3. Installation - Configuration (continued)<br />

18<br />

Set up IC Comms from IQL<br />

if required<br />

Use IqlTool2 (see section 2.2 step 5) and text communications<br />

IC Comms Module Nx(.. - (x=1 to y; y=4 for standard strategies)<br />

Parameter<br />

Function<br />

A - Remote device address<br />

If zero, 'global to' comms. If non-zero specifies<br />

target device address for 'data to' comms<br />

For 'global to' comms only, attribute of target IQ,<br />

B - Attribute<br />

references attribute in address module (0 'no<br />

attribute', - all IQs on Lan,1 'identifier', 2 'attribute<br />

2', 3 'attribute 3')<br />

N - Remote Lan<br />

Target IQ Lan number; if Lan zero, address zero,<br />

specifies global global<br />

I - Interval<br />

Interval between sending (minutes)<br />

S - Significant change Amount analogue must change before sending<br />

M - Source item string Item and parameter being sent (e.g. S1(V) )<br />

E - Destination module number No. of destination module receiving IC comms<br />

T - Destination type<br />

Type of destn module receiving comms (e.g. W,K)<br />

Lon<br />

LCI<br />

IQL<br />

S1<br />

S8<br />

K1<br />

K2<br />

K8<br />

I1<br />

I8<br />

W1<br />

W7<br />

W8<br />

Nx<br />

Nx<br />

IC Comms<br />

LINC<br />

IQ<br />

19<br />

Set up IC Comms from IQ<br />

if required<br />

IC Comms ‘direction’ in IQ must be:<br />

Global To, Min, Max, Sum, or<br />

Average (directions 2 to 6)<br />

see IQ Configuration<br />

Manual 90-1533<br />

20<br />

Lon<br />

Set up Communications from<br />

Supervisor if required<br />

e.g. 963 (drag and drop values)<br />

Note that standard strategy pages<br />

are available for 963 from<br />

Partnernet<br />

Terse Text Comms<br />

Use SET, PowerTool, or Wupdn and terse text<br />

communications<br />

IQL<br />

S1<br />

LINC<br />

Lon<br />

S8<br />

S1<br />

S16<br />

K1<br />

K8<br />

I1<br />

I16<br />

IQL<br />

A1<br />

A16<br />

A17<br />

A24<br />

B1,0<br />

B2,7<br />

W1 B18,0<br />

W8 B19,7<br />

LINC<br />

Nx<br />

Nx<br />

IQ<br />

IC Comms<br />

K1<br />

K2<br />

K8<br />

I1<br />

I8<br />

W1<br />

W7<br />

W8<br />

Note that any changes to the strategy parameters<br />

should immediately be followed by a write to the<br />

address module, [text comms command, R(z=O),<br />

recommended], to commit changes to flash<br />

memory.<br />

IQ