />
Hi-lume 3D delivers superior performance<br />
compared to other ballasts. It provides enhanced<br />
<strong>dimming</strong>, giving you the broadest range of light<br />
levels so you’ll always use the right light for the<br />
task at hand. It offers a high ballast factor for more<br />
light per fi xture so you can use fewer fi xtures in the<br />
space, saving money and time on lighting installation<br />
and maintenance costs. Furthermore, Hi-lume 3D<br />
is energy effi cient as evidenced by its high effi cacy/<br />
lumens per watt rating. Hi-lume 3D gives you the<br />
most light for a watt of power compared to nearly<br />
all other ballasts. Hi-lume 3D is the superior choice<br />
because you get better performance, effi ciently.<br />
Performance of T8 32W 2 Lamp 277V Ballasts<br />
Non-dim Ballast<br />
(90 lm/W)<br />
EcoSystemTM<br />
(89 lm/W)<br />
Hi-lume<br />
(82 lm/W)<br />
Hi-lume 3D 1.0<br />
(89 lm/W)<br />
Hi-lume 3D 1.17<br />
(91 lm/W)<br />
1.4<br />
8400<br />
1.2<br />
1.17 BF/<br />
7020 lm<br />
7200<br />
Ballast Factor (BF)<br />
1.0<br />
0.8<br />
0.6<br />
0.4<br />
0.88 BF/<br />
5280 lm<br />
0.85 BF/<br />
5100 lm<br />
10 to 1 Dimming Ratio<br />
0.95 BF/<br />
5700 lm<br />
100 to 1 Dimming Ratio<br />
1.00 BF/<br />
6000 lm<br />
118 to 1 Dimming Ratio<br />
138 to 1 Dimming Ratio<br />
6000<br />
4800<br />
3600<br />
2400<br />
lumens (lm)<br />
0.2<br />
1200<br />
0<br />
0.085 BF/510 lm<br />
0.0095 BF/57 lm<br />
0.0085 BF/51 lm<br />
0.0085 BF/51 lm<br />
0<br />
<strong>Lutron</strong> | 31
<strong>Lutron</strong>® |<br />
Tu-Wire ® 120 volt<br />
2-wire <strong>dimming</strong> ballasts<br />
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
1% Dimming<br />
5% Dimming<br />
Tu-Wire<br />
10% Dimming<br />
Ballast<br />
Current 2<br />
– Amps<br />
T8 Linear<br />
and U-Bent<br />
32W<br />
(48”)<br />
1<br />
2<br />
C 3<br />
C 3<br />
2W-T832-120-1<br />
2W-T832-120-2<br />
.37<br />
.70<br />
1” Dia<br />
Contact <strong>Lutron</strong> for<br />
other lamp lengths.<br />
T4 4-Pin<br />
Quad-Tube<br />
18W 2 B 4 2W-T418-120-2-S .41<br />
1/2” Dia<br />
26W 1<br />
2<br />
A 4<br />
2W-T426-120-1-S 5<br />
B 4 2W-T426-120-2-S<br />
.27<br />
.53<br />
T4 4-Pin<br />
Triple-Tube<br />
18W 2 B 4 2W-T418-120-2-S .41<br />
1/2” Dia<br />
26W 1<br />
2<br />
A 4<br />
2W-T426-120-1-S 5<br />
B 4 2W-T426-120-2-S<br />
.27<br />
.53<br />
32 W 1<br />
2<br />
A 4<br />
2W-T432-120-1-S 5<br />
B 4 2W-T432-120-2-S<br />
.33<br />
.58<br />
1 For case type information, see pages 36 and 37.<br />
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.<br />
3 Standard with terminals. Leaded options available. Please consult factory.<br />
4 Mounting studs standard. Delete suffi x -S if mounting studs not desired.<br />
5 One-lamp T4 models meet FCC Part 18 consumer requirements for residential use (FCC ID: JPZB001).<br />
32 | <strong>Lutron</strong>
<strong>Lutron</strong>® | TVE 120/277/347 volt<br />
0-10V <strong>dimming</strong> ballasts<br />
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1 1% Dimming 5% Dimming<br />
10% Dimming<br />
TVE<br />
Ballast<br />
Current 2<br />
– Amps<br />
T8 Linear<br />
and U-Bent<br />
1” Dia<br />
17W<br />
(24”)<br />
25W<br />
(36”)<br />
1 F TVE-T817-120-1 .14<br />
1 F TVE-T825-120-1 .24<br />
