<strong>SAFETY</strong> <strong>MANUAL</strong><br />

shall be provided for at least two transmission paths to the power supply, such<br />

that a short circuit or an interruption in one does not affect the other.<br />

[EN54 section 7.12 Co-incidence detection (option with requirements)<br />

Following the receipt of a signal from a fire detector, and until one or more<br />

confirmatory signals are received from the same or other points, the c.i.e.<br />

may have provision to inhibit either the indication of the fire alarm<br />

condition, or the operation of outputs to<br />

- fire alarm devices (item C of figure 1 of EN 54-1), and/or;<br />

- fire alarm routing equipment (item E of figure 1 of EN 54-1), and/or;<br />

- fire protection equipment (item G of figure 1 of EN 54-1) .<br />

In these cases at least the following shall apply:<br />

a) it shall be possible to select the feature at access level 3 for individual<br />

zones;<br />

b) the inhibition of one output signal shall not affect the actioning of other<br />

outputs.]<br />

[EN54 section 7.11, Delays to outputs (option with requirements - see also 9.4.2.c)<br />

and annex E)<br />

The control and indicating may have provision to delay the actioning of<br />

outputs to fire alarm devices (item C of figure 1 of EN 54-1) and/or to fire<br />

alarm routing equipment (item E of figure 1 of EN 54-1). In these cases at<br />

least the following shall apply:<br />

a) the operation of delays to outputs to C shall be selectable at<br />

access level 3 to apply to<br />

- fire detectors, and/or;<br />

- manual call points, and/or;<br />

- signals from specific zones;<br />

b) the operation of delays to outputs to E shall be selectable at<br />

access level 3, to apply to<br />

- fire detectors, and/or;<br />

- signals from specific zones.<br />

c) the delay times shall be configurable at access level 3, in increments not<br />

exceeding 1 minute, up to a maximum of 10 minutes;<br />

d) it shall be possible to override the delays and immediately action<br />

delayed outputs by means of a manual operation at access level 1<br />

and/or by means of a signal from a manual call point;<br />

e) the delay to one output signal shall not affect the actioning of other<br />

outputs.]<br />