29.01.2015 Views

fluorescent dimming systems |selection guide - Lutron

fluorescent dimming systems |selection guide - Lutron

fluorescent dimming systems |selection guide - Lutron

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

fl uorescent <strong>dimming</strong> <strong>systems</strong> | selection <strong>guide</strong><br />

July 2007<br />

<strong>Lutron</strong> | 1


<strong>Lutron</strong>® | fl uorescent <strong>dimming</strong> <strong>systems</strong><br />

Innovation and quality from the world leader in lighting controls.<br />

<strong>Lutron</strong> invented the world’s fi rst electronic<br />

<strong>dimming</strong> ballast over 30 years ago. From that<br />

point forward, <strong>Lutron</strong> has delivered value through<br />

a wide range of fl uorescent <strong>dimming</strong> options.<br />

<strong>Lutron</strong> offers an extensive selection of ballasts<br />

and controls, providing complete fl uorescent<br />

<strong>dimming</strong> <strong>systems</strong> to our customers.<br />

NEW Hi-lume® 3D digitally addressable <strong>dimming</strong> ballast<br />

2 | <strong>Lutron</strong>


<strong>Lutron</strong>’s fi rst principle:<br />

Taking care of you, our customer.<br />

Worldwide sales<br />

and service<br />

The <strong>Lutron</strong> Team is here to<br />

support you wherever and<br />

whenever you need us.<br />

Technical Support:<br />

24 Hours/7 Days<br />

1.800.523.9466<br />

Customer Service:<br />

8am-8pm ET<br />

1.888.LUTRON1<br />

Internet Support:<br />

www.lutron.com<br />

Commitment to innovation<br />

For over 45 years, <strong>Lutron</strong> has been dedicated to providing<br />

innovative products, services and technologies. We help you<br />

design, specify, and deliver the best performance, quality,<br />

and value to your customers.<br />

World-class quality<br />

<strong>Lutron</strong> quality is fueled by a relentless pursuit of the highest<br />

standards. Constant improvement includes an integrated<br />

quality system, strict engineering <strong>guide</strong>lines, and world-class<br />

quality and manufacturing processes.<br />

Comprehensive lighting control solutions<br />

<strong>Lutron</strong> is your comprehensive resource for lighting control<br />

solutions for any commercial or institutional application.<br />

Lighting Control Institute:<br />

1.610.282.6280<br />

Field Service:<br />

1.800.523.9466<br />

How to use this selection <strong>guide</strong>:<br />

The <strong>Lutron</strong> Fluorescent Dimming Systems Selection Guide helps you:<br />

• Determine the <strong>dimming</strong> range required for your application<br />

• Choose the appropriate <strong>Lutron</strong> <strong>dimming</strong> ballast<br />

• Choose your <strong>Lutron</strong> fl uorescent control<br />

In other sections of the Lighting Controls for Commercial<br />

Applications binder you will fi nd information on:<br />

• Architectural <strong>dimming</strong> <strong>systems</strong><br />

• Low-voltage switching <strong>systems</strong><br />

• Architectural <strong>dimming</strong> ballasts<br />

• Theatrical <strong>dimming</strong> capabilities<br />

• Integrated lighting<br />

automation <strong>systems</strong><br />

• Motorized window treatments<br />

• Floorplan based control software<br />

• Factory service plans<br />

<strong>Lutron</strong> | 01


<strong>Lutron</strong>® | table of contents<br />

Why dim fl uorescent 03<br />

<strong>Lutron</strong> quality 04<br />

Ballast control types 06<br />

Digitally addressable <strong>dimming</strong> ballasts 07<br />

Measured light vs. perceived light 08<br />

Dimming applications 09<br />

Benefi ts of 1% <strong>dimming</strong> 10<br />

Hi-lume® 1% 3-wire <strong>dimming</strong> ballasts 12<br />

Hi-lume® 3D 1% digital addressable <strong>dimming</strong> ballasts 14<br />

Compact SE 5% 3-wire <strong>dimming</strong> ballasts 16<br />

Tu-Wire® 5% 2-wire <strong>dimming</strong> ballasts 18<br />

EcoSystem 10% multi-input digital <strong>dimming</strong> ballasts 20<br />

Eco-10® 10% 3-wire <strong>dimming</strong> ballasts 22<br />

TVE 10% 0-10V <strong>dimming</strong> ballasts 24<br />

Select your <strong>dimming</strong> ballasts 26<br />

Ballast case dimensions 36<br />

Fluorescent <strong>dimming</strong> controls 38<br />

EcoSystem components 40<br />

Select your fl uorescent <strong>dimming</strong> controls 42<br />

Please see the <strong>Lutron</strong> Fluorescent<br />

Dimming Systems Technical Guide<br />

(P/N 366-606) for details on <strong>dimming</strong><br />

ballast installation, wiring, and other<br />

important information.<br />

See the <strong>Lutron</strong> EcoSystem Technical<br />

Guide (shown at right) (P/N 367-1028)<br />

for detailed information on EcoSystem<br />

light control solution.<br />

02 | <strong>Lutron</strong>


<strong>Lutron</strong>® | why dim fl uorescent<br />

The benefi ts of <strong>dimming</strong><br />

Create enticing ambiance<br />

Dimming creates a rich visual experience and adds<br />

fl exibility to any room, providing the right lighting<br />

environment for a variety of activities.<br />

Save electricity, maintain lamp life, and<br />

save the environment<br />

Dimming saves electricity and reduces the demand on<br />

HVAC <strong>systems</strong>. Dimming fl uorescent lighting instead<br />

of repeated switching helps to maintain lamp life.<br />

Give employees greater personal control<br />

Allowing employees to set preferred light levels<br />

for specifi c tasks results in greater employee<br />

comfort and improved performance.<br />

Combine lighting control strategies to<br />

enhance building performance<br />

Using occupancy sensors, daylight sensors and time<br />

clocks with fl uorescent <strong>dimming</strong> can help manage<br />

the lighting in an entire building and further reduce<br />

electric demand.<br />

Dimming fl uorescents saves energy<br />

Fluorescent lighting uses much less power<br />

than incandescent lighting. In a typical<br />

installation, a 32 watt compact fl uorescent<br />

lamp provides approximately the same light<br />

output as a 100 watt incandescent lamp.<br />

As both sources are dimmed, fl uorescent<br />

lamps continue to be a more energy<br />

effi cient light source.<br />

100W<br />

Power consumed by incandescent source<br />

Power<br />

80<br />

60<br />

40<br />

Over 60 watts of power<br />

is saved per fi xture by using<br />

fl uorescent lamps<br />

Power consumed by fl uorescent source<br />

20<br />

0<br />

0 20 40 60 80 100%<br />

Measured Light<br />

<strong>Lutron</strong> | 03


<strong>Lutron</strong>® | quality<br />

Superior components<br />

<strong>Lutron</strong> ballasts are manufactured to the highest<br />

level of quality, using carefully selected components.<br />

Maximum ballast lifetime is achieved by using only<br />

long-life components with signifi cant performance<br />

history. In many cases, <strong>Lutron</strong> works with component<br />

suppliers to design custom parts in order to improve<br />

overall ballast quality.<br />

Additionally, <strong>Lutron</strong> uses only metal ballast<br />

enclosures, allowing for optimal heat transfer<br />

to the lighting fi xture.<br />

Thermal Foldback<br />

<strong>Lutron</strong>’s patented Thermal Foldback technology<br />

is included in high-power ballasts, and actively<br />

monitors the ballast temperature. Power delivery<br />

to the lamps is automatically reduced, or “folded<br />

back”, to regulate ballast temperature, with minimal<br />

impact on light output. Thermal Foldback is designed<br />

to activate only if the ballast calibration point exceeds<br />

its rating. This maintains the ballast temperature to<br />

within 5ºC of its rating, preventing premature ballast<br />

failure from overheating. In a properly designed<br />

application, Thermal Foldback will not engage.<br />

Refer to Fluorescent Dimming Systems Technical<br />

Guide P/N 366-606 for information about proper<br />

installation and the calibration point.<br />

04 | <strong>Lutron</strong>


Failure Rate<br />

100% Test<br />

<strong>Lutron</strong> tests the performance of every ballast prior to<br />

shipment. This important step eliminates ballasts that<br />

do not meet specifi cations.<br />

100% Burn-in<br />

<strong>Lutron</strong> “burns in” every ballast prior to shipment.<br />

Defects due to faulty components are screened<br />

out in this process, resulting in a dramatic reduction<br />

of early failures in the fi eld.<br />

Extending ballast lifetime<br />

All electronic ballasts use components with a fi nite<br />

lifetime. A major factor for ballast lifetime is operating<br />

temperature. <strong>Lutron</strong> <strong>dimming</strong> ballasts are designed<br />

to maximize ballast lifetime.<br />

You have an opportunity to extend the lifetime of the<br />

ballast even further by designing or choosing fi xtures<br />

that operate the ballast at a lower temperature. For<br />

every 10ºC reduction in ballast case temperature,<br />

the ballast lifetime will be doubled.<br />

Customer receives<br />

<strong>Lutron</strong> ballast<br />

Low<br />

failure rate<br />

Useful life<br />

Running ballasts 10˚C Cooler<br />

DOUBLES useful life<br />

<strong>Lutron</strong> test<br />

and burn-in<br />

Product reliability curve<br />

<strong>Lutron</strong> <strong>dimming</strong> ballasts are burnt in prior to<br />

shipment, ensuring lower failure rate in the fi eld.<br />

Running ballasts 10ºC cooler can also double<br />

their useful life.<br />

Time<br />

Dimming by <strong>Lutron</strong>® OEM Program<br />

<strong>Lutron</strong> offers on-site factory training to OEM fi xture<br />

manufacturers through the Dimming by <strong>Lutron</strong> OEM<br />

Program. Additionally, the program allows OEM<br />

fi xture manufacturers to work together with <strong>Lutron</strong><br />

to grow sales, strengthen customer loyalty and<br />

satisfaction, and differentiate products. Doing<br />

business with <strong>Lutron</strong> has never been easier.<br />

For more information on the Dimming by<br />

<strong>Lutron</strong> OEM Program, please visit<br />

www.lutron.com/OEM.<br />

<strong>Lutron</strong> | 05


<strong>Lutron</strong>® | ballast control types<br />

In addition to offering ballasts with different low-end<br />

<strong>dimming</strong> levels, <strong>Lutron</strong> offers <strong>dimming</strong> ballasts with<br />

a variety of industry-standard control options.<br />

Hot<br />

Dimmed Hot<br />

Neutral<br />

3-wire<br />

3-wire control is a line-voltage phase-control <strong>dimming</strong> method.<br />

Along with Hot and Neutral, the <strong>dimming</strong> signal is communicated<br />

via a third wire called Dimmed Hot. All three wires are rated Class 1<br />

and can be run within the same conduit. 3-wire control is stable over<br />

long wire runs, allows for maximum circuit loading, and is very easy<br />

to wire.<br />

Dimmed Hot<br />

Neutral<br />

2-wire<br />

2-wire control is a line-voltage phase-control <strong>dimming</strong> method.<br />

