10.4 Watercharge, flow and quality<br />

To ensure proper operation of the unit, a minimum water volume<br />

is required in the system and the water flow must be within the<br />

operation range as specified in the table.<br />

<strong>SPCA</strong>-<strong>001</strong>-1RSB<br />

<strong>SPCA</strong>-002-1RSB<br />

<strong>SPCA</strong>-002RSB<br />

<strong>SPCA</strong>-003RSB<br />

<strong>SPCA</strong>-004RSB<br />

<strong>SPCA</strong>-005RSB<br />

<strong>SPCA</strong>-006RSB<br />

<strong>SPCA</strong>-007RSB<br />

<strong>SPCA</strong>-<strong>010RSB</strong><br />

Minim um<br />

water<br />

volume (l)<br />

29<br />

35<br />

35<br />

41<br />

61<br />

73<br />

93<br />

112<br />

159<br />

Minim um<br />

water flow<br />

(l/h)<br />

948<br />

1127<br />

1127<br />

1324<br />

1993<br />

2386<br />

3023<br />

3660<br />

5196<br />

Nominal<br />

water flow<br />

(l/h)<br />

997<br />

1187<br />

1187<br />

1393<br />

2098<br />

2511<br />

3182<br />

3853<br />

5469<br />

Maxim um<br />

water flow<br />

(l/h)<br />

1097<br />

1305<br />

1305<br />

1533<br />

2308<br />

2762<br />

3500<br />

4238<br />

6017<br />

Be sure the water quality is in accordance with the specifications<br />

below<br />

NOTES<br />

The above tables are purely<br />

indicative and non binding<br />

Items<br />

Items to be controlled:<br />

PH AT 25 Ô C<br />

∂lectrical conduct (mS/m) at 25 Ô C<br />

Chloride ion (mg CI-/I)<br />

Sulfate ion (mg SO 2/4/I<br />

M-alkalinity (ph 4.8) (mg SO3/I)<br />

Total hardness (mg CaCO3/I )<br />

Calcium hardness (mg CaCO3/I)<br />

Silica ion (mg SiO2/I<br />

Items to be referred to:<br />

Iron (mg Fe/I)<br />

Copper (mg Cu/I)<br />

Sulfide ion (mg S2-/I)<br />

Amonium ion (mg NH+4/I<br />

Remaining chloride (mg CI/I)<br />

Free carbide (mg SO2/I)<br />

Stability index<br />

Circulating<br />

water 20C<br />

Evaporator water<br />

6.8 - 8.0<br />

below 30<br />

below 50<br />

below 50<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

below 1.0<br />

below 1.0<br />

Not detectable<br />

below 0.3<br />

below 0.25<br />

below 0.4<br />

-<br />

Supply water<br />

6.8 - 8.0<br />

below 30<br />

below 200<br />

below 50<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

below 0.3<br />

below 0.1<br />

Not detectable<br />

below 0.1<br />

below 0.3<br />

below 4.0<br />

-<br />

Circulating<br />

water 20C-60C<br />

7.0 - 8.0<br />

below 30<br />

below 30<br />

below 30<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

Heated water<br />

below 1.0<br />

below 1.0<br />

Not detectable<br />

below 0.1<br />

below 0.1<br />

below 0.4<br />

-<br />

Supply water<br />

7.0 - 8.0<br />

below 30<br />

below 30<br />

below 30<br />

below 50<br />

below 70<br />

below 50<br />

below 30<br />

below 0.3<br />

below 1.0<br />

Not detectable<br />

below 0.1<br />

below 0.3<br />

below 4.0<br />

-<br />

Tendency<br />

if out of criteria<br />

corrosion + scale<br />

corrosion + scale<br />

corrosion<br />

corrosion<br />

scale<br />

scale<br />

scale<br />

scale<br />

corrosion + scale<br />

corrosion<br />

corrosion<br />

corrosion<br />

corrosion<br />

corrosion<br />

corrosion + scale<br />

10.5 Operating pressure of the refrigerant<br />

circuit.<br />

It is important to check the high and low pressure of the<br />

refrigerant circuit to ensure the proper operation of the unit and<br />

to guarantee that the rated output will be obtained.<br />

Attention:<br />

The pressures measured will vary between<br />

a maximum and minimum value, depending on the<br />

water and ambient temperatures at the moment<br />

of measurement.<br />

Cooling mode<br />

(region)<br />

low pressure<br />

high pressure<br />

Minim um<br />

(outdoor temp. 15 Ô Nominal<br />

CDB)<br />

(leaving water temp 6 Ô (outdoor temp. 35 Ô Maximum<br />

CDB)<br />

C) (leaving water temp, 7 Ô (outdoor temp. 38 Ô CDB)<br />

C) (leaving water temp, 25 Ô C)<br />

3,5-4 bar<br />

17-19 bar<br />

4-5 bar<br />

21-23 bar<br />

5,5-6 bar<br />

24-26 bar<br />

18<br />

Interklima Hydronic systems<br />

<strong>SPCA</strong> <strong>001</strong>-<strong>010RSB</strong> ñ R407c/Scroll