3.13.2 Electro-Magnetic Compatibility (EMC)<br />
The TMR system has been designed and tested to withstand normal levels of<br />
conducted and radiated electromagnetic interference and electrostatic discharge.<br />
Electrical noise conditions may vary greatly, depending on the equipment<br />
installation, wiring, other installed equipment, and its proximity to the TMR<br />
equipment. A detailed analysis of the installation electrical and magnetic conditions<br />
is rare. It is therefore necessary to ensure that the system as a whole <strong>com</strong>plies<br />
with the client’s requirements or appropriate standards; within Europe, the CE mark<br />
requirements form a legal minimum. For systems for applications outside Europe it<br />
is re<strong>com</strong>mended that at least the same measures be applied, and confirmation<br />
sought from the client or end-user that electromagnetic interference (EMI) levels<br />
shall not exceed of those shown in Table 9.<br />
Parameter Conditions Notes<br />
Electrostatic<br />
Discharge<br />
Electromagnetic<br />
Field<br />
Conducted Noise/<br />
Fast Transient<br />
Immunity Test<br />
(Burst)<br />
15kV air discharge<br />
8kV contact discharge<br />
10V/m<br />
23MHz to 1GHz<br />
2kV test voltage – power<br />
supplies<br />
1kV test voltage – digital I/O (‡<br />
24V)<br />
0.25kV test voltage – digital<br />
(