The ballast receives the <strong>dimming</strong> signal through the Dimmed Hot<br />

wire. Intended for small-scale retrofi t applications, the 2-wire control<br />

method is often the easiest way to implement <strong>dimming</strong> in existing<br />

fl uorescent fi xtures.<br />

Hot<br />

Neutral<br />

Control (+)<br />

Control (–)<br />

0-10V<br />

0-10V control is a low-voltage DC <strong>dimming</strong> method. Power<br />

wires are rated Class 1 and control wires are rated Class 2.<br />

This separation allows multiple circuits to use the same <strong>dimming</strong><br />

signal without additional power equipment. 0-10V control is not<br />

recommended for <strong>dimming</strong> below 10%, as fi xture-to-fi xture<br />

tracking can be signifi cantly affected by control wire length.<br />

Hot<br />

Neutral<br />

Control<br />

Control<br />

Multi-input digital<br />

Multi-input digital control is a wired communication technology that<br />

facilitates individual ballast addressing, connection of multiple control<br />

devices, and control of ballasts individually or in groups. The digital<br />

wires are polarity insensitive and may be wired in any topology. Digital<br />

communication wires may be run with the mains voltage (Class 1) or<br />

isolated from mains (Class 2). Multi-input digital control allows for the<br />

quick connection of devices and re-confi gurability.<br />

06 | <strong>Lutron</strong>


<strong>Lutron</strong>® | digitally addressable <strong>dimming</strong> ballasts<br />

A revolution in light control for<br />

open offi ces and classrooms<br />

A breakthrough in fl uorescent lighting control,<br />

multi-input digital control solutions start with a<br />

simple but essential building block–a digitally<br />

addressable <strong>dimming</strong> ballast–which replaces a<br />

non-dim ballast in a fi xture. Hi-lume® 3D and<br />

EcoSystem are examples of digitally addresable<br />

ballasts. Benefi ts:<br />

Simple to design<br />

• Fewer components<br />

• Can be wired topology- and polarity-free<br />

• No interfaces required<br />

Easy to maintain<br />

• No reprogramming when components are replaced<br />

• Infi nite re-confi gurability without Class 1 rewiring<br />

Cost effective<br />

• Costs less than other solutions available today<br />

• Fewer parts and pieces to install<br />

For details on Hi-Lume 3D,<br />

visit www.lutron.com/3d.<br />

For details on Ecosystem,<br />

visit www.lutron.com/ecosystem.<br />

<strong>Lutron</strong> | 07


<strong>Lutron</strong>® | measured light vs. perceived light<br />

The human eye responds to low light levels by<br />

enlarging the pupil, allowing more light to enter the<br />

eye. This response results in a difference between<br />

measured and perceived light levels. A lamp<br />

that is dimmed to 10% of its maximum measured<br />

light output is perceived as being dimmed to<br />

only 32%. Likewise, a lamp dimmed to 1%<br />

is perceived to be at 10%.<br />

1% Architectural <strong>dimming</strong><br />

5% High performance <strong>dimming</strong><br />

100%<br />

10% Lighting management <strong>dimming</strong><br />

90<br />

80<br />

70<br />

Measured<br />

Light<br />

60<br />

50<br />

40<br />

30<br />

20<br />

10<br />

5<br />

1<br />

0 10 22 32 40 50 60 70 80 90 100%<br />

Perceived Light<br />

Formula:<br />

Perceived Light (%) = 100 x<br />

Measured Light (%)<br />

100<br />

Source: IESNA Lighting Handbook, 9th Edition, (New York: IESNA, 2000), 27-4.<br />

08 | <strong>Lutron</strong>


<strong>Lutron</strong>® | <strong>dimming</strong> applications<br />

1%<br />

Architectural <strong>dimming</strong><br />

5%<br />

High performance <strong>dimming</strong><br />

10%<br />

Lighting management <strong>dimming</strong><br />

• Conference room/Boardroom<br />

• Lecture hall<br />

• Patient room/Examination<br />

and treatment room<br />

• House of worship<br />

• Theater<br />

• Convention area<br />

• Restaurants<br />

• Air traffi c control center<br />

• Industrial control room<br />

• Partitioned meeting room<br />

• Graphic art workstation<br />

• CAD/CAM workstation<br />

• Private offi ce<br />

• Retail<br />

• Presentation spaces<br />

• Critical task spaces<br />

• Small meeting room<br />

• Lobby<br />

• Hotel guest room<br />

• Residential (See page 28 for<br />

appropriate ballast types.)<br />

• Large open offi ce<br />

• Corridor/Stairwell<br />

• Utility room<br />

• Restroom<br />

• Customer service area/<br />

Call center<br />

• Classroom<br />

Design example<br />

At full brightness, the measured light in a space is 60 foot-candles.<br />

At the lowest dimmed level, 10% perceived light is desired.<br />

1% measured light (0.6 fcd)<br />

is perceived as 10%<br />

(desired result)<br />

5% measured light (3 fcd)<br />

is perceived as 22%<br />

(2x brighter than desired)<br />

10% measured light (6 fcd)<br />

is perceived as 32%<br />

(3x brighter than desired)<br />

<strong>Lutron</strong> | 09


<strong>Lutron</strong>® | benefi ts of 1% <strong>dimming</strong><br />

Architectural <strong>dimming</strong><br />

Architectural spaces often have a strong<br />

focus on aesthetics and comfort, creating an<br />

environment that portrays class and distinction.<br />

Architects and designers create these spaces<br />

for maximum versatility and require subtle<br />

control of the lighting. At <strong>Lutron</strong>, we design<br />

fl uorescent <strong>dimming</strong> ballasts to respond<br />

to the fi nest lighting adjustments required.<br />

Hi-lume® <strong>dimming</strong> ballasts allow control<br />

of your fl uorescent lights through full-range<br />

100% to 1% light output, providing the<br />

greatest available functionality for architectural<br />

fl uorescent lighting.<br />

10 | <strong>Lutron</strong><br />

Photograph © Nikolas Koenig.<br />

Architect: Richard Meyer & Partners, Architects.<br />

Lighting design: L’Observatoire International.


Hi-lume® | 1%<br />

Hi-lume 1% applications<br />

For years, 1% <strong>dimming</strong> has been the standard<br />

for conference room lighting. 1% CFL (compact<br />

fl uorescent lamps) <strong>dimming</strong> has opened up new<br />

areas for fl uorescents, giving required performance<br />

while meeting strict energy codes.<br />

In restaurants, combining Hi-lume with inviting,<br />

colored refl ectors creates a warm and intimate<br />

atmosphere for distinctive dining.<br />

Patient care areas need dimmed lights at<br />

night, but require bright light and true color<br />

rendering for accurate medical examinations.<br />

Fluorescent sources, with their consistent<br />

color temperature throughout the <strong>dimming</strong><br />

range, are an ideal source.<br />

Partitioned spaces, like conference rooms<br />

or ballrooms, require 1% <strong>dimming</strong> for specifi c<br />

tasks, allowing for a variety of activities to use<br />

the same space.<br />

Restaurants<br />

Patient<br />

Care Areas<br />

Photograph © Nikolas Koenig.<br />

Partitioned Spaces<br />

<strong>Lutron</strong> | 11


<strong>Lutron</strong>® | 1% architectural <strong>dimming</strong><br />

Hi-lume®<br />

Experience the benefi ts of true full-range 100%<br />

to 1% fl uorescent <strong>dimming</strong>. Designed to meet<br />

the most demanding lighting requirements,<br />

Hi-lume ballasts enable you to provide the<br />

ideal visual environment for any application.<br />

The Hi-lume family is extensive, featuring the<br />

world’s only 100% to 1% <strong>dimming</strong> ballasts<br />

for T4 compact fl uorescent lamps. Integrating<br />

Hi-lume 1% technology into your designs<br />

affords you full control over the lighting<br />

in any space.<br />

For maximum fl exibility, <strong>Lutron</strong> offers a<br />

full line of Hi-lume ballasts that are compatible<br />

with 3-wire and digital controls.<br />

Photograph © Kerun Ip,<br />

courtesy of Pei Partnership Architects.<br />

<strong>Lutron</strong> ballasts are tested for performance<br />

with Philips®, Sylvania®, and GE® lamps.<br />

For the complete listing of Hi-lume ballasts<br />

by <strong>Lutron</strong>, please see pages 26-29.<br />

• Dims T5-HO linear lamps<br />

• Hi-lume 3D Dims T8 Linear and<br />

T8 U-bent<br />

• Just 1” high x 1.18” wide<br />

• Color-keyed push-in connectors<br />

12 | <strong>Lutron</strong><br />

• Dims T8 linear and<br />

U-bent lamps<br />

• Dims T4 triple-tube<br />

compact lamps<br />

• Slim-profi le design–just 1” high<br />

• Color-keyed push-in connectors<br />

• Available with or without<br />

mounting studs


Hi-lume® | 1%<br />

Performance<br />

• Continuous, fl icker-free <strong>dimming</strong><br />

from 100% to 1%<br />

• Models available for T4 triple-tube CFL,T5-<br />

HO, and T8 lamps<br />

• 3-wire line voltage control for consistent fi x-<br />

ture-to-fi xture <strong>dimming</strong><br />

• Lamps turn on at any dimmed level without<br />

fl ashing to full brightness<br />

• Low harmonic distortion<br />

• Miswire protection<br />

• Slim-profi le and standard designs available<br />

• 100% performance tested<br />

• Ultra-quiet operation<br />

• Designed in the USA<br />

• 5-year warranty (limited) with fi eld service<br />

commissioning (3-year warranty standard)<br />

Specifications<br />

• Architectural <strong>dimming</strong> from 100% to 1% relative<br />

light output<br />

• No visible fl icker<br />

• Total Harmonic Distortion (THD) less than 10%<br />

• Power factor greater than .95<br />

• Ballast factor greater than .85 for T8 lamps<br />

• Ballast factor greater than .95 for T4 lamps<br />

• Ballast factor equal to 1.0 for T5-HO lamps<br />

• Frequency of operation greater than 25 kHz for T8<br />

lamps<br />

• Frequency of operation greater than 42 kHz for T4<br />

and T5-HO lamps<br />

• Inaudible in 27 dBA ambient environment<br />

• Inrush current limiting circuitry built-in (maximum of<br />

7 amps for 120V and 3 amps at 277V)<br />

• Internal fusing<br />

• Minimum lamp starting temperature 10°C (50°F)<br />

• Maximum ballast case temperature 75°C (167°F)<br />

3-wire control<br />

For the full offering of Hi-lume <strong>dimming</strong> ballast controls by<br />