32W<br />
(48”)<br />
1<br />
1<br />
1<br />
2<br />
2<br />
2<br />
3<br />
3<br />
F<br />
F<br />
F<br />
F<br />
F<br />
F<br />
F<br />
F<br />
TVE-T832-120-1<br />
TVE-T832-277-1<br />
TVE-T832-347-1<br />
TVE-T832-120-2<br />
TVE-T832-277-2<br />
TVE-T832-347-2<br />
TVE-T832-120-3<br />
TVE-T832-277-3<br />
.34<br />
.15<br />
.11<br />
.55<br />
.25<br />
.19<br />
.80<br />
.35<br />
T5<br />
Twin-Tube<br />
40W<br />
(22”)<br />
2<br />
2<br />
F<br />
F<br />
TVE-T540-120-2<br />
TVE-T540-277-2<br />
.61<br />
.25<br />
5/8” Dia<br />
1 For case type information, see pages 36 and 37.<br />
2 To calculate ballast input power, use the following formula: Watts = Ballast Current x Ballast Voltage<br />
(included in model number).<br />
<strong>Lutron</strong> | 33
<strong>Lutron</strong>® | EcoSystemTM 120 volt multi-input<br />
digital addressable <strong>dimming</strong> ballasts<br />
NEW!<br />
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
10% Dimming<br />
EcoSystem<br />
Ballast<br />
Current<br />
– Amps<br />
Ballast<br />
Factor<br />
Input<br />
Power<br />
Ballast<br />
Effi cacy<br />
Factor<br />
System<br />
Lumens 2<br />
System<br />
Effi cacy 2<br />
(Im/W)<br />
T8 Linear<br />
and U-Bent<br />
17W<br />
(24”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T817 J 120 1<br />
EC5 T817 J 120 2<br />
.158<br />
.292<br />
.85<br />
.85<br />
19<br />
35<br />
4.47<br />
2.43<br />
1,105<br />
2,210<br />
58<br />
63<br />
1” Dia<br />
25W<br />
(36”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T825 J 120 1<br />
EC5 T825 J 120 2<br />
.208<br />
.383<br />
.85<br />
.85<br />
25<br />
46<br />
3.40<br />
1.85<br />
1,615<br />
3,230<br />
65<br />
70<br />
32W<br />
(48”)<br />
1<br />
2<br />
2<br />
3<br />
J<br />
J<br />
G<br />
G<br />
EC5 T832 J 120 1<br />
EC5 T832 J 120 2<br />
EC5 T832 G120 2L<br />
EC5 T832 G120 3L<br />
.250<br />
.475<br />
.490<br />
.790<br />
.85<br />
.85<br />
.85<br />
.85<br />
30<br />
57<br />
58<br />
85<br />
2.83<br />
1.49<br />
1.47<br />
1.00<br />
2,550<br />
5,100<br />
5,100<br />
7,650<br />
85<br />
89<br />
88<br />
90<br />
T5 Linear<br />
14W<br />
(22”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T514 J 120 1<br />
EC5 T514 J 120 2<br />
.158<br />
.283<br />
1.00<br />
1.00<br />
19<br />
34<br />
5.26<br />
2.94<br />
1,350<br />
2,700<br />
71<br />
79<br />
5/8” Dia 21W<br />
(34”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T521 J 120 1<br />
EC5 T521 J 120 2<br />
.217<br />
.404<br />
1.00<br />
1.00<br />
26<br />
48.5<br />
3.85<br />
2.06<br />
2,100<br />
4,200<br />
81<br />
87<br />
28W<br />
(45”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T528 J 120 1<br />
EC5 T528 J 120 2<br />
.275<br />
.525<br />
1.00<br />
1.00<br />
33<br />
63<br />
3.03<br />
1.59<br />
2,900<br />
5,800<br />
88<br />
92<br />
T5-HO<br />
Linear<br />
High<br />
Output<br />
24W<br />
(22”)<br />
39W<br />
(34”)<br />
1<br />
2<br />
1<br />
2<br />
J<br />
J<br />
J<br />
J<br />
EC5 T524 J 120 1<br />
EC5 T524 J 120 2<br />
EC5 T539 J 120 1<br />
EC5 T539 J 120 2<br />
.226<br />
.434<br />
.359<br />
.695<br />
1.00<br />
1.00<br />
1.00<br />
1.00<br />
27<br />
52<br />
43<br />
83<br />
3.70<br />
1.92<br />
2.33<br />
1.20<br />
2,000<br />
4,000<br />
3,500<br />
7,000<br />
74<br />
