28.01.2015 Views

Handbook of Energy Storage for Transmission or ... - W2agz.com

Handbook of Energy Storage for Transmission or ... - W2agz.com

Handbook of Energy Storage for Transmission or ... - W2agz.com

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

EPRI Proprietary Licensed Material<br />

Regenesys Electricity <strong>St<strong>or</strong>age</strong> Technology<br />

Figure 5<br />

Artists Rendition <strong>of</strong> 10MW/100MWh Regenesys <strong>Energy</strong> <strong>St<strong>or</strong>age</strong> Plant<br />

Regenesys cell stacks consist <strong>of</strong> bipolar electrode plates spaced and held by insulating polymer<br />

frames, see Figure 2, above. These frames also serve to manifold and distribute the electrolyte<br />

into the cell <strong>com</strong>partments, which are separated by pieces <strong>of</strong> membrane material. Innogy uses a<br />

proprietary sealing arrangement between the frames to prevent electrolyte leakage between cell<br />

<strong>com</strong>partments and out <strong>of</strong> the stack. As can be seen in Figure 4, the frames holding the electrodes<br />

and the membranes are held together with thick end plates and tie bars, items which are not used<br />

in the United States by Powercell <strong>or</strong> ZBB, developers <strong>of</strong> zinc/bromine battery technologies. In<br />

the Innogy approach to a 12MW Regenesys plant, 1200 cell-stacks (100kW each) are arranged in<br />

a parallel and series array <strong>f<strong>or</strong></strong> a plant DC voltage <strong>of</strong> ~3000V. Shunt currents can flow in the<br />

hydraulically-parallel flow channels <strong>of</strong> cells in electrical series, with these shunt currents being<br />

limited in all flow batteries by using flow channels that are long enough and narrow enough to<br />

provide an effective limiting resistance. However, extra pumping power losses are thereby<br />

introduced that must be balanced with the reduction in shunt current losses than can be effected.<br />

Shunt current and pumping power losses are thus limited to 5-10% in Regenesys ES plants by<br />

suitable arrangements in the plumbing from the two electrolyte tanks to the individual cells <strong>of</strong><br />

the cell-stacks.<br />

Plant-wide tanks, rather than modularized units, were used in the design <strong>f<strong>or</strong></strong> a variety <strong>of</strong> reasons,<br />

including the necessity to remove, via a processing unit based on conventional chemical<br />

engineering technology, the sodium sulfate that builds up at a rate <strong>of</strong> 250-300lbs per day (<strong>f<strong>or</strong></strong> a<br />

12MW plant) in the negative electrolyte. Innogy indicates that such considerations also place a<br />

limit, <strong>f<strong>or</strong></strong> the next several years at least, on the minimum size plant that can be economically<br />

considered (nominally 100MWh/10MW).<br />

As a result <strong>of</strong> all the above considerations, the characteristics expected <strong>f<strong>or</strong></strong> 100MWh/10MW<br />

Regenesys plant engineered acc<strong>or</strong>ding to the Innogy design approach are as follows:<br />

Page 7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!