<strong>Lutron</strong>, please see pages 42 and 43.<br />

Hot<br />

Control<br />

Hot<br />

120/277VAC<br />

60Hz Feed<br />

Neutral<br />

Dimmed Hot<br />

Neutral<br />

Dimming<br />

Ballast<br />

<strong>Lutron</strong> | 13


<strong>Lutron</strong>® | 1% architectural <strong>dimming</strong><br />

Hi-lume® 3D<br />

Hi-lume 3D is a high-performance, energy-effi cient<br />

<strong>dimming</strong> ballast for demanding architectural<br />

applications. Hi-lume 3D is the world’s fi rst<br />

fl uorescent <strong>dimming</strong> ballast that can dim lights<br />

to less than 1% and more than 100% of rated<br />

lamp illumination for the most demanding lighting<br />

requirements. With Hi-lume 3D you get the highest<br />

performance fl uorescent <strong>dimming</strong> with the same<br />

effi ciency as non-dim ballasts.<br />

Hi-lume 3D is ideal for:<br />

• Ballrooms<br />

• Conference rooms<br />

• Critical task applications<br />

• Presentation spaces<br />

• Lobbies<br />

• Control rooms<br />

• Classrooms<br />

3 Dimensions of innovation<br />

Performance: broadest <strong>dimming</strong> range, 100% to<br />

0.7% of full light output.<br />

Versatility: compatible with a broad range of 3-wire<br />

controls and digital controls (EcoSystem /DALI). Plus,<br />

universal voltage input and small 1” high profi le to fi t<br />

any fi xture.<br />

Efficiency: industry-leading ballast effi cacy of up to<br />

91 lumens per watt.<br />

For the complete listing of Hi-lume® 3D ballasts<br />

by <strong>Lutron</strong>, please see page 30.<br />

• Dims T8 linear and U-bent lamps<br />

• Slim-profi le design–just 1” high x 1.18” wide<br />

14 | <strong>Lutron</strong>


Hi-lume® 3D | 1%<br />

Performance<br />

• Continuous, fl icker-free <strong>dimming</strong> down to<br />

0.7% of full light output<br />

• Models available for T8 lamps<br />

• EcoSystem digital bus control<br />

• Digital inputs allow for rezoning without rewiring<br />

• Lamps turn on at any dimmed level without<br />

fl ashing to full brightness<br />

• Low harmonic distortion<br />

• Miswire protection<br />

• Meets FCC Part 18 Non-Consumer requirements<br />

for EMI/RFI emissions<br />

• 100% performance tested<br />

• Ultra-quiet operation<br />

Specifications<br />

• No visible fl icker<br />

• Total Harmonic Distortion (THD) less than 10%<br />

• Power factor greater than .95<br />

• Frequency of operation greater than 42 kHz<br />

• Inaudible in 27 dBA ambient environment<br />

• Inrush current limiting circuitry built-in (maximum of<br />

7 amps for 120V and 3 amps at 277V)<br />

• Internal fusing<br />

• Minimum lamp starting temperature 10°C (50°F)<br />

• Maximum ballast case temperature 75°C (167°F)<br />

• Universal input voltage 120V/277V<br />

• Available in 1.0 and 1.17 ballast factor<br />

• Designed in the USA<br />

• 5-year warranty (limited) with fi eld service<br />

commissioning (3-year warranty standard)<br />

Multi-input digital control<br />

For the full offering of Hi-lume 3D <strong>dimming</strong> ballast<br />

controls by <strong>Lutron</strong>, please see page 42 and 43.<br />

Hot<br />

Neutral<br />

Dimming<br />

Ballast<br />

E1*<br />

E2*<br />

or<br />

Hot<br />

Dimmed Hot<br />

Neutral<br />

* To other ballasts and digital bus control<br />

<strong>Lutron</strong> | 15


<strong>Lutron</strong>® | 5% high performance <strong>dimming</strong><br />

Compact SETM<br />

For designs requiring the energy savings<br />

and aesthetic appeal of dimmed compact<br />

fl uorescent lamps, Compact SE <strong>dimming</strong><br />

ballasts are your solution. The Compact SE<br />

product family includes ballasts for nearly<br />

every type of compact fl uorescent lamp.<br />

Compact SE <strong>dimming</strong> ballasts deliver<br />

high performance 100% to 5% <strong>dimming</strong>,<br />

making them ideal for use in a variety of<br />

applications. In addition, Compact SE<br />

ballasts are compatible with the full line<br />

of 3-wire controls by <strong>Lutron</strong>.<br />

For the complete listing of Compact SE<br />

ballasts by <strong>Lutron</strong>, please see pages 26-29.<br />

Photograph © Kerun Ip,<br />

courtesy of Pei Partnership Architects.<br />

• Dims T5 twin-tube lamps<br />

16 | <strong>Lutron</strong><br />

• Dims T4 quad- and triple-tube<br />

compact lamps<br />

• Slim-profi le design–just 1” high<br />

• Color-keyed push-in connectors<br />

• Available with or without mounting studs


Compact SETM |<br />

5%<br />

Performance<br />

• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />

to 5% (for 1% <strong>dimming</strong> of compact fl uorescent<br />

lamps, see page 12)<br />

• 3-wire line voltage control for consistent fi x-<br />

ture-to-fi xture <strong>dimming</strong><br />

• Lamps turn on at any dimmed level without<br />

fl ashing to full brightness<br />

• Low harmonic distortion<br />

• Miswire protection<br />

• Slim-profi le design<br />

• 100% performance tested<br />

• Ultra-quiet operation<br />

• Designed in the USA<br />

• 5-year warranty (limited) with fi eld service<br />

commissioning (3-year warranty standard)<br />

Specifications<br />

• High performance <strong>dimming</strong> from 100% to 5%<br />

relative light output<br />

• No visible fl icker<br />

• Total Harmonic Distortion (THD) less than 10%<br />

• Power factor greater than .95<br />

• Ballast factor greater than .85 for<br />

T5 twin-tube lamps<br />

• Ballast factor greater than .95 for T4 quadand<br />

triple-tube compact lamps<br />

• Frequency of operation greater than 27 kHz for<br />

T5 twin-tube lamps<br />

• Frequency of operation greater than 42 kHz for<br />

T4 quad- and triple-tube compact lamps<br />

• Inaudible in 27 dBA ambient environment<br />

• Inrush current limiting circuitry built-in (maximum<br />

of 7 amps for 120V and 3 amps at 277V)<br />

• Internal fusing<br />

• Minimum lamp starting temperature 10°C (50°F)<br />

• Maximum ballast case temperature 75°C (167°F)<br />

3-wire control<br />

For the full offering of Compact SE <strong>dimming</strong> ballast controls<br />

by <strong>Lutron</strong>, please see pages 42 and 43.<br />

Hot<br />

Control<br />

Hot<br />

120/277VAC<br />

60Hz Feed<br />

Neutral<br />

Dimmed Hot<br />

Neutral<br />

Dimming<br />

Ballast<br />

<strong>Lutron</strong> | 17


<strong>Lutron</strong>® | 5% high performance <strong>dimming</strong><br />

Tu-Wire ®<br />

Retrofi t and small-space applications can<br />

benefi t from the ease of installation offered<br />

by <strong>Lutron</strong> Tu-Wire <strong>dimming</strong> ballasts.<br />

Tu-Wire ballasts offer high performance<br />

100% to 5% <strong>dimming</strong> for linear and<br />

compact fl uorescent lamps.<br />

Tu-Wire ballasts require only two wires<br />

(hot and neutral) for power and control.<br />

<strong>Lutron</strong> offers a wide range of compatible<br />

2-wire controls, making Tu-Wire a perfect<br />

choice for many applications. Additionally,<br />

one-lamp T4 models have been designed to<br />

meet FCC Part 18 consumer requirements.<br />

For the complete listing of Tu-Wire ballasts<br />

by <strong>Lutron</strong>, please see page 32.<br />

Interiors by Staffelbach<br />

Design Associates.<br />

• Dims T8 lamps<br />

• Slim-profi le design–just 1” high x 1.18” wide<br />

• Color-keyed push-in connectors<br />

18 | <strong>Lutron</strong><br />

• Dims T4 quad- and triple-tube<br />

compact lamps<br />

• Slim-profi le design–just 1” high<br />

• Color-keyed push-in connectors<br />

• Available with or without mounting studs


Tu-Wire ® | 5%<br />

Performance<br />

• Continuous, fl icker-free <strong>dimming</strong> from<br />

100% to 5%<br />

• 2-wire line voltage control for<br />

retrofi t applications<br />

• Lamps turn on at any dimmed level without<br />

fl ashing to full brightness<br />

• Low harmonic distortion<br />

• Slim-profi le design<br />

• One-lamp T4 models meet FCC Part 18<br />

consumer requirements for residential use<br />

(FCC ID: JPZB001)<br />

• 100% performance tested<br />

• Ultra-quiet operation<br />

• Designed in the USA<br />

• 5-year warranty (limited) with fi eld service<br />

commissioning (3-year warranty standard)<br />

Specifications<br />

• High performance <strong>dimming</strong> from 100% to 5%<br />

relative light output<br />

• No visible fl icker<br />

• Total Harmonic Distortion (THD) less than 20%<br />

• Power factor greater than .95<br />

• Ballast factor greater than .85 for T4 lamps<br />

• Ballast factor equal to 1.0 for T8 lamps<br />

• Frequency of operation greater than 42 kHz<br />

• Inaudible in 27 dBA ambient environment<br />

• Inrush current limiting circuitry built-in (maximum of<br />

7 amps inrush current per ballast)<br />

• Internal fusing<br />

• Minimum lamp starting temperature 10°C (50°F)<br />

• Maximum ballast case temperature 75°C (167°F)<br />

2-wire control<br />

For the full offering of Tu-Wire <strong>dimming</strong> ballast controls by<br />

<strong>Lutron</strong>, please see page 44.<br />

Hot<br />

Control<br />

Dimmed Hot<br />

120VAC<br />

60Hz Feed<br />

Neutral<br />

Neutral<br />

Dimming<br />

Ballast<br />

<strong>Lutron</strong> | 19


<strong>Lutron</strong>® | 10% lighting management <strong>dimming</strong><br />

EcoSystemTM<br />

EcoSystem devices employ revolutionary<br />

technology allowing each device to listen, think,<br />

decide and remember. EcoSystem fl uorescent<br />

lighting control solutions create fl uorescent lighting<br />

control <strong>systems</strong> with a simple building block<br />

architecture of EcoSystem fl uorescent <strong>dimming</strong><br />

ballasts, EcoSystem sensors, and EcoSystem<br />

controls, free from interfaces and power packs.<br />

EcoSystem fl uorescent solutions redefi ne<br />

fl uorescent lighting control as easy to design,<br />

easy to install, easy to maintain and cost effective.<br />

For the complete listing of EcoSystem<br />

ballasts by <strong>Lutron</strong>, please see<br />

pages 34 and 35.<br />

• Dims T8 linear and U-bent, T5 linear, and<br />

T5-HO linear lamps<br />

• Slim-profi le design–just 1” high x 1.18” wide<br />

• Color-keyed push-in connections<br />

• Dims T8 linear and U-bent lamps<br />

• Color-keyed push-in connectors<br />

with or without leads<br />

20 | <strong>Lutron</strong>


EcoSystemTM | 10%<br />

Performance<br />

• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />

to 10%<br />

• Models available for T5, T5-HO, and T8 lamps<br />

• Multi-input digital control<br />

• Digital inputs allow for rezoning without rewiring<br />

• High effi ciency–up to 92 lumen per watt<br />

• Lamps turn on at any dimmed level without<br />

fl ashing to full brightness<br />

• Low harmonic distortion<br />

• Miswire protection<br />

• Slim-profi le and standard designs available<br />

• Meets FCC Part 18 Non-Consumer requirements<br />

for EMI/RFI emissions<br />

• 100% performance tested<br />

• Ultra-quiet operation<br />

• Designed in the USA<br />

• 5-year warranty (limited) with fi eld service<br />

commissioning (3-year warranty standard)<br />

Specifications<br />

• Lighting management <strong>dimming</strong> from 100% to 10%<br />

relative light output<br />

• No visible fl icker<br />

• Total Harmonic Distortion (THD) less than 20%<br />

• Power factor greater than .95<br />

• Ballast factor greater than .85 for T8 lamps<br />

• Ballast factor equal to 1.0 for T5 and T5-HO lamps<br />

• Frequency of operation greater than 42 kHz<br />

• Inaudible in 27 dBA ambient environment<br />

• Inrush current limiting circuitry built-in (maximum of<br />

7 amps for 120V and 3 amps at 277V)<br />

• Internal fusing<br />

• Minimum lamp starting temperature 10°C (50°F)<br />

• Maximum ballast case temperature 75°C (167°F)<br />

Multi-input digital control<br />

For the full offering of EcoSystem <strong>dimming</strong> ballast<br />

controls by <strong>Lutron</strong>, please see page 45.<br />

Hot<br />

Neutral<br />

Dimming<br />

Ballast<br />

E1*<br />

E2* Sensors<br />

* To other ballasts and digital bus control<br />

<strong>Lutron</strong> | 21


<strong>Lutron</strong>® | 10% lighting management <strong>dimming</strong><br />