77<br />
81<br />
84<br />
5/8” Dia 54 W<br />
(45”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T554 J 120 1<br />
EC5 T554 J 120 2<br />
.500<br />
1.00<br />
1.00<br />
1.00<br />
60<br />
120<br />
1.67<br />
0.83<br />
5,000<br />
10,000<br />
83<br />
83<br />
Use EcoSystem ballast module (C5-BMF-2A) to integrate any <strong>Lutron</strong> Eco-10TM or Hi-lume®<br />
phase-control ballast into the EcoSystem bus.<br />
Sensors<br />
E1 3<br />
E2 3<br />
Hot<br />
Neutral<br />
BMF<br />
Switched Hot,<br />
Dimmed Hot<br />
and Neutral<br />
Dimming Ballast<br />
1 For case type information, see pages 36 and 37.<br />
2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specifi c data.<br />
3 To other ballasts and bus supply.<br />
34 | <strong>Lutron</strong>
<strong>Lutron</strong>® | EcoSystemTM 277 volt multi-input<br />
digital addressable <strong>dimming</strong> ballasts<br />
For the latest<br />
model numbers:<br />
www.lutron.com/ballasts<br />
Lamp<br />
Type<br />
Lamp<br />
Watts<br />
(Length)<br />
Lamps<br />
per<br />
Ballast<br />
Case<br />
Type 1<br />
10% Dimming<br />
EcoSystem<br />
Ballast<br />
Current<br />
– Amps<br />
Ballast<br />
Factor<br />
Input<br />
Power<br />
Ballast<br />
Effi cacy<br />
Factor<br />
System<br />
Lumens 2<br />
System<br />
Effi cacy 2<br />
(Im/W)<br />
T8 Linear<br />
and U-Bent<br />
17W<br />
(24”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T817 J 277 1<br />
EC5 T817 J 277 2<br />
.075<br />
.126<br />
.85<br />
.85<br />
19<br />
35<br />
4.47<br />
2.43<br />
1,105<br />
2,210<br />
58<br />
63<br />
1” Dia<br />
25W<br />
(36”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T825 J 277 1<br />
EC5 T825 J 277 2<br />
.095<br />
.166<br />
.85<br />
.85<br />
25<br />
46<br />
3.40<br />
1.85<br />
1,615<br />
3,230<br />
65<br />
70<br />
32W<br />
(48”)<br />
1<br />
2<br />
2<br />
3<br />
J<br />
J<br />
G<br />
G<br />
EC5 T832 J 277 1<br />
EC5 T832 J 277 2<br />
EC5 T832 G 277 2L<br />
EC5 T832 G 277 3L<br />
.108<br />
.206<br />
.216<br />
.320<br />
.85<br />
.85<br />
.85<br />
.85<br />
30<br />
57<br />
57<br />
86<br />
2.83<br />
1.49<br />
1.49<br />
0.99<br />
2,550<br />
5,100<br />
5,100<br />
7,632<br />
85<br />
89<br />
89<br />
89<br />
T5 Linear<br />
14W<br />
(22”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T514 J 277 1<br />
EC5 T514 J 277 2<br />
.078<br />
.123<br />
1.00<br />
1.00<br />
19<br />
34<br />
5.26<br />
2.94<br />
1,350<br />
2,700<br />
71<br />
79<br />
5/8” Dia 21W<br />
(34”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T521 J 277 1<br />
EC5 T521 J 277 2<br />
.094<br />
.175<br />
1.00<br />
1.00<br />
26<br />
48.5<br />
3.85<br />
2.06<br />
2,100<br />
4,200<br />
81<br />
87<br />
28W<br />
(45”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T528 J 277 1<br />
EC5 T528 J 277 2<br />
.119<br />
.227<br />
1.00<br />
1.00<br />
33<br />
63<br />
3.03<br />
1.59<br />
2,900<br />
5,800<br />
88<br />
92<br />
T5-HO<br />
Linear<br />
24W<br />
(22”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T524 J 277 1<br />
EC5 T524 J 277 2<br />
.100<br />
.191<br />
1.00<br />
1.00<br />
27<br />
52<br />
3.70<br />
1.92<br />
2,000<br />
4,000<br />
74<br />
77<br />
High<br />
Output<br />
39W<br />
(34”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T539 J 277 1<br />
