1.3 Installation - Fixing (continued)<br />

6<br />

Connect Lon (continued)<br />

LonMark<br />

Device<br />

IQL<br />

Lonworks bus<br />

LINC<br />

LINC<br />

IQ Outstations<br />

IQ Outstation<br />

Normal IQ System current loop Lan cable is not<br />

recommended<br />

Do not use screened cable<br />

Cable<br />

Max<br />

bus length<br />

Max node to node<br />

B elden 85102 500<br />

m (545 yds)<br />

500 m (545 yds)<br />

IQ system<br />

TP/1/0/16/HF/200 500<br />

m (545 yds) 400 m (430 yds)<br />

(Belden 8471)<br />

U L Level IV, 22 AWG 500<br />

m (545 yds)<br />

400 m (430 yds)<br />

J Y(St) Y2 x 2 x 0.8 500<br />

m (545 yds)<br />

320 m (350 yds)<br />

TIA5268A Cat. 5,<br />

24 AWG<br />

450<br />

m (490 yds) 250 m (270 yds)<br />

Terminal size 0.5 to 2.5 mm 2 (14 to 20 AWG)<br />

If used with LPT-10 (powered bus), cable lengths differ - see “Link Power Transceiver<br />

User’s Guide (078-0105-01C)”.<br />

Connect Inputs and Outputs<br />

7<br />

If non standard strategy, follow<br />

special installation instructions and<br />

jump to section 2.1 step 14<br />

Non-standard Strategy<br />

Installation Instructions<br />

8<br />

! " #<br />

+ + <br />

+<br />

Connect Inputs<br />

Terminal size 0.5 to<br />

2.55 mm 2 (14 to<br />

20 AWG)<br />

# <br />

<br />

<br />

Sensors TB/TS, TB/TS/K, TB/TS/KE, TB/TS/KEF<br />

recommended; wire as shown below.<br />

9<br />

2<br />

! " #<br />

<br />

+ <br />

+ <br />

! " # $ % &<br />

2 1 3 6 5 4<br />

TE/TS /K /F /E<br />

Room Display Module (RD-IQL/K, /KOS,<br />

/KOSF) provides monitor and control; wired as<br />

shown below:<br />

polarity<br />

independent<br />

Note that the IQL must be<br />

correctly set up to use the<br />

RD-IQL, see section 3 step 15<br />

Note that terminal types COM and<br />

C should not be connected together<br />

Configure/Commission<br />

IQL15+/xxx Installation<br />

Instructions, TG200344 -<br />

Sheet 2<br />

+<br />

"<br />

+<br />

$ %<br />

RD-IQL<br />

<br />

Local<br />

Space<br />

Temperature<br />

Sensor<br />

! " # $ % &<br />

Auto<br />

Local Setpoint<br />

Adjust<br />

Potentiometer<br />

Off<br />

Fan Speed Select<br />

T<br />

Pushbutton<br />

or PIR input<br />

∆T<br />

Window or<br />

Alarm<br />

contact<br />

Pushbutton or PIR<br />

input type selected<br />

by configuration<br />

parameter W6<br />

PIR<br />

PIR<br />

TE/TS<br />

/ <br />

TE/TS/K<br />

/ <br />

TE/TS/KE<br />

/ <br />

TE/TS/KEF<br />

/ <br />

RD/IQL/K<br />

S / / /<br />

RD/IQL/KOS<br />

S / /<br />

RD/IQL/KOSF<br />

S S / /<br />

input included in TB or RD<br />

S separate input may be used<br />

/ Input either cannot be connected, or will be ignored<br />

Connection of separate device to input required