Eco-10®<br />

To maximize the benefi ts of a lighting<br />

management system, use Eco-10 <strong>dimming</strong><br />

ballasts by <strong>Lutron</strong>. Eco-10 offers 100%<br />

to 10% <strong>dimming</strong>, and is ideal for use in any<br />

space where saving energy is the primary<br />

goal, and critical performance is secondary.<br />

Eco-10 ballasts are available for a large<br />

range of lamps, making them an ideal<br />

choice for applications with many different<br />

fi xture types. In addition, Eco-10 ballasts<br />

are fully compatible with <strong>Lutron</strong>’s complete<br />

line of 3-wire fl uorescent controls.<br />

For the complete listing of Eco-10 ballasts<br />

by <strong>Lutron</strong>, please see pages 26-29.<br />

Photograph © Peter Aaron/Esto.<br />

Architect: Robert A.M. Stern Architects.<br />

• Dims T5 twin-tube lamps<br />

22 | <strong>Lutron</strong><br />

• Dims T8 linear and U-bent, T5 linear, and<br />

T5-HO linear lamps<br />

• Dims 2’ and 3’ T5 lamps<br />

• Slim-profi le design–just 1” high x 1.18” wide<br />

• Color-keyed push-in connectors


Eco-10® | 10%<br />

Performance<br />

• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />

to 10%<br />

• 3-wire line-voltage control for consistent<br />

fi xture-to-fi xture <strong>dimming</strong><br />

• Lamps turn on at any dimmed level without<br />

fl ashing to full brightness<br />

• Low harmonic distortion<br />

• Slim-profi le and standard designs available<br />

• 100% performance tested<br />

• Ultra-quiet operation<br />

• Designed in the USA<br />

• 5-year warranty (limited) with fi eld service<br />

commissioning (3-year warranty standard)<br />

Specifications<br />

• Lighting management <strong>dimming</strong> from 100% to 10%<br />

relative light output<br />

• No visible fl icker<br />

• Total Harmonic Distortion (THD) less than 20%<br />

• Power factor greater than .95<br />

• Ballast factor greater than .85 for T8 lamps and T5<br />

twin-tube lamps<br />

• Ballast factor equal to 1.0 for T5 and T5-HO lamps<br />

• Frequency of operation greater than 25 kHz for T8<br />

lamps and T5 twin-tube lamps<br />

• Frequency of operation greater than 42 kHz for T5<br />

and T5-HO lamps<br />

• Inaudible in 27 dBA ambient environment<br />

• Inrush current limiting circuitry built-in (maximum of<br />

7 amps for 120V and 3 amps at 277V)<br />

• Internal fusing<br />

• Minimum lamp starting temperature 10°C (50°F)<br />

• Maximum ballast case temperature 75°C (167°F)<br />

3-wire control<br />

For the full offering of Eco-10 <strong>dimming</strong> ballast controls<br />

by <strong>Lutron</strong>, please see pages 42 and 43.<br />

Hot<br />

Control<br />

Hot<br />

120/277VAC<br />

60Hz Feed<br />

Neutral<br />

Dimmed Hot<br />

Neutral<br />

Dimming Ballast<br />

<strong>Lutron</strong> | 23


<strong>Lutron</strong>® | 10% lighting management <strong>dimming</strong><br />

