Type [29]: Inverter model (common to entire FUJI inverter system)<br />
The number is fixed to 1213h or 1214h or 1216h for the VG inverters.<br />
200V system: fixed to 1213h<br />
400V system: fixed to 1214h<br />
690V system: fixed to 1216h<br />
Type [31]: Speed<br />
15 8 7 0<br />
Data (0 to ±20,000) → (0 to ±12,000 × r/min) : (Data) × Nmax/20,000 conversion<br />
(Example) When the maximum speed is Nmax=1,500r/min,<br />
• If you want to direct a speed command of 1,000r/min,<br />
1,000<br />
Specify a data of × 20,000 → 13,333.<br />
1,500<br />
• If the read out data is 3,500,<br />
1,500<br />
You can determine the speed is × 3,500 → 262.5r/min.<br />
20,000<br />
Type [32]: Operation commands, [33]: Y1 to Y18<br />
This type is the same as S06 and S07.<br />
15 8 7 0<br />
[32] [33]<br />
0) FWD (forward operation command) Y1<br />
1) REV (reverse operation command) Y2<br />
2) X1 Y3<br />
3) X2 Y4<br />
4) X3 Y5A<br />
5) X4 Not used<br />
6) X5 Not used<br />
7) X6 Not used<br />
8) X7 Y11<br />
9) X8 Y12<br />
10) X9 Y13<br />
11) X11 Y14<br />
12) X12 Y15<br />
13) X13 Y16<br />
14) X14 Y17<br />
15) RST (RESET command) Y18<br />
13-32<br />
0: OFF<br />
1: ON