<strong>KH</strong>-<strong>10</strong><br />

<strong>KH</strong>-<strong>20</strong><br />

<strong>Duct</strong> <strong>hygrostats</strong><br />

Summary<br />

Mechanical air duct <strong>hygrostats</strong> for monitoring, control and limitation of<br />

relative humidity in HVAC units – air ducts, air handling units, greenhouses<br />

etc.<br />

Applications<br />

<br />

HVAC control systems – humidity limitation, humidity control etc.<br />

Function<br />

Change of relative humidity above the preset value actuates a potential-free contact<br />

which is brought to the output terminals. The setpoint value is set by a knob outside<br />

of the housing. The „-U“ types provide internal setpoint knob. The device is purely<br />

mechanical and needs no external power supply.<br />

Technical data<br />

Contact load<br />

Contact<br />

Cover<br />

Ambient temperature<br />

Dimensions of the housing<br />

Pocket length<br />

Protection degree<br />

15 (8) A, 24...250 V AC, min. 150 mA<br />

dustproof contact block, single potentialfree<br />

switching contact<br />

Polyamide reinforced with glass fibre<br />

(30 %), white colour<br />

-<strong>10</strong>...65°C<br />

<strong>10</strong>8 x 72.5 x 70 mm<br />

<strong>20</strong>0 mm<br />

IP65<br />

Electrical terminals screw terminals, for wires 0.14 .. 1.5 mm 2<br />

Hysteresis<br />

Setpoint range<br />

Max. air velocity<br />

4 % rH<br />

35 ... <strong>10</strong>0 % rH<br />

8 m/s<br />

domat <strong>KH</strong> 1


Types<br />

Hygrostats are delivered in following variants:<br />

Type<br />

Range<br />

(% rH)<br />

Difference<br />

between the<br />

stages<br />

(% rH)<br />

Stages<br />

Setpoint<br />

<strong>KH</strong>-<strong>10</strong> 35 ... <strong>10</strong>0 - 1 External<br />

<strong>KH</strong>-<strong>10</strong>U 35 ... <strong>10</strong>0 - 1 Internal<br />

<strong>KH</strong>-<strong>20</strong> 35 ... <strong>10</strong>0 3 ... 18 2 External<br />

<strong>KH</strong>-<strong>20</strong>U 35 ... <strong>10</strong>0 3 ... 18 2 Internal<br />

Terminals<br />

Terminal connection:<br />

1 – 4 : humidification<br />

1 – 2 : dehumidification<br />

FX: measured relative humidity<br />

FW: set relative humidity (setpoint) on the knob<br />

DX: difference between stage 1 and stage 2<br />

Internal settings<br />

The ..U types have the setpoint knob inside of the housing to prevent unauthorised<br />

operation.<br />

2 domat <strong>KH</strong>


Dimensions<br />

05/<strong>20</strong>09 Subject to technical changes.<br />