TVETM<br />

For applications requiring the use of 0-10V<br />

control, <strong>Lutron</strong> offers the TVE family of<br />

fl uorescent <strong>dimming</strong> ballasts. TVE ballasts<br />

are designed to work seamlessly with<br />

0-10V lighting management <strong>systems</strong>,<br />

including daylight harvesting and<br />

occupancy detection schemes.<br />

<strong>Lutron</strong> offers many choices for 0-10V<br />

controls, including interfaces to many of<br />

our <strong>dimming</strong> <strong>systems</strong>.<br />

For the complete listing of TVE ballasts<br />

by <strong>Lutron</strong>, please see page 33.<br />

• Dims T8 linear and U-bent lamps<br />

• 0-10V control<br />

• 347V ballasts available<br />

24 | <strong>Lutron</strong>


TVETM | 10%<br />

Performance<br />

• Continuous, fl icker-free <strong>dimming</strong> from 100%<br />

to 10%<br />

• 0-10V control<br />

• Lamps turn on at any dimmed level without<br />

fl ashing to full brightness<br />

• Low harmonic distortion<br />

• 100% performance tested<br />

• Ultra-quiet operation<br />

• Designed in the USA<br />

• 5-year warranty (limited) with fi eld service<br />

commissioning (3-year warranty standard)<br />

Specifications<br />

• Lighting management <strong>dimming</strong> from 100% to 10%<br />

relative light output<br />

• No visible fl icker<br />

• Total Harmonic Distortion (THD) less than 20%<br />

• Power factor greater than .95<br />

• Ballast factor greater than .85<br />

• Frequency of operation greater than 25 kHz<br />

• Inaudible in 27 dBA ambient environment<br />

• Inrush current limiting circuitry built-in (maximum of<br />

7 amps for 120V, 3 amps for 277V and 347V)<br />

• Internal fusing<br />

• Minimum lamp starting temperature 10°C (50°F)<br />

• Maximum ballast case temperature 75°C (167°F)<br />

0-10V control<br />

For the full offering of TVE <strong>dimming</strong> ballast controls by<br />

<strong>Lutron</strong>, please see page 45.<br />

Hot<br />

120/277/347VAC<br />

60Hz Feed<br />

Control*<br />

Hot<br />

Neutral<br />

Control (+)<br />

Control (–)<br />

Neutral<br />

* Based on control being used, wiring method may differ.<br />

Dimming Ballast<br />

<strong>Lutron</strong> | 25


<strong>Lutron</strong>® | Hi-lume®, Compact SE , Eco-10®<br />

120 volt 3-wire <strong>dimming</strong> ballasts<br />

For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

1% Dimming<br />

Hi-lume<br />

5% Dimming<br />

10% Dimming<br />

Eco-10<br />

Ballast<br />

Current 2<br />

– Amps<br />

T5 Linear<br />

14W<br />

(22”)<br />

1<br />

2<br />

C 3 —<br />

C 3 —<br />

E 3 T514 C 120 1<br />

E 3 T514 C 120 2<br />

.17<br />

.32<br />

5/8” Dia 21W<br />

(34”)<br />

1<br />

2<br />

C 3 —<br />

C 3 —<br />

E 3 T521 C 120 1<br />

E 3 T521 C 120 2<br />

.25<br />

.43<br />

28W<br />

(45”)<br />

1<br />

2<br />

C 3 —<br />

C 3 —<br />

ECO-T528-120-1<br />

ECO-T528-120-2<br />

.30<br />

.55<br />

T5-HO<br />

Linear<br />

24W<br />

(22”)<br />

1<br />

2<br />

C 3<br />

C 3<br />

FDB-T524-120-1<br />

FDB-T524-120-2<br />

ECO-T524-120-1<br />

ECO-T524-120-2<br />

.26<br />

.45<br />

5/8” Dia<br />

39W<br />

(34”)<br />

1<br />

2<br />

C 3<br />

C 3<br />

FDB-T539-120-1<br />

FDB-T539-120-2<br />

ECO-T5H39-120-1<br />

ECO-T5H39-120-2<br />

.38<br />

.76<br />

54W<br />

(45”)<br />

1<br />

2<br />

C 3<br />

C 3<br />

FDB-T554-120-1<br />

FDB-T554-120-2<br />

ECO-T554-120-1<br />

ECO-T554-120-2<br />

.58<br />

1.1<br />

T8 Linear<br />

and U-Bent<br />

17W<br />

(24”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

FDB-2427-120-1<br />

FDB-2427-120-2<br />

FDB-2427-120-3<br />

ECO-T817-120-1<br />

ECO-T817-120-2<br />

ECO-T817-120-3<br />

.19<br />

.31<br />

.43<br />

1” Dia 25W<br />

(36”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

FDB-3627-120-1<br />

FDB-3627-120-2<br />

FDB-3627-120-3<br />

ECO-T825-120-1<br />

ECO-T825-120-2<br />

—<br />

.24<br />

.43<br />

.62<br />

32 W<br />

(48”)<br />

1<br />

1<br />

1<br />

2<br />

2<br />

2<br />

3<br />

F<br />

D<br />

D<br />

F<br />

D<br />

D<br />

F<br />

FDB-4827-120-1<br />

—<br />

—<br />

FDB-4827-120-2<br />

—<br />

—<br />

FDB-4827-120-3<br />

—<br />

ECO-T832-120-1-L<br />

ECO-T832-120-1-T<br />

—<br />

ECO-T832-120-2-L<br />

ECO-T832-120-2-T<br />

ECO-T832-120-3<br />

.30<br />

.34<br />

.34<br />

.57<br />

.53<br />

.53<br />

.82<br />

40W<br />

(60”)<br />

1<br />

2<br />

F<br />

F<br />

FDB-6027-120-1<br />

FDB-6027-120-2<br />

—<br />

—<br />

.36<br />

.64<br />

Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />

See page 30 for model numbers.<br />

1 For case type information, see pages 36 and 37.<br />

2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.<br />

3 Standard with terminals. Leaded options available. Please consult factory.<br />

26 | <strong>Lutron</strong>


For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

1% Dimming<br />

Hi-lume<br />

5% Dimming<br />

Compact SE<br />

10% Dimming<br />

Eco-10<br />

Ballast<br />

Current 2<br />

– Amps<br />

T4 4-Pin<br />

Quad-Tube<br />

18W 1<br />

2<br />

A 3 —<br />

B 3 —<br />

FDB-T418-120-1-S<br />

FDB-T418-120-2-S<br />

—<br />

—<br />

.20<br />

.42<br />

1/2” Dia<br />

26W 1<br />

2<br />

A 3 —<br />

B 3 —<br />

FDB-T426-120-1-S<br />

FDB-T426-120-2-S<br />

—<br />

—<br />

.26<br />

.50<br />

T4 4-Pin<br />

Triple-Tube<br />

18W 1<br />

2<br />

A 3 —<br />

B 3 —<br />

FDB-T418-120-1-S<br />

FDB-T418-120-2-S<br />

—<br />

—<br />

.20<br />

.42<br />

1/2” Dia<br />

26W 1<br />

2<br />

A 3<br />

B 3<br />

HL3-T426-120-1-S<br />

—<br />

FDB-T426-120-1-S<br />

FDB-T426-120-2-S<br />

—<br />

—<br />

.26<br />

.50<br />

32W 1<br />

2<br />

A 3<br />

B 3<br />

HL3-T432-120-1-S<br />

—<br />

FDB-T432-120-1-S<br />

FDB-T432-120-2-S<br />

—<br />

—<br />

.31<br />

.59<br />

42W 1<br />

2<br />

B 3 —<br />

B 3 —<br />

FDB-T442-120-1-S<br />

FDB-T442-120-2-S<br />

—<br />

—<br />

.39<br />

.67<br />

T5<br />

Twin-Tube<br />

36/39W<br />

(16”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

—<br />

—<br />

—<br />

FDB-1643-120-1<br />

FDB-1643-120-2<br />

FDB-1643-120-3<br />

ECO-T539-120-1<br />

ECO-T539-120-2<br />

ECO-T539-120-3<br />

.33<br />

.58<br />

.85<br />

5/8” Dia 40W<br />

(22”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

—<br />

—<br />

—<br />

FDB-2227-120-1<br />

FDB-2227-120-2<br />

FDB-2227-120-3<br />

ECO-T540-120-1<br />

ECO-T540-120-2<br />

ECO-T540-120-3<br />

.33<br />

.61<br />

.88<br />

50 W<br />

(22”)<br />

1<br />

2<br />

F<br />

F<br />

—<br />

—<br />

FDB-2243-120-1<br />

FDB-2243-120-2<br />

ECO-T550-120-1<br />

ECO-T550-120-2<br />

.38<br />

.69<br />

Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />

See page 30 for model numbers.<br />

1 For case type information, see pages 36 and 37.<br />

2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.<br />

3 Mounting studs standard. Delete suffi x -S if mounting studs not desired.<br />

<strong>Lutron</strong> | 27


<strong>Lutron</strong>® | Hi-lume®, Compact SE , Eco-10®<br />

277 volt 3-wire <strong>dimming</strong> ballasts<br />

For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

1% Dimming<br />

Hi-lume<br />

5% Dimming<br />

10% Dimming<br />

Eco-10<br />

Ballast<br />

Current 2<br />

– Amps<br />

T5 Linear<br />

14W<br />

(22”)<br />

1<br />

2<br />

C 3 —<br />

C 3 —<br />

E 3 T514 C 277 1<br />

E 3 T514 C 277 2<br />

.08<br />

.14<br />

5/8” Dia 21W<br />

(34”)<br />

1<br />

2<br />

C 3 —<br />

C 3 —<br />

E 3 T521 C 277 1<br />

E 3 T521 C 277 2<br />

.11<br />

.19<br />

28W<br />

(45”)<br />

1<br />

2<br />

C 3 —<br />

C 3 —<br />

ECO-T528-277-1<br />

ECO-T528-277-2<br />

.14<br />

.25<br />

T5-HO<br />

Linear<br />

24W<br />

(22”)<br />

1<br />

2<br />

C 3<br />

C 3<br />

FDB-T524-277-1<br />

FDB-T524-277-2<br />

ECO-T524-277-1<br />

ECO-T524-277-2<br />

.13<br />

.20<br />

5/8” Dia<br />

39W<br />

(34”)<br />

1<br />

2<br />

C 3<br />

C 3<br />

FDB-T539-277-1<br />

FDB-T539-277-2<br />

ECO-T5H39-277-1<br />

ECO-T5H39-277-2<br />

.17<br />

.31<br />

54W<br />

(45”)<br />

1<br />

2<br />

C 3<br />

C 3<br />

FDB-T554-277-1<br />

FDB-T554-277-2<br />

ECO-T554-277-1<br />

ECO-T554-277-2<br />

.25<br />

.45<br />

T8 Linear<br />

and U-Bent<br />

17W<br />

(24”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

FDB-2427-277-1<br />

FDB-2427-277-2<br />

FDB-2427-277-3<br />

ECO-T817-277-1<br />

ECO-T817-277-2<br />

ECO-T817-277-3<br />

.08<br />

.15<br />

.20<br />

1” Dia 25W<br />

(36”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

FDB-3627-277-1<br />

FDB-3627-277-2<br />

FDB-3627-277-3<br />

ECO-T825-277-1<br />

ECO-T825-277-2<br />

—<br />

.12<br />

.19<br />

.28<br />

32 W<br />

(48”)<br />

1<br />

1<br />

1<br />

2<br />

2<br />

2<br />

3<br />

F<br />

D<br />

D<br />

F<br />

D<br />

D<br />

F<br />

FDB-4827-277-1<br />

—<br />

—<br />

FDB-4827-277-2<br />

—<br />

—<br />

FDB-4827-277-3<br />

ECO-T832-277-1<br />

ECO-T832-277-1-L<br />

ECO-T832-277-1-T<br />

ECO-T832-277-2<br />

ECO-T832-277-2-L<br />

ECO-T832-277-2-T<br />

ECO-T832-277-3<br />

.14/.15 4<br />

.14<br />

.14<br />

.25/.22 4<br />

.23<br />

.23<br />

.35<br />

40W<br />

(60”)<br />

1<br />

2<br />

F<br />

F<br />

FDB-6027-120-1<br />

FDB-6027-277-2<br />

—<br />

—<br />

.16<br />

.30<br />

Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />

See page 30 for model numbers.<br />

1 For case type information, see pages 36 and 37.<br />

2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 277.<br />

3 Standard with terminals. Leaded options available. Please consult factory.<br />

4 Eco-10 ballast current.<br />

28 | <strong>Lutron</strong>


For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

1% Dimming<br />

Hi-lume<br />

5% Dimming<br />

Compact SE<br />

10% Dimming<br />

Eco-10<br />

Ballast<br />

Current 2<br />

– Amps<br />

T4 4-Pin<br />

Quad-Tube<br />

18W 1<br />

2<br />

A 3 —<br />

B 3 —<br />

FDB-T418-277-1-S<br />

FDB-T418-277-2-S<br />

—<br />

—<br />

.08<br />

.17<br />

1/2” Dia<br />

26W 1<br />

2<br />

A 3 —<br />

B 3 —<br />

FDB-T426-277-1-S<br />

FDB-T426-277-2-S<br />

—<br />

—<br />

.12<br />

.21<br />

T4 4-Pin<br />

Triple-Tube<br />

18W 1<br />

2<br />

A 3 —<br />

B 3 —<br />

FDB-T418-277-1-S<br />

FDB-T418-277-2-S<br />

—<br />

—<br />

.08<br />

.17<br />

1/2” Dia<br />

26W 1<br />

2<br />

A 3<br />

B 3<br />

HL3-T426-277-1-S<br />

—<br />

FDB-T426-277-1-S<br />

FDB-T426-277-2-S<br />

—<br />

—<br />

.12<br />

.21<br />

32W 1<br />

2<br />

A 3<br />

B 3<br />

HL3-T432-277-1-S<br />

—<br />

FDB-T432-277-1-S<br />

FDB-T432-277-2-S<br />

—<br />

—<br />

.13<br />

.24<br />

42W 1<br />

2<br />

B 3 —<br />

B 3 —<br />

FDB-T442-277-1-S<br />

FDB-T442-277-2-S<br />

—<br />

—<br />

.16<br />

.29<br />

T5<br />

Twin-Tube<br />

36/39W<br />

(16”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

—<br />

—<br />

—<br />

FDB-1643-277-1<br />

FDB-1643-277-2<br />

FDB-1643-277-3<br />

ECO-T539-277-1<br />

ECO-T539-277-2<br />

ECO-T539-277-3<br />

.14<br />

.25<br />

.35<br />

5/8” Dia 40W<br />

(22”)<br />

1<br />

2<br />

3<br />

F<br />

F<br />

F<br />

—<br />

—<br />

—<br />

FDB-2227-277-1<br />

FDB-2227-277-2<br />

FDB-2227-277-3<br />

ECO-T540-277-1<br />

ECO-T540-277-2<br />

ECO-T540-277-3<br />

.14<br />

.25<br />

.38<br />

50 W<br />

(22”)<br />

1<br />

2<br />

F<br />

F<br />

—<br />

—<br />

FDB-2243-277-1<br />

FDB-2243-277-2<br />

ECO-T550-277-1<br />

ECO-T550-277-2<br />

.17<br />

.32<br />

Hi-lume® 3D digital addressable <strong>dimming</strong> ballasts can also work with 3-wire controls.<br />

