Catalog - Radix.co.in
Catalog - Radix.co.in
Catalog - Radix.co.in
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Multi-channel Data Logger<br />
ISOLOG<br />
Memory for 11000+ re<strong>co</strong>rds<br />
(x16 channels) for 9 days logg<strong>in</strong>g<br />
Universal Input : RTD,<br />
Thermo<strong>co</strong>uple, 4~20 mA, etc<br />
Sophisticated SCADA-like Utility -<br />
free with ISOLOG<br />
Isolog Utility<br />
Datalogger<br />
• Upto 16 <strong>in</strong>puts, 16 outputs<br />
• Universal Input : 8 Thermo<strong>co</strong>uples, Pt100, mV or<br />
mA <strong>in</strong>put front panel selection without DIP for<br />
each channel<br />
• RS485 with MODBUS RTU<br />
Datalogg<strong>in</strong>g<br />
• Process Value, Alarm and Time Stamp Logg<strong>in</strong>g<br />
• Memory for 11000+ re<strong>co</strong>rds for <strong>co</strong>nt<strong>in</strong>uous<br />
periodic logg<strong>in</strong>g over 9 days<br />
• Memory for 5000+ re<strong>co</strong>rds for event logg<strong>in</strong>g<br />
• Programmable logg<strong>in</strong>g <strong>in</strong>terval<br />
• Onl<strong>in</strong>e and offl<strong>in</strong>e datalogg<strong>in</strong>g<br />
• Sophisticated SCADA-like Utility software for data<br />
retrieval, view<strong>in</strong>g, etc.<br />
• Full datalogg<strong>in</strong>g <strong>co</strong>ntrol through Utility<br />
• 2-level security for Utility<br />
www.radix.<strong>co</strong>.<strong>in</strong>/isolog.html<br />
CAT#382R2/P1/4/300612/A
Multi-channel Data Logger<br />
ISOLOG<br />
GROUPING / COMMON ALARM<br />
VERSIONS 2.XX<br />
Fig 1<br />
GROUP1<br />
GROUP2 GROUP3 GROUP16<br />
CH2 CH7 CH8 CH9 CH11<br />
Upto 16 channels<br />
Upto 16<br />
setpo<strong>in</strong>ts<br />
SP2 SP7 SP8<br />
RLY2 RLY7 RLY8<br />
Maximum No.<br />
Channels<br />
Groups<br />
Channels <strong>in</strong> a group<br />
Setpo<strong>in</strong>ts <strong>in</strong> a group<br />
Setpo<strong>in</strong>ts <strong>in</strong> all<br />
Relays<br />
16<br />
16<br />
16<br />
16<br />
16<br />
16<br />
Note : Any channel can be selected <strong>in</strong> several groups. Upto 16 groups can be made.<br />
Example<br />
• No. of <strong>in</strong>puts : 16 • Input type / unit / resolution : See Table 2<br />
• No. of groups : 16 • No. of relays : 16<br />
• Channels / relays / relay logic <strong>in</strong> each group : See Table 1<br />
• While group<strong>in</strong>g any channel, unit & display resolution of that channel &<br />
group level should be same.<br />
TABLE 1<br />
Group No. Channels Selected Setpo<strong>in</strong>t Selected Relay No.<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2<br />
1<br />
2, 7, 8, 9, 11<br />
8, 9, 11, 13<br />
1, 4, 6<br />
4, 5, 6<br />
10, 12<br />
3, 14, 15, 16<br />
14, 16<br />
2, 7, 8<br />
1, 9, 11<br />
3<br />
4<br />
5, 6<br />
10, 12<br />
13, 15<br />
2, 7, 8<br />
1, 9, 11<br />
3<br />
4<br />
5, 6<br />
10, 12<br />
13, 15<br />
2<br />
3, 14<br />
14, 16<br />
14, 16<br />
TABLE 2<br />
Channel No. Input type Unit<br />
Resolution<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
9<br />
10<br />
11<br />
12<br />
13<br />
14<br />
15<br />
16<br />
TC B<br />
TC E<br />
TC J<br />
TC K<br />
TC N<br />
