Heavy Duty Balanced Opposed Compressors - Ariel Corporation
Heavy Duty Balanced Opposed Compressors - Ariel Corporation
Heavy Duty Balanced Opposed Compressors - Ariel Corporation
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
FOR MODELS: JGZ AND JGU SECTION 4 LUBRICATION<br />
switch will be open until the button is pushed and the contact will close. If a momentary push<br />
button switch is NC then when it is taken out of the box the switch will be closed until the<br />
button is pushed.) This does not apply to divider block monitoring devices.<br />
Divider block device manufacturers have "simplified" things for the mechanic. Normally<br />
Open (NO) refers to the state the switch is in when the divider block is cycling or the unit is<br />
running. An NO switch means that when the unit is running the shutdown switch is open or<br />
non-failsafe. If a wire falls off or is cut while the unit is running the control system will never<br />
stop the unit. If the device is damaged or a wire has come loose at startup the control system<br />
would never know there is a problem. An NC switch means that when the unit is running<br />
the shutdown switch is closed or failsafe. Now if a wire falls off or is cut the control system<br />
will detect that the switch is open and shutdown the unit.<br />
<strong>Ariel</strong> recommends using a NC (failsafe) switch. However, when a NO (non-failsafe) switch<br />
is used, <strong>Ariel</strong> recommends testing the shutdown circuits at least once a month.<br />
II. Proximity switch - This is a device that will sense the position of the divider block piston<br />
and will produce a switch change of state or a pulse every time the pin changes position. This<br />
device must be combined with a PLC or some other counter/timer device to produce the shutdown.<br />
Some devices on the market will open the switch when the pin is toward the left and<br />
close when the pin is toward the right. Others will produce a 0.5 second pulse when the pin<br />
moves from left to right. If this is used it is the responsibility of the control system to sense the<br />
switch cycling and stop the unit if a block stops cycling.<br />
APPLICATION NOTES - Proximity Switch<br />
<strong>Ariel</strong> recommends setting up the control system to find the time between cycles triggered<br />
when the switch transitions from off to on. See Figure 4-7 suggested control system block<br />
diagram.<br />
1. Shutdown time with no lubrication - The distribution block cycle times will vary<br />
slightly from cycle to cycle. Seeing 12 seconds one cycle then 15 seconds the<br />
next then 14 the next is normal. The recommended shutdown time is: 2 times the<br />
design cycle time + 30 seconds limited between 30 seconds and 3 minutes.<br />
LIMIT (2 x design cycle time + 30 seconds) 30, 180<br />
Design cycle time is found on the compressor lube sheets or tag on the compressor.<br />
2. DE-BOUNCE and latching circuits - Depending on the device and control system<br />
scan time it may be necessary to include de-bounce hardware and/or software.<br />
Some of the devices do not have built in de-bounce circuits and can cause a fast<br />
control system to double or triple count. Other times it may be necessary to latch<br />
the input thus allowing the control system to detect only the first transition from<br />
low to high. This becomes significant when displaying the cycle time for the operator<br />
to set the pump flow rates and when calculating the total oil through the<br />
divider block.<br />
3. Suggested Operator Displays:<br />
Divider block cycle time - The operator will need to set the lube system pumps according<br />
to the recommended divider block cycle times. It is helpful for the operator<br />
to have a display of divider block cycle time in seconds. This will be used to adjust<br />
the lube pumps as the pumps wear out and when the pumps are replaced to set<br />
divider block cycle times.<br />
PAGE 4 - 22 7/09