3. Installation - Configuration (continued)<br />
14<br />
Check Operation - Fan Speed Select<br />
IN3<br />
) K J<br />
BB<br />
OUT1, 2, 3<br />
# <br />
<br />
<br />
If Occupied and Remote Fan Speed (K7) Auto<br />
Fan Speed Switch can be provided by TB/TS/KEF or<br />
RD-IQL/KOSF (see section 1.3 step 8)<br />
Set up Strategy Parameters<br />
15 if required<br />
Use IqlTool2 (see section 2.2 step 5 ) and text<br />
communications<br />
For standard strategies use table below, else refer to<br />
non-standard strategy installation instructions<br />
Parameter<br />
K1(V)<br />
K2(V)<br />
K3(V)<br />
K4(V)<br />
K5(V)<br />
K6(V)<br />
K7(V)<br />
K8(V)<br />
Label<br />
Remote<br />
Setpoint<br />
RemoteSpaceTemp<br />
OCC Deadbnd<br />
Standby<br />
Deadbnd<br />
NOCC Deadbnd<br />
Remote<br />
Occ<br />
Remote<br />
Fan Spd<br />
Remote<br />
SP Offset<br />
Function<br />
Base<br />
setpoint can be adjusted remotely<br />
Used<br />
if bound to Lon sensor, or if local sensor disconnected<br />
Deadband<br />
around setpoint during Occ<br />
Deadband<br />
around setpoint during Standby<br />
Deadband<br />
around setpoint during Nocc<br />
Sets<br />
state 0=Occ, 1=Nocc, 2=Bypass, 3=Standby<br />
Sets<br />
speed 0=off, 1=Low, 2=Med, 3=High, 4=Auto<br />
Used<br />
if bound to a Lon Sensor or if local adjust is disconnected<br />
20 ° C<br />
20 ° C<br />
1 ° C<br />
2 ° C<br />
12 ° C<br />
Default<br />
0=Occupied<br />
4=Auto<br />
0 ° C<br />
K15(V)<br />
W2(S)<br />
W3(S)<br />
O ffset range<br />
Defines<br />
range of Local SP adjust pot.<br />
S ummer Mode<br />
Winter<br />
(heat only) or Summer (cool only) (only used for /WR2, /WT2)<br />
Elec<br />
Disable<br />
Disable<br />
Electric Heater if set to I<br />
2 ° C<br />
O=Winter<br />
O=enable Elec<br />
W5(S)<br />
W6(S)<br />
W7(S)<br />
W8(S)<br />
L1(G)<br />
L1(I)<br />
L2(G)<br />
L2(I)<br />
Window mode<br />
O=Pb<br />
I=PIR<br />
Frost<br />
Condition<br />
Remote<br />
Shutdown<br />
Window contact if set to I, alarm contact if set to O<br />
PIR if set to I, Pushbutton if set to O<br />
Overrides<br />
heating to 98 % (not /AR2) if unoccupied<br />
Shuts<br />
off fan, and sets heat/cool to zero<br />
Heat<br />
Loop Gain<br />
40<br />
Heat<br />
Loop Integral<br />
Cool<br />
Loop Gain<br />
-40<br />
Cool<br />
Loop Integral<br />
O=alarm contact<br />
O=pushbutton<br />
O=no frost<br />
O=no shutdown<br />
0 mins<br />
0 mins<br />
Note that any changes to the strategy parameters should immediately be followed by a write to the address<br />
module, [text comms command, R(z=O), recommended], to commit changes to flash memory.<br />
If used with RD-IQL (see section 1.3 step 8), the following must be configured: Local Space Temp Type<br />
S9(Y=6), Local SP Adjust Type S10(Y=6), Local Fan Speed Type S11(Y=6), O=Pb I=PIR W6(S=O)<br />
default, Remote Fan Spd K7(V=4) default, followed by R(z=I) to write changes to flash and reset.<br />
Configuration for RD-IQL is facilitated by IqlTool2.<br />
If the sensor on IN1 is to be used, leave local Space Temp Type at default, S9(Y=1). If the fan speed<br />
switch on IN3 is to be used, leave Local Fan Speed type at default, S11 (Y=3).<br />
If required the strategy type may be changed (e.g. /AR2 to /WR2) but<br />
a /E strategy cannot be changed to a /AUX strategy or vice versa:<br />
IQL15+/xxx data<br />
sheet TA200367