EC5 T539 J 277 2<br />
.158<br />
.306<br />
1.00<br />
1.00<br />
43<br />
83<br />
2.33<br />
1.20<br />
3,500<br />
7,000<br />
81<br />
84<br />
5/8” Dia 54 W<br />
(45”)<br />
1<br />
2<br />
J<br />
J<br />
EC5 T554 J 277 1<br />
EC5 T554 J 277 2<br />
.217<br />
.433<br />
1.00<br />
1.00<br />
60<br />
120<br />
1.67<br />
0.83<br />
5,000<br />
10,000<br />
83<br />
83<br />
1 For case type information, see pages 36 and 37.<br />
2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specifi c data.<br />
<strong>Lutron</strong> | 35
<strong>Lutron</strong>® | ballast case dimensions<br />
A<br />
B<br />
H<br />
G<br />
A<br />
F<br />
I<br />
E<br />
8-32 Threaded Stud<br />
0.29" (.736mm)<br />
D<br />
C<br />
A<br />
B<br />
C<br />
D<br />
E<br />
F<br />
G<br />
H<br />
I<br />
4.20” (107mm)<br />
1.00” (25mm)<br />
3.00” (76mm)<br />
4.90” (124mm)<br />
4.60” (117mm) C-C<br />
(mounting centers)<br />
2.00” (51mm)<br />
1.08” (27mm)<br />
1.60” (41mm)<br />
1.39” (35mm)<br />
B<br />
B<br />
H<br />
G<br />
A<br />
F<br />
I<br />
E<br />
8-32 Threaded Stud<br />
0.29" (.736mm)<br />
D<br />
C<br />
A<br />
B<br />
C<br />
D<br />
E<br />
F<br />
G<br />
H<br />
I<br />
6.00” (152mm)<br />
1.00” (25mm)<br />
3.00” (76mm)<br />
6.75” (171mm)<br />
6.50” (165mm) C-C<br />
(mounting centers)<br />
2.00” (51mm)<br />
1.16” (29mm)<br />
1.60” (41mm)<br />
1.39” (35mm)<br />
C or J<br />
C<br />
B<br />
F<br />
Note: Dotted area for sensor attachment applies<br />
for EcoSystemTM J can only.<br />
A<br />
G<br />
D<br />
E<br />
A<br />
B<br />
C<br />
D<br />
E<br />
F<br />
G<br />
16.12” (409mm)<br />
1.00” (25mm)<br />
1.18” (30mm)<br />
18.00” (457mm)<br />
17.70” (450mm)<br />
C-C (mounting<br />
centers)<br />
6.82” (173mm)<br />
(J only)<br />
0.394”(10mm)<br />
(J only)<br />
36 | <strong>Lutron</strong>
D<br />
C<br />
B<br />
A<br />
D<br />
E<br />
A 7.13” (181mm)<br />
B 1.00” (25mm)<br />
C 1.58” (40mm)<br />
D 9.50” (241mm)<br />
E 8.91” (226mm)<br />
Slot mounting centers<br />
If using 4-hole mount,<br />
mounting centers are 9.00”<br />
(229mm) X 1.06” (27mm).<br />
Optional lamp wires<br />
are 36” (0.90m)<br />
Optional power<br />
and control wires<br />
are 18” (0.45m)<br />
F<br />
C<br />
B<br />
A<br />
E<br />
D<br />
A 8.30” (211mm)<br />
B 1.50” (38mm)<br />
C 2.38” (60.5mm)<br />
D 9.50” (241mm)<br />
E 8.91” (226mm)<br />
Slot mounting centers<br />
If using 4-hole mount,<br />
mounting centers are 9.21”<br />
(234mm) X 1.70” (43mm).<br />
Lamp wires<br />
are 36” (0.90m)<br />
Power and control<br />
wires are 18” (0.45m)<br />
G<br />
C<br />
B<br />
Lamp wires<br />
are 36” (0.90m)<br />
A<br />
D<br />
E<br />
Power and control<br />
wires are 18” (0.45m)<br />
A 7.13” (181mm)<br />
B 1.00” (25mm)<br />
C 2.38” (60.5mm)<br />
D 9.50” (241mm)<br />
E 8.91” (226mm)<br />
Slot mounting centers<br />
If using 4-hole mount,<br />
mounting centers are 9.00”<br />
(229mm) X 1.06” (27mm).<br />
Proper ballast mounting is critical in providing effective grounding and for<br />
managing ballast heat. Please refer to the <strong>Lutron</strong> Fluorescent Dimming<br />
Systems Technical Guide (P/N 366-606) for detailed information.<br />
<strong>Lutron</strong> | 37
<strong>Lutron</strong>® | fl uorescent <strong>dimming</strong> controls<br />
