10.4 Watercharge, flow and quality<br />
To ensure proper operation of the unit, a minimum water volume<br />
is required in the system and the water flow must be within the<br />
operation range as specified in the table.<br />
<strong>SPCA</strong>-<strong>001</strong>-1RSB<br />
<strong>SPCA</strong>-002-1RSB<br />
<strong>SPCA</strong>-002RSB<br />
<strong>SPCA</strong>-003RSB<br />
<strong>SPCA</strong>-004RSB<br />
<strong>SPCA</strong>-005RSB<br />
<strong>SPCA</strong>-006RSB<br />
<strong>SPCA</strong>-007RSB<br />
<strong>SPCA</strong>-<strong>010RSB</strong><br />
Minim um<br />
water<br />
volume (l)<br />
29<br />
35<br />
35<br />
41<br />
61<br />
73<br />
93<br />
112<br />
159<br />
Minim um<br />
water flow<br />
(l/h)<br />
948<br />
1127<br />
1127<br />
1324<br />
1993<br />
2386<br />
3023<br />
3660<br />
5196<br />
Nominal<br />
water flow<br />
(l/h)<br />
997<br />
1187<br />
1187<br />
1393<br />
2098<br />
2511<br />
3182<br />
3853<br />
5469<br />
Maxim um<br />
water flow<br />
(l/h)<br />
1097<br />
1305<br />
1305<br />
1533<br />
2308<br />
2762<br />
3500<br />
4238<br />
6017<br />
Be sure the water quality is in accordance with the specifications<br />
below<br />
NOTES<br />
The above tables are purely<br />
indicative and non binding<br />
Items<br />
Items to be controlled:<br />
PH AT 25 Ô C<br />
∂lectrical conduct (mS/m) at 25 Ô C<br />
Chloride ion (mg CI-/I)<br />
Sulfate ion (mg SO 2/4/I<br />
M-alkalinity (ph 4.8) (mg SO3/I)<br />
Total hardness (mg CaCO3/I )<br />
Calcium hardness (mg CaCO3/I)<br />
Silica ion (mg SiO2/I<br />
Items to be referred to:<br />
Iron (mg Fe/I)<br />
Copper (mg Cu/I)<br />
Sulfide ion (mg S2-/I)<br />
Amonium ion (mg NH+4/I<br />
Remaining chloride (mg CI/I)<br />
Free carbide (mg SO2/I)<br />
Stability index<br />
Circulating<br />
water 20C<br />
Evaporator water<br />
6.8 - 8.0<br />
below 30<br />
below 50<br />
below 50<br />
below 50<br />
below 70<br />
below 50<br />
below 30<br />
below 1.0<br />
below 1.0<br />
Not detectable<br />
below 0.3<br />
below 0.25<br />
below 0.4<br />
-<br />
Supply water<br />
6.8 - 8.0<br />
below 30<br />
below 200<br />
below 50<br />
below 50<br />
below 70<br />
below 50<br />
below 30<br />
below 0.3<br />
below 0.1<br />
Not detectable<br />
below 0.1<br />
below 0.3<br />
below 4.0<br />
-<br />
Circulating<br />
water 20C-60C<br />
7.0 - 8.0<br />
below 30<br />
below 30<br />
below 30<br />
below 50<br />
below 70<br />
below 50<br />
below 30<br />
Heated water<br />
below 1.0<br />
below 1.0<br />
Not detectable<br />
below 0.1<br />
below 0.1<br />
below 0.4<br />
-<br />
Supply water<br />
7.0 - 8.0<br />
below 30<br />
below 30<br />
below 30<br />
below 50<br />
below 70<br />
below 50<br />
below 30<br />
below 0.3<br />
below 1.0<br />
Not detectable<br />
below 0.1<br />
below 0.3<br />
below 4.0<br />
-<br />
Tendency<br />
if out of criteria<br />
corrosion + scale<br />
corrosion + scale<br />
corrosion<br />
corrosion<br />
scale<br />
scale<br />
scale<br />
scale<br />
corrosion + scale<br />
corrosion<br />
corrosion<br />
corrosion<br />
corrosion<br />
corrosion<br />
corrosion + scale<br />
10.5 Operating pressure of the refrigerant<br />
circuit.<br />
It is important to check the high and low pressure of the<br />
refrigerant circuit to ensure the proper operation of the unit and<br />
to guarantee that the rated output will be obtained.<br />
Attention:<br />
The pressures measured will vary between<br />
a maximum and minimum value, depending on the<br />
water and ambient temperatures at the moment<br />
of measurement.<br />
Cooling mode<br />
(region)<br />
low pressure<br />
high pressure<br />
Minim um<br />
(outdoor temp. 15 Ô Nominal<br />
CDB)<br />
(leaving water temp 6 Ô (outdoor temp. 35 Ô Maximum<br />
CDB)<br />
C) (leaving water temp, 7 Ô (outdoor temp. 38 Ô CDB)<br />
C) (leaving water temp, 25 Ô C)<br />
3,5-4 bar<br />
17-19 bar<br />
4-5 bar<br />
21-23 bar<br />
5,5-6 bar<br />
24-26 bar<br />
18<br />
Interklima Hydronic systems<br />
<strong>SPCA</strong> <strong>001</strong>-<strong>010RSB</strong> ñ R407c/Scroll