TC R<br />
TC S<br />
TC T<br />
Pt100<br />
LIN V (0~50 mV)<br />
0~20 mA<br />
4~20 mA<br />
Pt100<br />
TC N<br />
TC J<br />
TC K<br />
°C<br />
°F<br />
°K<br />
°C<br />
°C<br />
°C<br />
°F<br />
°F<br />
°F<br />
BAR<br />
°F<br />
BAR<br />
°F<br />
°K<br />
°K<br />
°K<br />
0.1<br />
1<br />
0.1<br />
0.1<br />
0.1<br />
0.1<br />
1<br />
1<br />
1<br />
0.001<br />
1<br />
0.001<br />
1<br />
0.1<br />
0.1<br />
0.1<br />
DIAGRAM 1<br />
CONTROL FUNCTIONS<br />
ON<br />
OFF<br />
HIGH ALARM<br />
LOW ALARM<br />
SP<br />
HYST<br />
SP<br />
HYST<br />
TABLE 3<br />
SENSOR / INPUT<br />
Pt - 6% Rh / Pt - 30% RH (B)<br />
RANGE LIMITS<br />
(°C / EU)<br />
LOW SCALE HIGH SCALE<br />
400<br />
1820<br />
RANGE IN WHICH<br />
ACCURACY IS SPECIFIED<br />
LOW SCALE HIGH SCALE<br />
400<br />
1820<br />
TYPICAL ACCURACY<br />
AT 30 °C<br />
(°C / EU)<br />
± 3<br />
WORST CASE<br />
ACCURACY<br />
(°C / EU)<br />
± 5<br />
Chromel / Constantan (E)<br />
-270<br />
1000<br />
0<br />
1000<br />
± 1<br />
± 3<br />
Iron / Constantan (J)<br />
-210<br />
760<br />
0<br />
760<br />
± 1<br />
± 3<br />
Chromel / Alumel (K)<br />
-270<br />
1372<br />
-50<br />
1200<br />
± 1<br />
± 3<br />
Nicrosil / Nisil (N)<br />
-270<br />
1300<br />
-50<br />
1200<br />
± 1<br />
± 3<br />
Pt / Pt - 13% Rh (R)<br />
0<br />
1760<br />
0<br />
1760<br />
± 2<br />
± 5<br />
Pt / Pt - 10% Rh (S)<br />
0<br />
1760<br />
0<br />
1760<br />
± 2<br />
± 5<br />
Copper / Constantan (T)<br />
-270<br />
400<br />
-200<br />
400<br />
± 1<br />
± 3<br />
Pt100, 3-wire<br />
-200<br />
850<br />
-200<br />
850<br />
± 0.5<br />
± 2.0<br />
L<strong>in</strong>ear (0~50 mV, 0~20 mA, 4~20 mA)<br />
-19999<br />
19999<br />
-19999<br />
19999<br />
± 5 EU<br />
± 20 EU<br />
www.radix.<strong>co</strong>.<strong>in</strong>/isolog.html<br />
CAT#382R2/P2/4/300612/A
Multi-channel Data Logger<br />
ISOLOG<br />
Specifications<br />
Specifications & features are subject to change without notice.<br />
INPUTS<br />
Maximum no. of channels (X) 16<br />
Input types<br />
Thermo<strong>co</strong>uple<br />
B, E, J, K, N, R, S, T<br />
RTD<br />
Pt100, 3-wire<br />
L<strong>in</strong>ear <strong>in</strong>put<br />
0~50 mV, 0~20 mA, 4~20 mA<br />
(each <strong>in</strong>put <strong>in</strong>dependently scaleable<br />
and without any DIP re<strong>co</strong>nfiguration)<br />
Channel scan rate<br />
< 1.6 se<strong>co</strong>nds for 16 channels<br />
Channel-to-channel isolation Suitable for low (leakage) voltages<br />
less than 3V AC<br />
Input protection<br />
Thermo<strong>co</strong>uple, mV,<br />
± 10 V DC max<br />
RTD <strong>in</strong>puts<br />
Current <strong>in</strong>puts<br />
Current limit < 30 mA, 28 V DC max<br />
Range limits See Table 3<br />
Accuracy See Table 3<br />
Cold junction <strong>co</strong>mpensation Automatic<br />
Sensor break protection User programmable<br />
CONTROL<br />
Control functions<br />
(Diagram 1)<br />
Alarm functions High alarm<br />
Low alarm<br />
Control action<br />
Direct / reverse<br />
Hysteresis<br />
0.1 - 99.9 °C / °F / EU<br />
Alarm type<br />
Autoreset, Latch, Hold, Latch + Hold<br />
Latch (Ltch) Once relay gets ON, it rema<strong>in</strong>s 'ON'<br />
until alarm is acknowledged bykey.<br />