Wallbox dimmers<br />
NovaTa®<br />
Classic, thin-profi le<br />
linear-slide dimmer<br />
Nova®<br />
Contractor’s choice in<br />
linear-slide dimmers<br />
Wallbox dimmers<br />
Vierti NEW!<br />
Available 4 th Quarter 2007<br />
Combines style and simplicity in<br />
a remarkably innovative control.<br />
•<br />
set the perfect light level with a<br />
single touch or slide of the fi nger<br />
• customize with different<br />
LED colors<br />
To learn more about Vierti visit<br />
www.lutron.com/vierti<br />
Lyneo® Lx NEW!<br />
The simple, clean lines of the<br />
dimmer and matching switch<br />
ensure a coordinated look for<br />
your project.<br />
To learn more about Lyneo Lx<br />
visit www.lutron.com/lyneo<br />
Vareo®<br />
Elegant thin-profi le<br />
TapSwitch dimmer<br />
Diva®<br />
Designer dimmer<br />
that matches your<br />
paddle switches<br />
Wireless remote controls<br />
Skylark®<br />
Original designer-style<br />
slide dimmer<br />
Ariadni®<br />
Dimmer that matches<br />
your toggle switches<br />
RadioTouch®<br />
•<br />
Wireless control<br />
of multiple lighting zones<br />
•<br />
Occupancy sensing,<br />
motorized shade and<br />
A/V equipment control optional<br />
•<br />
Ideal for retrofi t applications<br />
To learn more about the product visit<br />
www.lutron.com/hlc<br />
To learn more about the product visit<br />
www. lutron.com/radiotouch<br />
38 | <strong>Lutron</strong>
Preset scene control<br />
Preset scene control<br />
GRAFIK Eye® QS<br />
NEW!<br />
•<br />
Light and shade control in one unit<br />
•<br />
Engravings on large, backlit buttons<br />
•<br />
Information display with energy saving<br />
reading included<br />
•<br />
Built-in astronomical time clock<br />
•<br />
Direct connections to sensors and<br />
other devices<br />
To learn more about the product visit<br />
www. lutron.com/grafi keyeqs<br />
Spacer System <br />
•<br />
Up to fi ve preset scenes<br />
•<br />
Easy upgrade for enclosed<br />
offi ces and conference rooms<br />
•<br />
Dims multiple sources<br />
To learn more about the product visit<br />
www. lutron.com/spacersystem.<br />
NEW!<br />
GRAFIK Eye®<br />
•<br />
Create and recall 4-16 room<br />
lighting scenes<br />
•<br />
Optional accessories for wireless<br />
remote control, remote scene<br />
selection, and more<br />
•<br />
Controls multiple sources<br />
To learn more about the product visit<br />
www. lutron.com/grafi keye<br />
Quantum Solution<br />
Whole-building light and energy management.<br />
Controls electric lights and shades from a central<br />
location; confi gures, monitors, analyzes, and reports on<br />
the light for an entire building or campus. Furthermore,<br />
the Quantum Green Glance demonstrates how much<br />
energy your building is saving.<br />
To learn more about the product visit<br />
www. lutron.com/quantum.<br />
<strong>Lutron</strong> | 39
<strong>Lutron</strong>® | EcoSystemTM components<br />
Ballasts<br />
Sensors/Receivers<br />
EcoSystem Daylight<br />
Sensor with IR Receiver<br />
EcoSystem T8 Digital Ballast<br />
EcoSystem T8, T5 and T5-HO Digital Ballast<br />
•<br />
Smooth and continuous <strong>dimming</strong> from<br />
100% to 10%<br />
•<br />
Provides power for one occupancy sensor,<br />
one daylight sensor, and one personal control<br />