See page 30 for model numbers.<br />

For case type information, see pages 36 and 37.<br />

2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 277.<br />

3 Standard with terminals. Leaded options available. Please consult factory.<br />

<strong>Lutron</strong> | 29


<strong>Lutron</strong>® |<br />

Hi-lume® 3D Universal Voltage<br />

digital multi-input <strong>dimming</strong> ballasts<br />

NEW!<br />

For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

T8 Linear<br />

and U-Bent<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

1% Dimming<br />

Hi-lume 3D<br />

Input<br />

Voltage<br />

Ballast<br />

Current<br />

– Amps<br />

Ballast<br />

Factor<br />

Input<br />

Power<br />

Ballast<br />

Effi cacy<br />

Factor<br />

System<br />

Lumens 2<br />

1 C<br />

120 0.298 1.00 36 2.80 3,000 84<br />

H3D T832 C UNV 1 10<br />

1 C 277 0.127 1.00 35 2.84 3,000 85<br />

System<br />

Effi cacy 2<br />

(Im/W)<br />

1” Dia<br />

32W<br />

(48”)<br />

1 C<br />

120 0.338 1.17 41 2.88 3,510 87<br />

H3D T832 C UNV 1 17<br />

1 C 277 0.143 1.17 40 2.95 3,510 89<br />

2 C<br />

120 0.573 1.00 69 1.45 6,000 87<br />

H3D T832 C UNV 2 10<br />

2 C 277 0.243 1.00 67 1.49 6,000 89<br />

2 C<br />

120 0.662 1.17 79 1.47 7,020 88<br />

H3D T832 C UNV 2 17<br />

2 C 277 0.279 1.17 77 1.51 7,020 91<br />

1 For case type information, see pages 36 and 37.<br />

2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specifi c data.<br />

30 | <strong>Lutron</strong>


Hi-lume® 3D | features<br />

Enhanced <strong>dimming</strong>, high ballast factor,<br />

and improved effi ciency<br />

Hi-lume 3D delivers superior performance<br />

compared to other ballasts. It provides enhanced<br />

<strong>dimming</strong>, giving you the broadest range of light<br />

levels so you’ll always use the right light for the<br />

task at hand. It offers a high ballast factor for more<br />

light per fi xture so you can use fewer fi xtures in the<br />

space, saving money and time on lighting installation<br />

and maintenance costs. Furthermore, Hi-lume 3D<br />

is energy effi cient as evidenced by its high effi cacy/<br />

lumens per watt rating. Hi-lume 3D gives you the<br />

most light for a watt of power compared to nearly<br />

all other ballasts. Hi-lume 3D is the superior choice<br />

because you get better performance, effi ciently.<br />

Performance of T8 32W 2 Lamp 277V Ballasts<br />

Non-dim Ballast<br />

(90 lm/W)<br />

EcoSystemTM<br />

(89 lm/W)<br />

Hi-lume<br />

(82 lm/W)<br />

Hi-lume 3D 1.0<br />

(89 lm/W)<br />

Hi-lume 3D 1.17<br />

(91 lm/W)<br />

1.4<br />

8400<br />

1.2<br />

1.17 BF/<br />

7020 lm<br />

7200<br />

Ballast Factor (BF)<br />

1.0<br />

0.8<br />

0.6<br />

0.4<br />

0.88 BF/<br />

5280 lm<br />

0.85 BF/<br />

5100 lm<br />

10 to 1 Dimming Ratio<br />

0.95 BF/<br />

5700 lm<br />

100 to 1 Dimming Ratio<br />

1.00 BF/<br />

6000 lm<br />

118 to 1 Dimming Ratio<br />

138 to 1 Dimming Ratio<br />

6000<br />

4800<br />

3600<br />

2400<br />

lumens (lm)<br />

0.2<br />

1200<br />

0<br />

0.085 BF/510 lm<br />

0.0095 BF/57 lm<br />

0.0085 BF/51 lm<br />

0.0085 BF/51 lm<br />

0<br />

<strong>Lutron</strong> | 31


<strong>Lutron</strong>® |<br />

Tu-Wire ® 120 volt<br />

2-wire <strong>dimming</strong> ballasts<br />

For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

1% Dimming<br />

5% Dimming<br />

Tu-Wire<br />

10% Dimming<br />

Ballast<br />

Current 2<br />

– Amps<br />

T8 Linear<br />

and U-Bent<br />

32W<br />

(48”)<br />

1<br />

2<br />

C 3<br />

C 3<br />

2W-T832-120-1<br />

2W-T832-120-2<br />

.37<br />

.70<br />

1” Dia<br />

Contact <strong>Lutron</strong> for<br />

other lamp lengths.<br />

T4 4-Pin<br />

Quad-Tube<br />

18W 2 B 4 2W-T418-120-2-S .41<br />

1/2” Dia<br />

26W 1<br />

2<br />

A 4<br />

2W-T426-120-1-S 5<br />

B 4 2W-T426-120-2-S<br />

.27<br />

.53<br />

T4 4-Pin<br />

Triple-Tube<br />

18W 2 B 4 2W-T418-120-2-S .41<br />

1/2” Dia<br />

26W 1<br />

2<br />

A 4<br />

2W-T426-120-1-S 5<br />

B 4 2W-T426-120-2-S<br />

.27<br />

.53<br />

32 W 1<br />

2<br />

A 4<br />

2W-T432-120-1-S 5<br />

B 4 2W-T432-120-2-S<br />

.33<br />

.58<br />

1 For case type information, see pages 36 and 37.<br />

2 To calculate ballast input power, use the following formula: Watts = Ballast Current x 120.<br />

3 Standard with terminals. Leaded options available. Please consult factory.<br />

4 Mounting studs standard. Delete suffi x -S if mounting studs not desired.<br />

5 One-lamp T4 models meet FCC Part 18 consumer requirements for residential use (FCC ID: JPZB001).<br />

32 | <strong>Lutron</strong>


<strong>Lutron</strong>® | TVE 120/277/347 volt<br />

0-10V <strong>dimming</strong> ballasts<br />

For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1 1% Dimming 5% Dimming<br />

10% Dimming<br />

TVE<br />

Ballast<br />

Current 2<br />

– Amps<br />

T8 Linear<br />

and U-Bent<br />

1” Dia<br />

17W<br />

(24”)<br />

25W<br />

(36”)<br />

1 F TVE-T817-120-1 .14<br />

1 F TVE-T825-120-1 .24<br />

32W<br />

(48”)<br />

1<br />

1<br />

1<br />

2<br />

2<br />

2<br />

3<br />

3<br />

F<br />

F<br />

F<br />

F<br />

F<br />

F<br />

F<br />

F<br />

TVE-T832-120-1<br />

TVE-T832-277-1<br />

TVE-T832-347-1<br />

TVE-T832-120-2<br />

TVE-T832-277-2<br />

TVE-T832-347-2<br />

TVE-T832-120-3<br />

TVE-T832-277-3<br />

.34<br />

.15<br />

.11<br />

.55<br />

.25<br />

.19<br />

.80<br />

.35<br />

T5<br />

Twin-Tube<br />

40W<br />

(22”)<br />

2<br />

2<br />

F<br />

F<br />

TVE-T540-120-2<br />

TVE-T540-277-2<br />

.61<br />

.25<br />

5/8” Dia<br />

1 For case type information, see pages 36 and 37.<br />

2 To calculate ballast input power, use the following formula: Watts = Ballast Current x Ballast Voltage<br />

(included in model number).<br />

<strong>Lutron</strong> | 33


<strong>Lutron</strong>® | EcoSystemTM 120 volt multi-input<br />

digital addressable <strong>dimming</strong> ballasts<br />

NEW!<br />

For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

10% Dimming<br />

EcoSystem<br />

Ballast<br />

Current<br />

– Amps<br />

Ballast<br />

Factor<br />

Input<br />

Power<br />

Ballast<br />

Effi cacy<br />

Factor<br />

System<br />

Lumens 2<br />

System<br />

Effi cacy 2<br />

(Im/W)<br />

T8 Linear<br />

and U-Bent<br />

17W<br />

(24”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T817 J 120 1<br />

EC5 T817 J 120 2<br />

.158<br />

.292<br />

.85<br />

.85<br />

19<br />

35<br />

4.47<br />

2.43<br />

1,105<br />

2,210<br />

58<br />

63<br />

1” Dia<br />

25W<br />

(36”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T825 J 120 1<br />

EC5 T825 J 120 2<br />

.208<br />

.383<br />

.85<br />

.85<br />

25<br />

46<br />

3.40<br />

1.85<br />

1,615<br />

3,230<br />

65<br />

70<br />

32W<br />

(48”)<br />

1<br />

2<br />

2<br />

3<br />

J<br />

J<br />

G<br />

G<br />

EC5 T832 J 120 1<br />

EC5 T832 J 120 2<br />

EC5 T832 G120 2L<br />

EC5 T832 G120 3L<br />

.250<br />

.475<br />

.490<br />

.790<br />

.85<br />

.85<br />

.85<br />

.85<br />

30<br />

57<br />

58<br />

85<br />

2.83<br />

1.49<br />

1.47<br />

1.00<br />

2,550<br />

5,100<br />

5,100<br />

7,650<br />

85<br />

89<br />

88<br />

90<br />

T5 Linear<br />

14W<br />

(22”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T514 J 120 1<br />

EC5 T514 J 120 2<br />

.158<br />

.283<br />

1.00<br />

1.00<br />

19<br />

34<br />

5.26<br />

2.94<br />

1,350<br />

2,700<br />

71<br />

79<br />

5/8” Dia 21W<br />

(34”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T521 J 120 1<br />

EC5 T521 J 120 2<br />

.217<br />

.404<br />

1.00<br />

1.00<br />

26<br />

48.5<br />

3.85<br />

2.06<br />

2,100<br />

4,200<br />

81<br />

87<br />

28W<br />

(45”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T528 J 120 1<br />

EC5 T528 J 120 2<br />

.275<br />

.525<br />

1.00<br />

1.00<br />

33<br />

63<br />

3.03<br />

1.59<br />

2,900<br />

5,800<br />

88<br />

92<br />

T5-HO<br />

Linear<br />

High<br />

Output<br />

24W<br />

(22”)<br />

39W<br />

(34”)<br />

1<br />

2<br />

1<br />

2<br />

J<br />

J<br />

J<br />

J<br />

EC5 T524 J 120 1<br />

EC5 T524 J 120 2<br />

EC5 T539 J 120 1<br />

EC5 T539 J 120 2<br />

.226<br />

.434<br />

.359<br />

.695<br />

1.00<br />

1.00<br />

1.00<br />

1.00<br />

27<br />

52<br />

43<br />

83<br />

3.70<br />

1.92<br />

2.33<br />

1.20<br />

2,000<br />

4,000<br />

3,500<br />

7,000<br />

74<br />

77<br />

81<br />

84<br />

5/8” Dia 54 W<br />

(45”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T554 J 120 1<br />

EC5 T554 J 120 2<br />

.500<br />

1.00<br />

1.00<br />

1.00<br />

60<br />

120<br />

1.67<br />

0.83<br />

5,000<br />

10,000<br />

83<br />

83<br />

Use EcoSystem ballast module (C5-BMF-2A) to integrate any <strong>Lutron</strong> Eco-10TM or Hi-lume®<br />