Hold Alarm is disabled at power ON.<br />
After process variable reaches<br />
normal (non alarm) value, the alarm<br />
is enabled.<br />
Ltch.Hold Comb<strong>in</strong>ation of Latch & Hold logic.<br />
OUTPUTS<br />
Maximum no. of outputs (Y)<br />
Output type<br />
Relay <strong>co</strong>ntact type<br />
Relay <strong>co</strong>ntact rat<strong>in</strong>g<br />
ADJUSTMENTS<br />
Setpo<strong>in</strong>t<br />
Alarm<br />
Unit<br />
Resolution<br />
OTHER MAJOR<br />
PARAMETERS<br />
Setpo<strong>in</strong>t lock<br />
Level lock<br />
Display scan rate<br />
SKIP channel<br />
16 (8 <strong>in</strong>built, 8 <strong>in</strong> external relay unit)<br />
a) Electromagnetic relay<br />
b) SSR drive<br />
NO-C<br />
5A / 230V AC, resistive<br />
Full range adjustable<br />
Full range adjustable<br />
User selectable<br />
User selectable<br />
0.0001,0.001,0.01, 0.1or 1 for<br />
l<strong>in</strong>ear <strong>in</strong>put, 0.1 or 1 for temperature<br />
Yes/No<br />
Yes/No<br />
1~99 se<strong>co</strong>nds/channel<br />
Enable/disable<br />
COMMUNICATION<br />
Port<br />
RS485, isolated<br />
Baud rate<br />
4800/9600/19200/38400 bps<br />
Proto<strong>co</strong>l<br />
Modbus RTU<br />
Slave ID User programmable, 1~255<br />
Datatype<br />
Float, Swapped float, Integer<br />
Integer x10<br />
M<strong>in</strong>imum poll<strong>in</strong>g <strong>in</strong>terval 250 millise<strong>co</strong>nds<br />
Parameters<br />
Process variables<br />
Read only<br />
Setpo<strong>in</strong>ts<br />
Read & write from the host<br />
<strong>co</strong>mputer<br />
Alarm status<br />
Read only<br />
Relay status<br />
Read only<br />
DATA LOGGING<br />
Process value logg<strong>in</strong>g<br />
Max total re<strong>co</strong>rds 11466<br />
(with logg<strong>in</strong>g <strong>in</strong>terval of 1 m<strong>in</strong>)<br />
Re<strong>co</strong>rd details<br />
16 x PV with real time stamp<br />
Logg<strong>in</strong>g <strong>in</strong>terval<br />
1 to 99 m<strong>in</strong>utes<br />
Alarm logg<strong>in</strong>g<br />
Max total re<strong>co</strong>rds 5460<br />
Re<strong>co</strong>rd details<br />
Alarm status with related PV<br />
details & real time stamp<br />
Logg<strong>in</strong>g <strong>in</strong>terval<br />
Event based<br />
CALIBRATION<br />
Zero & span<br />
display<br />
User calibration<br />
CJC calibration<br />
INDICATION<br />
Display type<br />
EXTERNAL RELAY UNIT<br />
Dimensions<br />
Mount<strong>in</strong>g<br />
Through front panel keys &<br />
Sensor span and sensor zero<br />
Room temperature<br />
0.56” (15 mm), 7 - segment LED<br />
and 2x16 character LCD display<br />
Process variable<br />
Upper, 4 ½ digit, LED display<br />
Setpo<strong>in</strong>t<br />
Middle, 4 ½ digit, LED display<br />
Channel no.<br />
Lower, 2 digit, LED display<br />
Status <strong>in</strong>dication<br />
16 LEDs for alarm, 16 LEDs for<br />
relay status & 2x16 LCD<br />
OTHER<br />
Keypad<br />
Membrane, tactile, 3 keys<br />
Memory for programmed Non-volatile, <strong>in</strong>def<strong>in</strong>ite duration<br />
parameters<br />
Field Connections<br />
Screw type <strong>co</strong>nnections <strong>in</strong> plug-<strong>in</strong><br />