input (infrared receiver or wallstation)<br />
•<br />
Communicates status and sensor inputs over<br />
the EcoSystem bus<br />
•<br />
Automatically dim the lights when the available<br />
daylight is high and brighten the light when the<br />
available daylight is low in order to maintain a<br />
specifi c light level in the space<br />
•<br />
Integrated IR receiver for<br />
EcoSystem programming<br />
•<br />
1 daylight sensor can control multiple<br />
fi xtures or groups of fi xtures differently<br />
Modules<br />
EcoSystem Ballast Module<br />
Fixture-mounted (BMF)<br />
•<br />
Allows integration of any <strong>Lutron</strong> Eco-10 <br />
or Hi-lume® phase-control ballast into<br />
the EcoSystem<br />
•<br />
Provides power for one occupancy sensor, one<br />
daylight sensor, and one personal control input<br />
(infrared receiver or wallstation)<br />
20VDC Occupancy Sensor<br />
•<br />
Use an ultrasonic sensor for small movement<br />
detection when fans or other automated<br />
<strong>systems</strong> are not present<br />
•<br />
Use an infrared sensor for occupant detection<br />
when “line of sight” is available from the sensor<br />
•<br />
Use a dual-tech sensor for a combination of<br />
both technologies<br />
EcoSystem IR Receiver<br />
•<br />
Can control individual or grouped<br />
EcoSystem ballasts or modules<br />
•<br />
Flashing LED response to indicate<br />
signal reception<br />
40 | <strong>Lutron</strong>
Controls<br />
Support components<br />
EcoSystem 1-Button Wallstation<br />
and IR Receiver<br />
•<br />
Allows user to manually control any of<br />
the fi xtures on the bus for simple on/off,<br />
raise/lower<br />
EcoSystem Programmer<br />
•<br />
Handles programming changes for all<br />
sensors, ballasts, and modules<br />
•<br />
Transmits to any IR receiver, daylight<br />
sensor, or EcoSystem wallstation<br />
•<br />
Simple user interface allows programming<br />
without training or <strong>guide</strong>book<br />
EcoSystem 4-Button Wallstation<br />
and IR Receiver<br />
•<br />
Allows occupants to save and recall different<br />
lighting scenes in multi-purpose rooms<br />
EcoSystem Bus Supply<br />
•<br />
Required for two or more ballasts (or<br />
modules) to work together<br />
•<br />
Powers the communication bus and is<br />
capable of supporting up to 64 ballasts<br />
or modules<br />
EcoSystem Remote Control<br />
and IR Receiver<br />
•<br />
For personal control of lighting<br />
See the <strong>Lutron</strong> EcoSystem Technical Guide<br />
(P/N 367-1028) for detailed information.<br />
<strong>Lutron</strong> | 41
<strong>Lutron</strong>® | select your fl uorescent <strong>dimming</strong> controls<br />
3-wire controls for Hi-lume®, Compact SE and Eco-10 ballasts<br />
Control Family<br />
Description<br />
Ballast<br />
Voltage<br />
Control<br />
Model Number<br />
Control<br />
Capacity<br />
NovaTa®<br />
Thin Profi le<br />
Slide-To-Off<br />
Dimmer<br />
single pole<br />
single pole<br />
single pole, 3-way, preset<br />
single pole, 3-way, preset<br />
120V<br />
277V<br />
120V<br />
277V<br />
NTF-10-<br />
NTF-10-277-<br />
NTF-103P-<br />
NTF-103P-277-<br />
16A<br />
8A<br />
8A<br />
8A<br />
Nova®<br />
Standard Profi le<br />
Slide-To-Off<br />
Dimmer<br />
single pole<br />
single pole<br />
single pole, 3-way, preset<br />