phase-control ballast into the EcoSystem bus.<br />

Sensors<br />

E1 3<br />

E2 3<br />

Hot<br />

Neutral<br />

BMF<br />

Switched Hot,<br />

Dimmed Hot<br />

and Neutral<br />

Dimming Ballast<br />

1 For case type information, see pages 36 and 37.<br />

2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specifi c data.<br />

3 To other ballasts and bus supply.<br />

34 | <strong>Lutron</strong>


<strong>Lutron</strong>® | EcoSystemTM 277 volt multi-input<br />

digital addressable <strong>dimming</strong> ballasts<br />

For the latest<br />

model numbers:<br />

www.lutron.com/ballasts<br />

Lamp<br />

Type<br />

Lamp<br />

Watts<br />

(Length)<br />

Lamps<br />

per<br />

Ballast<br />

Case<br />

Type 1<br />

10% Dimming<br />

EcoSystem<br />

Ballast<br />

Current<br />

– Amps<br />

Ballast<br />

Factor<br />

Input<br />

Power<br />

Ballast<br />

Effi cacy<br />

Factor<br />

System<br />

Lumens 2<br />

System<br />

Effi cacy 2<br />

(Im/W)<br />

T8 Linear<br />

and U-Bent<br />

17W<br />

(24”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T817 J 277 1<br />

EC5 T817 J 277 2<br />

.075<br />

.126<br />

.85<br />

.85<br />

19<br />

35<br />

4.47<br />

2.43<br />

1,105<br />

2,210<br />

58<br />

63<br />

1” Dia<br />

25W<br />

(36”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T825 J 277 1<br />

EC5 T825 J 277 2<br />

.095<br />

.166<br />

.85<br />

.85<br />

25<br />

46<br />

3.40<br />

1.85<br />

1,615<br />

3,230<br />

65<br />

70<br />

32W<br />

(48”)<br />

1<br />

2<br />

2<br />

3<br />

J<br />

J<br />

G<br />

G<br />

EC5 T832 J 277 1<br />

EC5 T832 J 277 2<br />

EC5 T832 G 277 2L<br />

EC5 T832 G 277 3L<br />

.108<br />

.206<br />

.216<br />

.320<br />

.85<br />

.85<br />

.85<br />

.85<br />

30<br />

57<br />

57<br />

86<br />

2.83<br />

1.49<br />

1.49<br />

0.99<br />

2,550<br />

5,100<br />

5,100<br />

7,632<br />

85<br />

89<br />

89<br />

89<br />

T5 Linear<br />

14W<br />

(22”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T514 J 277 1<br />

EC5 T514 J 277 2<br />

.078<br />

.123<br />

1.00<br />

1.00<br />

19<br />

34<br />

5.26<br />

2.94<br />

1,350<br />

2,700<br />

71<br />

79<br />

5/8” Dia 21W<br />

(34”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T521 J 277 1<br />

EC5 T521 J 277 2<br />

.094<br />

.175<br />

1.00<br />

1.00<br />

26<br />

48.5<br />

3.85<br />

2.06<br />

2,100<br />

4,200<br />

81<br />

87<br />

28W<br />

(45”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T528 J 277 1<br />

EC5 T528 J 277 2<br />

.119<br />

.227<br />

1.00<br />

1.00<br />

33<br />

63<br />

3.03<br />

1.59<br />

2,900<br />

5,800<br />

88<br />

92<br />

T5-HO<br />

Linear<br />

24W<br />

(22”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T524 J 277 1<br />

EC5 T524 J 277 2<br />

.100<br />

.191<br />

1.00<br />

1.00<br />

27<br />

52<br />

3.70<br />

1.92<br />

2,000<br />

4,000<br />

74<br />

77<br />

High<br />

Output<br />

39W<br />

(34”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T539 J 277 1<br />

EC5 T539 J 277 2<br />

.158<br />

.306<br />

1.00<br />

1.00<br />

43<br />

83<br />

2.33<br />

1.20<br />

3,500<br />

7,000<br />

81<br />

84<br />

5/8” Dia 54 W<br />

(45”)<br />

1<br />

2<br />

J<br />

J<br />

EC5 T554 J 277 1<br />

EC5 T554 J 277 2<br />

.217<br />

.433<br />

1.00<br />

1.00<br />

60<br />

120<br />

1.67<br />

0.83<br />

5,000<br />

10,000<br />

83<br />

83<br />

1 For case type information, see pages 36 and 37.<br />

2 Actual number may vary with lamp model. Please consult lamp manufacturer for lamp-specifi c data.<br />

<strong>Lutron</strong> | 35


<strong>Lutron</strong>® | ballast case dimensions<br />

A<br />

B<br />

H<br />

G<br />

A<br />

F<br />

I<br />

E<br />

8-32 Threaded Stud<br />

0.29" (.736mm)<br />

D<br />

C<br />

A<br />

B<br />

C<br />

D<br />

E<br />

F<br />

G<br />

H<br />

I<br />

4.20” (107mm)<br />

1.00” (25mm)<br />

3.00” (76mm)<br />

4.90” (124mm)<br />

4.60” (117mm) C-C<br />

(mounting centers)<br />

2.00” (51mm)<br />

1.08” (27mm)<br />

1.60” (41mm)<br />

1.39” (35mm)<br />

B<br />

B<br />

H<br />

G<br />

A<br />

F<br />

I<br />

E<br />

8-32 Threaded Stud<br />

0.29" (.736mm)<br />

D<br />

C<br />

A<br />

B<br />

C<br />

D<br />

E<br />

F<br />

G<br />

H<br />

I<br />

6.00” (152mm)<br />

1.00” (25mm)<br />

3.00” (76mm)<br />

6.75” (171mm)<br />

6.50” (165mm) C-C<br />

(mounting centers)<br />

2.00” (51mm)<br />

1.16” (29mm)<br />

1.60” (41mm)<br />

1.39” (35mm)<br />

C or J<br />

C<br />

B<br />

F<br />

Note: Dotted area for sensor attachment applies<br />

for EcoSystemTM J can only.<br />

A<br />

G<br />

D<br />

E<br />

A<br />

B<br />

C<br />

D<br />

E<br />

F<br />

G<br />

16.12” (409mm)<br />

1.00” (25mm)<br />

1.18” (30mm)<br />

18.00” (457mm)<br />

17.70” (450mm)<br />

C-C (mounting<br />

centers)<br />

6.82” (173mm)<br />

(J only)<br />

0.394”(10mm)<br />

(J only)<br />

36 | <strong>Lutron</strong>


D<br />

C<br />

B<br />

A<br />

D<br />

E<br />

A 7.13” (181mm)<br />

B 1.00” (25mm)<br />

C 1.58” (40mm)<br />

D 9.50” (241mm)<br />

E 8.91” (226mm)<br />

Slot mounting centers<br />

If using 4-hole mount,<br />

mounting centers are 9.00”<br />

(229mm) X 1.06” (27mm).<br />

Optional lamp wires<br />

are 36” (0.90m)<br />

Optional power<br />

and control wires<br />

are 18” (0.45m)<br />

F<br />

C<br />

B<br />

A<br />

E<br />

D<br />

A 8.30” (211mm)<br />

B 1.50” (38mm)<br />

C 2.38” (60.5mm)<br />

D 9.50” (241mm)<br />

E 8.91” (226mm)<br />

Slot mounting centers<br />

If using 4-hole mount,<br />

mounting centers are 9.21”<br />

(234mm) X 1.70” (43mm).<br />

Lamp wires<br />

are 36” (0.90m)<br />

Power and control<br />

wires are 18” (0.45m)<br />

G<br />

C<br />

B<br />

Lamp wires<br />

are 36” (0.90m)<br />

A<br />

D<br />

E<br />

Power and control<br />

wires are 18” (0.45m)<br />

A 7.13” (181mm)<br />

B 1.00” (25mm)<br />

C 2.38” (60.5mm)<br />

D 9.50” (241mm)<br />

E 8.91” (226mm)<br />

Slot mounting centers<br />

If using 4-hole mount,<br />

mounting centers are 9.00”<br />

(229mm) X 1.06” (27mm).<br />

Proper ballast mounting is critical in providing effective grounding and for<br />

managing ballast heat. Please refer to the <strong>Lutron</strong> Fluorescent Dimming<br />

Systems Technical Guide (P/N 366-606) for detailed information.<br />

<strong>Lutron</strong> | 37


<strong>Lutron</strong>® | fl uorescent <strong>dimming</strong> controls<br />

Wallbox dimmers<br />

NovaTa®<br />

Classic, thin-profi le<br />

linear-slide dimmer<br />

Nova®<br />

Contractor’s choice in<br />

linear-slide dimmers<br />

Wallbox dimmers<br />

Vierti NEW!<br />

Available 4 th Quarter 2007<br />

Combines style and simplicity in<br />

a remarkably innovative control.<br />

•<br />

set the perfect light level with a<br />

single touch or slide of the fi nger<br />

• customize with different<br />

LED colors<br />

To learn more about Vierti visit<br />

www.lutron.com/vierti<br />

Lyneo® Lx NEW!<br />

The simple, clean lines of the<br />

dimmer and matching switch<br />

ensure a coordinated look for<br />

your project.<br />

To learn more about Lyneo Lx<br />

visit www.lutron.com/lyneo<br />

Vareo®<br />

Elegant thin-profi le<br />

TapSwitch dimmer<br />

Diva®<br />

Designer dimmer<br />

that matches your<br />

paddle switches<br />

Wireless remote controls<br />

Skylark®<br />

Original designer-style<br />

slide dimmer<br />

Ariadni®<br />

Dimmer that matches<br />

your toggle switches<br />

RadioTouch®<br />

•<br />

Wireless control<br />

of multiple lighting zones<br />

•<br />

Occupancy sensing,<br />

motorized shade and<br />

A/V equipment control optional<br />

•<br />

Ideal for retrofi t applications<br />

To learn more about the product visit<br />

www.lutron.com/hlc<br />

To learn more about the product visit<br />

www. lutron.com/radiotouch<br />

38 | <strong>Lutron</strong>


Preset scene control<br />

Preset scene control<br />

GRAFIK Eye® QS<br />

NEW!<br />

•<br />

Light and shade control in one unit<br />

•<br />

Engravings on large, backlit buttons<br />

•<br />

Information display with energy saving<br />

reading included<br />

•<br />

Built-in astronomical time clock<br />

•<br />

Direct connections to sensors and<br />

other devices<br />

To learn more about the product visit<br />

www. lutron.com/grafi keyeqs<br />

Spacer System <br />

•<br />

Up to fi ve preset scenes<br />

•<br />

Easy upgrade for enclosed<br />

offi ces and conference rooms<br />

•<br />

Dims multiple sources<br />

To learn more about the product visit<br />

www. lutron.com/spacersystem.<br />

NEW!<br />

GRAFIK Eye®<br />

•<br />

Create and recall 4-16 room<br />

lighting scenes<br />

•<br />

Optional accessories for wireless<br />

remote control, remote scene<br />

selection, and more<br />

•<br />

Controls multiple sources<br />

To learn more about the product visit<br />

www. lutron.com/grafi keye<br />

Quantum Solution<br />

Whole-building light and energy management.<br />

Controls electric lights and shades from a central<br />

location; confi gures, monitors, analyzes, and reports on<br />

the light for an entire building or campus. Furthermore,<br />

the Quantum Green Glance demonstrates how much<br />

energy your building is saving.<br />

To learn more about the product visit<br />

www. lutron.com/quantum.<br />

<strong>Lutron</strong> | 39


<strong>Lutron</strong>® | EcoSystemTM components<br />

Ballasts<br />

Sensors/Receivers<br />

EcoSystem Daylight<br />

Sensor with IR Receiver<br />

EcoSystem T8 Digital Ballast<br />

EcoSystem T8, T5 and T5-HO Digital Ballast<br />

•<br />

Smooth and continuous <strong>dimming</strong> from<br />

100% to 10%<br />

•<br />

Provides power for one occupancy sensor,<br />

one daylight sensor, and one personal control<br />

input (infrared receiver or wallstation)<br />

•<br />

Communicates status and sensor inputs over<br />

the EcoSystem bus<br />

•<br />

Automatically dim the lights when the available<br />

daylight is high and brighten the light when the<br />

available daylight is low in order to maintain a<br />

specifi c light level in the space<br />

•<br />

Integrated IR receiver for<br />

EcoSystem programming<br />

•<br />

1 daylight sensor can control multiple<br />

fi xtures or groups of fi xtures differently<br />

Modules<br />

EcoSystem Ballast Module<br />

Fixture-mounted (BMF)<br />

•<br />

Allows integration of any <strong>Lutron</strong> Eco-10 <br />

or Hi-lume® phase-control ballast into<br />

the EcoSystem<br />

•<br />

Provides power for one occupancy sensor, one<br />

daylight sensor, and one personal control input<br />

(infrared receiver or wallstation)<br />

20VDC Occupancy Sensor<br />

•<br />

Use an ultrasonic sensor for small movement<br />

detection when fans or other automated<br />

<strong>systems</strong> are not present<br />

•<br />

Use an infrared sensor for occupant detection<br />

when “line of sight” is available from the sensor<br />

•<br />

Use a dual-tech sensor for a combination of<br />

both technologies<br />

EcoSystem IR Receiver<br />

•<br />

Can control individual or grouped<br />

EcoSystem ballasts or modules<br />

•<br />

Flashing LED response to indicate<br />

signal reception<br />

40 | <strong>Lutron</strong>


Controls<br />

Support components<br />

EcoSystem 1-Button Wallstation<br />

and IR Receiver<br />

•<br />

Allows user to manually control any of<br />

the fi xtures on the bus for simple on/off,<br />

raise/lower<br />

EcoSystem Programmer<br />

•<br />

Handles programming changes for all<br />

sensors, ballasts, and modules<br />

•<br />

Transmits to any IR receiver, daylight<br />

sensor, or EcoSystem wallstation<br />

•<br />

Simple user interface allows programming<br />

without training or <strong>guide</strong>book<br />

EcoSystem 4-Button Wallstation<br />

and IR Receiver<br />

•<br />

Allows occupants to save and recall different<br />

lighting scenes in multi-purpose rooms<br />

EcoSystem Bus Supply<br />

•<br />

Required for two or more ballasts (or<br />

modules) to work together<br />

•<br />

Powers the communication bus and is<br />

capable of supporting up to 64 ballasts<br />

or modules<br />

EcoSystem Remote Control<br />

and IR Receiver<br />

•<br />

For personal control of lighting<br />

See the <strong>Lutron</strong> EcoSystem Technical Guide<br />

(P/N 367-1028) for detailed information.<br />

<strong>Lutron</strong> | 41


<strong>Lutron</strong>® | select your fl uorescent <strong>dimming</strong> controls<br />

