FOR MODELS: JGZ AND JGU SECTION 4 LUBRICATION<br />
2. Days of over and under lubrication.<br />
3. Total oil consumption of compressor lube system<br />
4. Daily and total lost dollars (US) for over lubricating.<br />
5. Total divider block cycles,<br />
6. Total run time of the compressor.<br />
The Proflo PF1 monitor can store one year’s worth of operating data in a first in, first out (FIFO)<br />
memory.<br />
The FFT software can be used to reset Proflo PF1 memory. The reset time and date is recorded<br />
to the Proflo PF1's Electrical Erasable Programmable Read Only Memory, (EEPROM).<br />
To start the download push the SET button then push the mode button 5 times until the LCD<br />
displays SEND DATA? then push the SET button. Set the FFT software to accept the Proflo<br />
PF1 data and hold the handheld computer in a position to communicate with the IrDA port. The<br />
LCD will display SENDING. If there is no devise to receive the data the LCD will display FAIL-<br />
URE and after 30 seconds return to LAST and AVG default display.<br />
The software provides for conversion to Microsoft Excel files for trending and graphing.<br />
Hand held Palm operating system computers are available at most electronic or discount<br />
stores or on the Internet.<br />
For more details on this product and other Proflo PF1 accessories, see the <strong>Ariel</strong> web at<br />
www.arielcorp.com and/or contact your packager or <strong>Ariel</strong>.<br />
Proflo PF1 Setup Alarm Time and Mode:<br />
To setup the Alarm contact output operation, red wires, first push the SET button. Push mode<br />
button six (6) times until LCD displays SETUP?. Push SET button and the LCD will scroll to 1.<br />
SET ALARM TIME. Push and release set button to change alarm-shutdown from 30 to 240<br />
seconds. When the compressors leave <strong>Ariel</strong> this time is set to 120 seconds. <strong>Ariel</strong> recommends<br />
setting the alarm time to 2 times the normal cycle time rounded up to the nearest<br />
5 seconds. This time should not be less than 30 seconds or greater than 180 seconds.<br />
Normal design cycle time can be found on a nameplate on the lube oil pump box.<br />
The control system must be configured to shutdown the compressor for a no-flow indication.<br />
Push the mode button, two (2) more times and the LCD will scroll to SET ALARM MODE. Push<br />
set button to toggle from N/O normally open or N/C normally closed. <strong>Ariel</strong> recommends using<br />
the NC operation.<br />
After wiring mode is set the monitor will automatically return to the LAST and AVG display in<br />
30 seconds.<br />