term<strong>in</strong>als<br />
Plug-<strong>in</strong> Term<strong>in</strong>al Type<br />
a) Standard (Brass nickel plated)<br />
b) Gold plated<br />
Supply voltage<br />
a) 85~265 V AC, 50/60 hz<br />
b) 24 V DC supply<br />
Power <strong>co</strong>nsumption<br />
5 watts<br />
Dimensions (<strong>in</strong> mm)<br />
ISOLOG<br />
96(H)x192(W)x220(D)<br />
FLP ISOLOG X8Y8 & below :<br />
420(H)x365(W)x165(D)<br />
X12Y0 & above :<br />
500(H)x365(W)x165(D)<br />
Mount<strong>in</strong>g<br />
ISOLOG<br />
In panel cutout of 90x186 mm<br />
FLP ISO LOG Surface<br />
FLP enclosure<br />
Certified flameproof for<br />
gas groups I, IIA & IIB<br />
Protection (FLP enclosure) IP55<br />
Operat<strong>in</strong>g ambient temperature 0 - 50 °C<br />
Relative humidity<br />
Below 90%, non <strong>co</strong>ndens<strong>in</strong>g<br />
Flameproof<br />
Version<br />
75(H)x100(W)x110(D)<br />
Snap on for 35mm DIN rail to<br />
DIN 46277<br />
www.radix.<strong>co</strong>.<strong>in</strong>/isolog.html<br />
CAT#382R2/P3/4/300612/A
Multi-channel Data Logger<br />
ISOLOG<br />
Isolog Utility : Excel Report<br />
Order<strong>in</strong>g Information<br />
NON-FLAMEPROOF WITH SMPS<br />
Channels Relays Software Version Order Code<br />
8 0 Indicator 2305 0000 0<br />
16 0 Indicator 2305 0100 0<br />
8 4 Group<strong>in</strong>g / Common alarms 2305 1010 0<br />
16 4 Group<strong>in</strong>g / Common alarms 2305 1110 0<br />
8 8 Group<strong>in</strong>g / Common alarms 2305 1020 0<br />
16 8 Group<strong>in</strong>g / Common alarms 2305 1120 0<br />
FLAMEPROOF WITH SMPS<br />
Channels Relays Software Version Order Code<br />
8 0 Indicator 2307 0000 2<br />
16 0 Indicator 2307 0100 2<br />
8 4 Group<strong>in</strong>g / Common alarms 2307 1010 2<br />
16 4 Group<strong>in</strong>g / Common alarms 2307 1110 2<br />
8 8 Group<strong>in</strong>g / Common alarms 2307 1020 2<br />
16 8 Group<strong>in</strong>g / Common alarms 2307 1120 2<br />
Order<strong>in</strong>g Options<br />
The follow<strong>in</strong>g order<strong>in</strong>g options are available on request.<br />
M<strong>in</strong>imum order quantity and/or m<strong>in</strong>imum order value may apply.<br />
Option<br />
1<br />
2<br />
Factors<br />
24 VDC supply voltage<br />
16 relay<br />
www.radix.<strong>co</strong>.<strong>in</strong>/isolog.html<br />
AN ISO 9001:2008 COMPANY<br />
INSTRUMENTS T : + 91 22 42537777 x 701 F : + 91 22 42537700 E : sales@radix.<strong>co</strong>.<strong>in</strong><br />
SENSORS T : + 91 22 42537777 x 732 F : + 91 22 42537700 E : sensors@radix.<strong>co</strong>.<strong>in</strong><br />
GAUGES T : + 91 22 42537777 x 733 F : + 91 22 42537700 E : gauges@radix.<strong>co</strong>.<strong>in</strong><br />
AUTOMATION C : 0-9322405471 C : 0-9324319150 E : automation@radix.<strong>co</strong>.<strong>in</strong><br />
<strong>Radix</strong> Electrosystems Pvt Ltd, B-14, 2nd Floor, Ghanshyam Indl Estate, Veera Desai Road, Andheri (West), Mumbai - 400 053, India<br />
Tel : + 91 22 42537777 · Fax : + 91 22 42537700 · Email : sales@radix.<strong>co</strong>.<strong>in</strong> · www.radix.<strong>co</strong>.<strong>in</strong><br />
www.radix.<strong>co</strong>.<strong>in</strong><br />
CAT#382R2/P4/4/300612/A