3-wire controls for Hi-lume®, Compact SE and Eco-10 ballasts<br />

Control Family<br />

Description<br />

Ballast<br />

Voltage<br />

Control<br />

Model Number<br />

Control<br />

Capacity<br />

NovaTa®<br />

Thin Profi le<br />

Slide-To-Off<br />

Dimmer<br />

single pole<br />

single pole<br />

single pole, 3-way, preset<br />

single pole, 3-way, preset<br />

120V<br />

277V<br />

120V<br />

277V<br />

NTF-10-<br />

NTF-10-277-<br />

NTF-103P-<br />

NTF-103P-277-<br />

16A<br />

8A<br />

8A<br />

8A<br />

Nova®<br />

Standard Profi le<br />

Slide-To-Off<br />

Dimmer<br />

single pole<br />

single pole<br />

single pole, 3-way, preset<br />

single pole, 3-way, preset<br />

120V<br />

277V<br />

120V<br />

277V<br />

NF-10-<br />

NF-10-277-<br />

NF-103P-<br />

NF-103P-277-<br />

16A<br />

8A<br />

8A<br />

8A<br />

Vareo®<br />

Tapswitch/<br />

Preset Slide<br />

Dimmer<br />

single pole, 3-way 120V VF-10- 8A 1<br />

Diva®<br />

Paddle Switch/<br />

Preset Slide<br />

Dimmer<br />

single pole, 3-way<br />

single pole, 3-way<br />

120V<br />

277V<br />

DVF-103P-<br />

DVF-103P-277-<br />

8A<br />

6A<br />

Skylark®<br />

Rocker Switch/<br />

Preset Slide<br />

Dimmer<br />

single pole<br />

single pole<br />

single pole, 3-way<br />

single pole, 3-way<br />

120V<br />

277V<br />

120V<br />

277V<br />

SF-10P-<br />

SF-12P-277-<br />

SF-103P-<br />

SF-12P-277-3-<br />

8A<br />

6A<br />

8A<br />

6A<br />

Ariadni®<br />

Toggle Switch/<br />

Preset Slide<br />

Dimmer<br />

single pole, 3-way<br />

single pole, 3-way<br />

120V<br />

277V<br />

AYF-103P-<br />

AYF-103P-277-<br />

8A<br />

6A<br />

NEW!<br />

Vierti <br />

Single-touch<br />

lighting conrol<br />

single pole/multi-location<br />

single pole/multi-location<br />

120V<br />

277V<br />

VTF-6AM-<br />

VTF-6AM-277-<br />

6A<br />

6A<br />

NEW!<br />

Lyneo Lx<br />

Pushbutton<br />

preset slide<br />

dimmer<br />

single pole, 3-way, preset<br />

single pole, 3-way, preset<br />

120V<br />

277V<br />

LXF-103PL-<br />

LXF-103PL-277-<br />

8A<br />

6A<br />

1 Not to exceed 20 <strong>Lutron</strong> 3-wire <strong>dimming</strong> ballasts.<br />

42 | <strong>Lutron</strong>


Control Family<br />

RadioTouch®<br />

Wireless<br />

Multi-Zone<br />

Control<br />

Description<br />

controller<br />

wallbox transmitter<br />

tabletop transmitter<br />

Ballast<br />

Voltage<br />

Control<br />

Model Number<br />

120/277V RTA-RX-F-<br />

RTA-WX- 1<br />

RTA-TX-<br />

Control<br />

Capacity<br />

16A<br />

NEW!<br />

Spacer System <br />

Wireless Preset<br />

Scene Control<br />

GRAFIK Eye® QS<br />

Light and Shade<br />

Control System<br />

single pole<br />

single pole<br />

multi-location<br />

multi-location<br />

remote control<br />

control unit<br />

remote control (optional)<br />

120V<br />

277V<br />

120V<br />

277V<br />

120V<br />

277V<br />

SPSF-6A-<br />

SPSF-6A-277-<br />

SPSF-6AM- 2<br />

SPSF-6AM-277- 2<br />

SPS-4IT-RP<br />

QSG-_ 3 P120<br />

GRX-IT<br />

6A 1<br />

6A 1<br />

6A 1<br />

6A 1<br />

16A per zone<br />

GRAFIK Eye®<br />

Multi-Scene<br />

Preset Control<br />

control unit<br />

remote control (optional)<br />

120/277V GRX-310_ 4<br />

GRX-IT-WH<br />

16A per zone<br />

GRAFIK<br />

5000/6000/7000 TM<br />

Lighting Control<br />

System<br />

centralized lighting<br />

control<br />

120/277V<br />

Contact your <strong>Lutron</strong><br />

representative for details<br />

1 Wallbox transmitter may be powered by 120 or 277V.<br />

2 Also requires SPS-AD- or SPS-AD-277- for multi-location <strong>dimming</strong> (10 maximum).<br />

3 Insert 3, 4, or 6 (number of zones); requires PHPM-3F-DV-WH.<br />

4 Insert 2, 3, 4, or 6 (number of zones); requires PHPM-3F-DV-WH.<br />

5 For sensors, central monitoring software, etc., contact <strong>Lutron</strong>.<br />

6 Contact <strong>Lutron</strong> if more ballasts or shades are needed.<br />

<strong>Lutron</strong> | 43


<strong>Lutron</strong>® | select your fl uorescent <strong>dimming</strong> controls<br />

2-wire controls for Tu-Wire® ballasts<br />

NEW!<br />

Control Family<br />

NovaTa®<br />

Thin Profi le<br />

Slide-To-Off<br />

Dimmer<br />

Nova®<br />

Standard Profi le<br />

Slide-To-Off<br />

Dimmer<br />

Diva®<br />

Paddle Switch/<br />

Preset Slide<br />

Dimmer<br />

Skylark®<br />

Rocker Switch/<br />

Preset Slide<br />

Dimmer<br />

RadioTouch®<br />

Wireless<br />

Multi-Zone<br />

Control<br />

Spacer System <br />

Wireless Preset<br />

Scene Control<br />

GRAFIK Eye® QS<br />

Light and Shade<br />

Control System<br />

GRAFIK Eye®<br />

Multi-Scene<br />

Preset Control<br />

GRAFIK<br />

5000/6000/7000 TM<br />

Lighting Control<br />

System<br />

Ballast Control<br />

Control<br />

Description<br />

Voltage Model Number Capacity<br />

single pole 120V NTFTU-5A- 5A 1<br />

single pole 120V NFTU-5A- 5A 1<br />

single pole, 3-way 120V DVFTU-5A3P- 5A 1<br />

single pole, 3-way 120V SFTU-5A3P- 5A 1<br />

controller<br />

wallbox transmitter<br />

tabletop transmitter<br />

single pole<br />

remote control<br />

control unit<br />

remote control (optional)<br />

control unit<br />

remote control (optional)<br />

centralized lighting<br />

control<br />

120V RTA-RX-F- 2<br />

120V<br />

120V<br />

RTA-WX- 3<br />

RTA-TX-<br />

SPSFTU-5A-<br />

SPS-4IT-RP<br />

QSG-_ 4 P120<br />

GRX-IT<br />

120V GRX-310_ 5<br />

120/277V<br />

GRX-IT<br />

16A<br />

5A 1<br />

Contact your <strong>Lutron</strong><br />

representative for details<br />

16A, 6.7A per zone<br />

16A, 6.7A per zone<br />

44 | <strong>Lutron</strong><br />

1 Minimum capacity: 2 ballasts.<br />

2 Requires FDI-FTU-16A-120 interface.<br />

3 Wallbox transmitter may be powered by 120 or 277V.<br />

4 Insert 3, 4, or 6 (number of zones).<br />

5 Insert 2, 3, 4, or 6 (number of zones).<br />

6 Contact <strong>Lutron</strong> if more ballasts or shades are needed.


0-10V controls for TVE® ballasts<br />

Control Family<br />

NovaTa®<br />

Thin Profi le<br />

Slide-To-Off<br />

Dimmer<br />

Nova®<br />

Standard Profi le<br />

Slide-To-Off<br />

Dimmer<br />

Description<br />

Ballast<br />

Voltage<br />

Control<br />

Model Number<br />

Control<br />

Capacity<br />

single pole 120/277/347V NTFTV- 1 Up to 60 ballasts<br />

or Relay Pack<br />

Capacity<br />

single pole 120/277/347V NFTV- 1 Up to 60 ballasts<br />

or Relay Pack<br />

Capacity<br />

RadioTouch®<br />

Wireless<br />

Multi-Zone<br />

Control<br />

controller<br />

controller<br />

wallbox transmitter<br />

tabletop transmitter<br />

347V<br />

120/277V<br />

RTA-RX-F-347<br />

RTA-RX-F-<br />

RTA-WX- 2<br />

RTA-TX-<br />

8A/40 ballasts<br />

16A<br />

NEW!<br />

GRAFIK Eye® QS<br />

Light and Shade<br />

Control System<br />

control unit<br />

remote control (optional)<br />

120V<br />

QSG-_ 3 P120<br />

GRX-IT<br />

16A/100 ballasts<br />

multi-input digital controls for EcoSystem ballasts<br />

NEW!<br />

Control Family Description Control Model Number<br />

EcoSystem Daylight Sensor sensor<br />

C-SR-M1-WH<br />

with IR Receiver<br />

EcoSystem IR Receiver<br />

for Personal Control<br />

IR receiver C-R-M1-WH<br />

EcoSystem<br />

Occupancy Sensor<br />

EcoSystem<br />

1-Button with Raise/Lower<br />

EcoSystem<br />

4-Button with Raise/Lower<br />

QuantumTM<br />

Whole-building light and energy<br />

management<br />

sensor<br />

wall control<br />

wall control<br />

lighting hub<br />

Q-manager PC<br />

LOS-_ _ _ (Please visit<br />

www.lutron.com/occsensors for full line)<br />

CC-1BRL-WH<br />

CC-4BRL-WH<br />

1 Requires relay pack to switch power to ballasts. Please consult factory.<br />

2 Wallbox transmitter may be powered by 120 or 277V.<br />

3 Insert 3,4, or 6 (number of zones); requires GRX-TVI interface.<br />

Contact your <strong>Lutron</strong><br />

representative for details<br />

www.lutron.com/quantum<br />

<strong>Lutron</strong> | 45


www.lutron.com<br />

<strong>Lutron</strong> Electronics Co., Inc.<br />

7200 Suter Road<br />

Coopersburg, PA 18036-1299<br />

World Headquarters 1.610.282.3800<br />

Barcelona | Beijing | Berlin | Hong Kong | London | Madrid | Mexico City |<br />

Milan | Paris | Sao Paulo | Shanghai | Singapore | Tokyo<br />

Technical Support Center 1.800.523.9466<br />

Customer Service 1.888.LUTRON1<br />

Cover photograph © Peter Aaron/Esto. Architect: Davis Brody Bond Architects.<br />

Lighting design: Fisher Marantz Stone.<br />

© 07/2007 <strong>Lutron</strong> Electronics Co., Inc. | Made and printed in the U.S.A. | P/N 366-002<br />

46 | <strong>Lutron</strong>