<strong>SAFETY</strong> <strong>MANUAL</strong><br />
Digital Inputs<br />
8403, Triplicated, 24<br />
VDC<br />
8423, Triplicated,<br />
120VDC<br />
Digital Inputs<br />
8402, Dual,<br />
24 VDC<br />
Analog Inputs<br />
8431, Triplicated<br />
8433, Triplicated,<br />
isolated<br />
Analog Inputs<br />
8432, Dual<br />
TÜV Certified<br />
Configuration<br />
Internal 2oo3<br />
(2oo3 implemented in<br />
a single module)<br />
Internal 1oo2D<br />
(1oo2 implemented in<br />
a single module)<br />
Internal 2oo3<br />
(2oo3 implemented in<br />
a single module)<br />
Internal 1oo2D<br />
(1oo2 implemented in<br />
a single module)<br />
Conditions<br />
Normally energized (de-energize to trip): certified<br />
SIL 3 or AK6.<br />
Normally de-energized (energize to trip): certified<br />
only for applications that fulfil the requirements<br />
under section 3.2.4.<br />
Normally energized (de-energize to trip): certified<br />
SIL 3 or AK6.<br />
Normally de-energized (energize to trip): certified<br />
only for applications that fulfil the requirements<br />
under section 3.2.4.<br />
Time-limited operation in degraded mode<br />
Within the manufactures specified safety accuracy<br />
limits. The safety state of the analogue input has to<br />
be defined to 0 mA/0 V<br />
Certified SIL 3 or AK6.<br />
Within the manufactures specified safety accuracy<br />
limits. The safety state of the analogue input has to<br />
be defined to 0 mA/0 V<br />
Time-limited operation in degraded mode.<br />
Certified: SIL 3 or AK6<br />
Table 2 - Input Modules High Density I/O<br />
Digital Outputs<br />
8451, Triplicated 24<br />
VDC<br />
8471, Triplicated<br />
120VDC<br />
8461, Triplicated<br />
48VDC<br />
Analog Outputs<br />
8480 Analog Output<br />
4-20 mA<br />
TÜV Certified<br />
Configuration<br />
Internal 2oo3<br />
(2oo3 implemented in<br />
a single module)<br />
Not safety related but<br />
interference free<br />
Conditions<br />
Normally energized (de-energize to trip): certified<br />
SIL 3 or AK6.<br />
Normally de-energized (energize to trip): certified<br />
only for applications that fulfil the requirements<br />
under section 3.2.4.<br />
May be used in single module or master/slave<br />
configurations.<br />
Certified as non-interfering and can be used for nonsafety-critical<br />
output devices.<br />
Table 3 - Output Modules High Density I/O<br />
Doc Number P8094<br />
Issue 14 September 2003 Page 39 of 67