Heavy Duty Balanced Opposed Compressors - Ariel Corporation
Heavy Duty Balanced Opposed Compressors - Ariel Corporation
Heavy Duty Balanced Opposed Compressors - Ariel Corporation
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
FOR MODELS: JGZ AND JGU SECTION 4 LUBRICATION<br />
ratings of <strong>Ariel</strong> filters. For this reason, <strong>Ariel</strong> does not recommend after market filters. Exercise<br />
caution if an after market filter is installed. Do not use a by-pass type filter.<br />
Pressure gauges are provided for monitoring pressure drop across the filter. Differential pressure<br />
is the primary indication of a plugged filter.<br />
Compressor Prelube Pump<br />
An automated compressor pre-lube system is strongly recommended for all <strong>Ariel</strong> compressors<br />
to extend bearing life and reduce operating costs. <strong>Compressors</strong> that meet any of the following<br />
criteria are required to have an automated pre-lube system to provide oil flow prior to start-up:<br />
1. Electric motor driven compressors.<br />
2. Unattended-start compressors, regardless of driver type.<br />
3. All large frame compressor models (JGC, JGD, JGZ, JGU, JGB, JGV, KBB and KBV).<br />
Automated compressor pre-lube systems must be designed and sized to provide 10 psig (0.7<br />
bar g ) minimum pressure for a minimum of 30 seconds prior to starting, at the inlet to the oil<br />
gallery (after the filter), with minimum start-up oil viscosity and maximum allowable filter differential<br />
pressure. It is suggested that the prelube pump be sized at approximately 25% of the<br />
frame oil pump capacity. Reference Technical Manual, Section 1, Frame Specification Tables<br />
for frame oil pump flow rates, or see the Electronic Databook in the <strong>Ariel</strong> Performance Program.<br />
The purpose is to be sure there is oil flow to all bearings and bushings, and the clearances<br />
are filled with oil prior to start-up. A start permissive is desirable to sense for minimum<br />
required pressure/time at the inlet to the oil gallery.<br />
Automated systems are to provide for shutdown if 35 psig (2.4 bar g ) oil pressure is not<br />
achieved within 10 seconds after the initiation of start-up (from when crankshaft starts to turn).<br />
If a compressor will not start or shuts down at start-up due to low oil pressure, do not<br />
attempt to re-start until the cause of low pressure is corrected.<br />
Engine driven compressors with manual pre-lube pumps are to be adequately pre-lubed prior<br />
to starting. If 35 psig (2.4 bar g ) oil pressure is not achieved within 10 seconds after reaching<br />
engine idle speed, shutdown the compressor and correct the cause. Repeat manual pre-lube<br />
prior to each cranking for start-up.<br />
Pre-lube pumps are to be located prior to the oil filter. When oil pressure exceeds 35 psig (2.4<br />
bar g ) at start-up, a low oil pressure shutdown set at 35 psig (2.4 bar g ) must be active for all<br />
compressors.<br />
Oil Heaters<br />
Frame oil heaters may be needed if the compressor must be started in cold weather applications.<br />
Depending on the operational aspects of the compressor, one possible heating mode is<br />
to maintain the temperature in the compressor frame to a minimum temperature so that the<br />
compressor can be started immediately if needed, see Table 4-1. Another mode is to heat the<br />
oil from ambient to a minimum temperature prior to starting, see Table 4-2. The specific application<br />
requirements will determine which heating mode is necessary.<br />
Circulation type heaters are recommended. All compressor models have at least one connection<br />
for a heater. Four and Six throw frames have two locations. The maximum allowable wattage<br />
per unit area for an immersion heater is 15 W/in 2 (2.3 W/cm 2 ). This limit will prevent oil<br />
7/09 PAGE 4 - 9