a) Mark the values of the maximum axial and lateral movement for 1000 full load cycles, taken from the dimension table, onto the X- and Y-<br />
axis.<br />
maximum axial movement = ± 46 mm<br />
maximum lateral movement = ± 77 mm<br />
b) By connecting these corner points, the movement triangle is obtained (movement limiting line)<br />
c) Mark the requested lateral movement (if the movement distribution is asymmetrical, take the maximum lateral movement part). At the<br />
intersection with the movement limiting line, the maximum permissible axial movement of ± 22 mm can be determined.<br />
So the expansion joint type UFS 6-20, DN 200, allows simultaneous axial movement of ± 22 mm, in addition to the requested lateral movement<br />
of ± 40 mm.<br />
Calculation of the prerestraint<br />
Movement formula:<br />
H = movement = total movement [mm]<br />
Prerestraint formula:<br />
prerestraint<br />
<br />
H<br />
2<br />
H (t<br />
<br />
t<br />
max<br />
e<br />
t<br />
t<br />
min<br />
min<br />
)<br />
<br />
mm<br />
<br />
t min = minimum temperature [°C]<br />
t max = maximum temperature [°C]<br />
t e = installation temperature [°C]<br />
Example<br />
axial movement = ± 22 mm<br />
lateral movement = ± 40 mm<br />
t min = 0 °C<br />
t max = 120 °C<br />
t e = 20 °C<br />
44 44 (20 0)<br />
axial prerestraint = <br />
= 14,67 mm 14.7 mm<br />
2 120 0<br />
80 80 (20 0)<br />
lateral prerestraint = <br />
= 26,67 mm 26.7 mm<br />
2 120 0<br />
4