single pole, 3-way, preset<br />
120V<br />
277V<br />
120V<br />
277V<br />
NF-10-<br />
NF-10-277-<br />
NF-103P-<br />
NF-103P-277-<br />
16A<br />
8A<br />
8A<br />
8A<br />
Vareo®<br />
Tapswitch/<br />
Preset Slide<br />
Dimmer<br />
single pole, 3-way 120V VF-10- 8A 1<br />
Diva®<br />
Paddle Switch/<br />
Preset Slide<br />
Dimmer<br />
single pole, 3-way<br />
single pole, 3-way<br />
120V<br />
277V<br />
DVF-103P-<br />
DVF-103P-277-<br />
8A<br />
6A<br />
Skylark®<br />
Rocker Switch/<br />
Preset Slide<br />
Dimmer<br />
single pole<br />
single pole<br />
single pole, 3-way<br />
single pole, 3-way<br />
120V<br />
277V<br />
120V<br />
277V<br />
SF-10P-<br />
SF-12P-277-<br />
SF-103P-<br />
SF-12P-277-3-<br />
8A<br />
6A<br />
8A<br />
6A<br />
Ariadni®<br />
Toggle Switch/<br />
Preset Slide<br />
Dimmer<br />
single pole, 3-way<br />
single pole, 3-way<br />
120V<br />
277V<br />
AYF-103P-<br />
AYF-103P-277-<br />
8A<br />
6A<br />
NEW!<br />
Vierti <br />
Single-touch<br />
lighting conrol<br />
single pole/multi-location<br />
single pole/multi-location<br />
120V<br />
277V<br />
VTF-6AM-<br />
VTF-6AM-277-<br />
6A<br />
6A<br />
NEW!<br />
Lyneo Lx<br />
Pushbutton<br />
preset slide<br />
dimmer<br />
single pole, 3-way, preset<br />
single pole, 3-way, preset<br />
120V<br />
277V<br />
LXF-103PL-<br />
LXF-103PL-277-<br />
8A<br />
6A<br />
1 Not to exceed 20 <strong>Lutron</strong> 3-wire <strong>dimming</strong> ballasts.<br />
42 | <strong>Lutron</strong>
Control Family<br />
RadioTouch®<br />
Wireless<br />
Multi-Zone<br />
Control<br />
Description<br />
controller<br />
wallbox transmitter<br />
tabletop transmitter<br />
Ballast<br />
Voltage<br />
Control<br />
Model Number<br />
120/277V RTA-RX-F-<br />
RTA-WX- 1<br />
RTA-TX-<br />
Control<br />
Capacity<br />
16A<br />
NEW!<br />
Spacer System <br />
Wireless Preset<br />
Scene Control<br />
GRAFIK Eye® QS<br />
Light and Shade<br />
Control System<br />
single pole<br />
single pole<br />
multi-location<br />
multi-location<br />
remote control<br />
control unit<br />
remote control (optional)<br />
120V<br />
277V<br />
120V<br />
277V<br />
120V<br />
277V<br />
SPSF-6A-<br />
SPSF-6A-277-<br />
SPSF-6AM- 2<br />
SPSF-6AM-277- 2<br />
SPS-4IT-RP<br />
QSG-_ 3 P120<br />
GRX-IT<br />
6A 1<br />
6A 1<br />
6A 1<br />
6A 1<br />
16A per zone<br />
GRAFIK Eye®<br />
Multi-Scene<br />
Preset Control<br />
control unit<br />
remote control (optional)<br />
120/277V GRX-310_ 4<br />
GRX-IT-WH<br />
16A per zone<br />
GRAFIK<br />
5000/6000/7000 TM<br />
Lighting Control<br />
System<br />
centralized lighting<br />
control<br />
120/277V<br />
Contact your <strong>Lutron</strong><br />
representative for details<br />
1 Wallbox transmitter may be powered by 120 or 277V.<br />
2 Also requires SPS-AD- or SPS-AD-277- for multi-location <strong>dimming</strong> (10 maximum).<br />
3 Insert 3, 4, or 6 (number of zones); requires PHPM-3F-DV-WH.<br />
4 Insert 2, 3, 4, or 6 (number of zones); requires PHPM-3F-DV-WH.<br />
5 For sensors, central monitoring software, etc., contact <strong>Lutron</strong>.<br />
6 Contact <strong>Lutron</strong> if more ballasts or shades are needed.<br />
<strong>Lutron</strong> | 43
<strong>Lutron</strong>® | select your fl uorescent <strong>dimming</strong> controls<br />
