India’s No. 1<br />

<strong>IES</strong> <strong>Academy</strong><br />

Transformer<br />

Chapter-1<br />

If one of the transformers is disconnected, it results in open-delta connection. It can supply a<br />

balanced load.<br />

In the delta/delta connection if one of the transformers is disconnected, the resulting<br />

connection is known as open-delta. Supposing the b-phase transformer is removed, and the<br />

open-delta is excited from balanced 3-phase supply, then the voltage Vb 1<br />

b 2<br />

= Vbc does not<br />

change as it equals – (Vca + Vab); thus the voltage on the secondary side still remain balanced<br />

3-phase. If the maximum allowable secondary phase current is Iph, the transformer can handle<br />

VA of<br />

Sopen-delta = 3 VI<br />

ph<br />

Which for normal delta/delta connection is<br />

Sdelta = 3VIph<br />

Thus the open-delta connection has a VA rating of 1/<br />

delta/delta connection.<br />

3 = 0.58 of the rating of the normal<br />

The maximum allowable secondary phase current is Iph, the transformer can handle VAopen-delta<br />

= √3 VIph = S'<br />

For normal (Δ/Δ) Connection, VA delta = 3VIph = S<br />

S '<br />

S = √<br />

13<br />

= 0.58<br />

Star/Delta (Yd) Connection – (+30° and –30° connections<br />

are obtained)<br />

www.iesacademy.com E-mail: iesacademy@yahoo.com Page-27<br />

25, 1 st Floor, Jia Sarai, Near IIT. New Delhi-16 Ph: 011-26537570, 9810958290