2-wire controls for Tu-Wire® ballasts<br />
NEW!<br />
Control Family<br />
NovaTa®<br />
Thin Profi le<br />
Slide-To-Off<br />
Dimmer<br />
Nova®<br />
Standard Profi le<br />
Slide-To-Off<br />
Dimmer<br />
Diva®<br />
Paddle Switch/<br />
Preset Slide<br />
Dimmer<br />
Skylark®<br />
Rocker Switch/<br />
Preset Slide<br />
Dimmer<br />
RadioTouch®<br />
Wireless<br />
Multi-Zone<br />
Control<br />
Spacer System <br />
Wireless Preset<br />
Scene Control<br />
GRAFIK Eye® QS<br />
Light and Shade<br />
Control System<br />
GRAFIK Eye®<br />
Multi-Scene<br />
Preset Control<br />
GRAFIK<br />
5000/6000/7000 TM<br />
Lighting Control<br />
System<br />
Ballast Control<br />
Control<br />
Description<br />
Voltage Model Number Capacity<br />
single pole 120V NTFTU-5A- 5A 1<br />
single pole 120V NFTU-5A- 5A 1<br />
single pole, 3-way 120V DVFTU-5A3P- 5A 1<br />
single pole, 3-way 120V SFTU-5A3P- 5A 1<br />
controller<br />
wallbox transmitter<br />
tabletop transmitter<br />
single pole<br />
remote control<br />
control unit<br />
remote control (optional)<br />
control unit<br />
remote control (optional)<br />
centralized lighting<br />
control<br />
120V RTA-RX-F- 2<br />
120V<br />
120V<br />
RTA-WX- 3<br />
RTA-TX-<br />
SPSFTU-5A-<br />
SPS-4IT-RP<br />
QSG-_ 4 P120<br />
GRX-IT<br />
120V GRX-310_ 5<br />
120/277V<br />
GRX-IT<br />
16A<br />
5A 1<br />
Contact your <strong>Lutron</strong><br />
representative for details<br />
16A, 6.7A per zone<br />
16A, 6.7A per zone<br />
44 | <strong>Lutron</strong><br />
1 Minimum capacity: 2 ballasts.<br />
2 Requires FDI-FTU-16A-120 interface.<br />
3 Wallbox transmitter may be powered by 120 or 277V.<br />
4 Insert 3, 4, or 6 (number of zones).<br />
5 Insert 2, 3, 4, or 6 (number of zones).<br />
6 Contact <strong>Lutron</strong> if more ballasts or shades are needed.
0-10V controls for TVE® ballasts<br />
Control Family<br />
NovaTa®<br />
Thin Profi le<br />
Slide-To-Off<br />
Dimmer<br />
Nova®<br />
Standard Profi le<br />
Slide-To-Off<br />
Dimmer<br />
Description<br />
Ballast<br />
Voltage<br />
Control<br />
Model Number<br />
Control<br />
Capacity<br />
single pole 120/277/347V NTFTV- 1 Up to 60 ballasts<br />
or Relay Pack<br />
Capacity<br />
single pole 120/277/347V NFTV- 1 Up to 60 ballasts<br />
or Relay Pack<br />
Capacity<br />
RadioTouch®<br />
Wireless<br />
Multi-Zone<br />
Control<br />
controller<br />
controller<br />
wallbox transmitter<br />
tabletop transmitter<br />
347V<br />
120/277V<br />
RTA-RX-F-347<br />
RTA-RX-F-<br />
RTA-WX- 2<br />
RTA-TX-<br />
8A/40 ballasts<br />
16A<br />
NEW!<br />
GRAFIK Eye® QS<br />
Light and Shade<br />
Control System<br />
control unit<br />
remote control (optional)<br />
120V<br />
QSG-_ 3 P120<br />
GRX-IT<br />
16A/100 ballasts<br />
multi-input digital controls for EcoSystem ballasts<br />
NEW!<br />
Control Family Description Control Model Number<br />
EcoSystem Daylight Sensor sensor<br />
C-SR-M1-WH<br />
with IR Receiver<br />
EcoSystem IR Receiver<br />
for Personal Control<br />
IR receiver C-R-M1-WH<br />
EcoSystem<br />
Occupancy Sensor<br />
EcoSystem<br />
1-Button with Raise/Lower<br />
EcoSystem<br />
4-Button with Raise/Lower<br />
QuantumTM<br />
Whole-building light and energy<br />
management<br />
sensor<br />
wall control<br />
wall control<br />
lighting hub<br />
Q-manager PC<br />
LOS-_ _ _ (Please visit<br />
www.lutron.com/occsensors for full line)<br />
CC-1BRL-WH<br />
CC-4BRL-WH<br />
1 Requires relay pack to switch power to ballasts. Please consult factory.<br />
2 Wallbox transmitter may be powered by 120 or 277V.<br />
3 Insert 3,4, or 6 (number of zones); requires GRX-TVI interface.<br />
Contact your <strong>Lutron</strong><br />
representative for details<br />
www.lutron.com/quantum<br />
<strong>Lutron</strong> | 45
www.lutron.com<br />
<strong>Lutron</strong> Electronics Co., Inc.<br />
7200 Suter Road<br />
Coopersburg, PA 18036-1299<br />
World Headquarters 1.610.282.3800<br />
Barcelona | Beijing | Berlin | Hong Kong | London | Madrid | Mexico City |<br />
Milan | Paris | Sao Paulo | Shanghai | Singapore | Tokyo<br />
Technical Support Center 1.800.523.9466<br />
Customer Service 1.888.LUTRON1<br />
Cover photograph © Peter Aaron/Esto. Architect: Davis Brody Bond Architects.<br />
Lighting design: Fisher Marantz Stone.<br />
© 07/2007 <strong>Lutron</strong> Electronics Co., Inc. | Made and printed in the U.S.A. | P/N 366-002<br />
46 | <strong>Lutron</strong>